background image

8

5.  Push ESC button to exit program mode
 

NOTE: If after 60 seconds no button is pressed while in 

Program Mode, the audible alarm sounds for five (5) 

seconds.  Dryer will resume previous operating mode.

6.  Manual Operation

a.  To manually turn the refrigeration system on or off 

use ‘On/Off’ button; Push ‘Schedule On/Off and Enter’ 

button to return to schedule.

  NOTE: After power interruption dryer will reenergize 

in Manual override, refrigeration system off. To restart 

Schedule:  Push ‘Schedule On/Off and Enter’ button. 

B.  

Starting dryer

IMPORTANT: Dryer must be energized 24 hours before starting 

refrigeration compressor.
NOTE: It is recommended that dryer be started 15 minutes 

before compressed air flow begins.
1.   On water-cooled models: after 24 hours, begin cooling 

water flow.

2.  Check for proper electrical voltage.
3.  Slowly pressurize unit air side by opening inlet isolation 

valve. Check for leaks.

4.  After 15 minutes, open outlet isolation valve slowly.
5.  Close air bypass valve.
6.  Dryer may be operated in Manual or Scheduled modes.
NOTE: ON MODELS 500, 600, and 750, CHECK FOR CORRECT 

PHASING OF UNIT.  After starting the dryer, if an unusual 

noise is heard, or if the discharge line does not get hot, the 

refrigeration compressor may be running in the reverse 

direction.  Immediately stop the dryer, reverse two of the power 

leads, restart the dryer, and verify the unusual noise is corrected 

and the refrigerant discharge line is hot.  FAILURE TO DO SO MAY 

DAMAGE THE COMPRESSOR AND VOID THE WARRANTY.
  Manual mode - push On/Off button - refrigeration 

compressor will start and run, green Compressor-on light will 

illuminate.  In this mode compressor will run continuously 

and will not be turned on and off by the monitor. MANUAL 

OVERRIDE will appear on interface panel. 

  Schedule mode - push Schedule On/Off and Enter button.  

SCHEDULE RUNNING will appear on the interface panel. 

The refrigeration compressor will continue to be on or off 

(as  selected  in  the  Manual  Override  Mode)  until  the  next 

scheduled event. The compressor will then turn on or off 

as programmed.

NOTE:  Schedule may be returned to the manual mode at any 

time using the ‘Schedule On/Off and Enter’ button. MANUAL 

OVERRIDE will appear on interface panel. To reinstitute Schedule, 

push the ‘Schedule On/Off and Enter’ button again.
NOTE:  Restart after the power interruption. Unit will be in 

MANUAL OVERRIDE mode, refrigeration compressor, off when 

power is restored after power interruption.
7.   To reinstitute SCHEDULE RUNNING, push ‘Schedule On/Off 

and Enter’ button.

IMPORTANT: Dryer must be energized 24 hours before 

refrigeration compressor is started.

C.  

Operating check points

1.   Check that green Power-on light is illuminated
2.   Check that green Compressor-on light is illuminated if 

dryer is on in the manual mode or it is a scheduled on 

time 

IMPORTANT:  Refrigeration compressor must be restarted after 

power interruption.
3.   Check interface panel
NOTE: Interface panel will scroll through three screens (Current 

Time/Operating Status, Hours to Service and Total Operating 

Hours).

a.  Verify that current time is correct
b.  Check HRS TO SERVICE:  this indicates time remaining 

until service is required; allow time for required 

maintenance items to be ordered

c.   Check operating status:
 

MANUAL OVERRIDE - Dryer is either running continuously 

(not being controlled by the scheduled on/off times) or 

the refrigeration compressor has been shut off using 

the ‘On/Off’ button. 

  SCHEDULE RUNNING - Refrigeration compressor 

is being turned on and off by the monitor per-

programmed schedule (see B.3. to set schedule).

d.  Check Temperature indicator - indicator should read in 

the green area.

e.   Check Alarm/Service light If illuminated, check Interface 

panel.
1)  If SERVICE DRYER appears, scheduled maintenance 

time has elapsed (HRS TO SERVICE is 0). Perform 

needed service and reset service interval (see B.3.).

2)  If ALARM appears, a dryer fault is indicated; see 

Troubleshooting Guide for possible remedies.   After 

fault correction push Reset button to turn Fault 

alarm off.

 

Type of FAULTS:

  LOW PRESSURE - the refrigeration compressor 

control circuit has opened because of  low suction 

pressure.

  HIGH PRESSURE - the refrigeration compressor 

control circuit has opened because of high head 

pressure.  The high pressure switch must be reset 

manually once the fault is corrected. Red reset 

button is located on pressure switch inside unit. 

  HIGH TEMPERATURE - compressed air temperature 

is above the set point.

 

COMPRESSOR - Normally open (NO) auxiliary contact 

on the compressor contactor is open when the dryer 

is on.

 

HEATER - Normally closed (NC) auxiliary contact on 

the compressor contactor is open when the dryer 

is off.

  TEMP SENSOR - Occurs if the temperature sensor 

circuit is open or shorted.  If open, the left-most 

LED in the temperature display will be illuminated.  

If shorted, all the LEDs in the temperature display 

will be illuminated.

  DRAIN - electric drain contains a high water level 

alarm that activates if drain fails to discharge. 

Summary of Contents for RNC100

Page 1: ...NG DIAGRAM I Controller Level 2 Model 100 thru 150 115 or 208 230V 60 Hz 100 or 240V 50 Hz 17 Models 200 thru 600 230 400 460V 3 50 60 Hz 18 19 Model 750 230 400 460V 3 50 60 Hz 20 21 WIRING DIAGRAM I...

Page 2: ...our plant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist...

Page 3: ...is and has not been preset at the factory for this altitude contact manufacturer s Service Department G The installation of a flexible connection prior to the dryer is recommended to prevent possible...

Page 4: ...DELS 500 600 and 750 CHECK FOR CORRECT PHASING OF UNIT After starting the dryer if an unusual noise is heard or if the discharge line does not get hot the refrigeration compressor may be running in th...

Page 5: ...F 49 C D Maximum ambient temperature Air cooled models 110 F 43 C Water cooled models 130 F 54 C E Minimum ambient temperature 40 F 4 C 2 2 Start up IMPORTANT Energize dryer disconnect switch provide...

Page 6: ...tton until Main Menu screen appears Use the Up and Down arrow buttons to scroll through the list of submenu choices Press Enter button to view the submenu that is displayed Press ESC to exit the Main...

Page 7: ...urs that refrigeration compressor is operating are counted b Press ESC at any time to return to the Main Menu NOTE On dryers with air cooled condensers regular condenser cleaning is recommended Dirtin...

Page 8: ...compressor off when power is restored after power interruption 7 To reinstitute SCHEDULE RUNNING push Schedule On Off and Enter button IMPORTANT Dryer must be energized 24 hours before refrigeration...

Page 9: ...he following for proper drain function Automatic Draining Valve handle should be positioned parallel to the valve body as shown with the arrow on the handle pointing toward the EDD In this position co...

Page 10: ...EPRESSURIZE BEFORE SERVICING If filter has not been depressurized before disassembly an audible alarm will sound when the bowl begins to be removed from the head If this occurs stop disassembly isolat...

Page 11: ...parator weekly by pushing test button on control panel 3 5 Rebuild drain mechanism annually To facilitate service maintenance kits are available See page 26 Models RNC200 thru RNC750 Separator Element...

Page 12: ...led models scfm 60 Hz 50 Hz 100 84 125 105 150 125 200 170 250 210 RNC MODEL 300 400 500 600 750 Rated capacity of air cooled models scfm 60 Hz 50 Hz 300 250 400 340 500 420 600 540 750 630 TABLE 2 Ai...

Page 13: ...60 Hz N A 1 1 2 0 50 Hz N A 0 9 1 7 Electrical Data Nominal Voltage 115 1 60 208 230 3 60 Min Max Voltage 104 127 187 253 Input Power Rated Flow watts 875 1070 1100 1255 1962 Rated Load Amps 9 5 13 0...

Page 14: ...sig 2 8 barg minimum Flow Required with 85 F Cooling Water gallons per minute 60 Hz 2 0 2 1 4 9 6 8 50 Hz 1 7 1 8 4 1 5 6 Electrical Data Nominal Voltage 208 230 3 60 Min Max Voltage 187 253 Input Pow...

Page 15: ...2 600 30 15 766 30 15 766 30 15 766 30 15 766 30 15 766 30 15 766 30 15 766 E 17 62 448 17 62 448 17 62 448 30 15 766 30 15 766 30 15 766 30 15 766 39 62 1006 39 62 1006 39 62 1006 F 19 62 498 19 62 4...

Page 16: ...1 L2 230 VAC CUSTOMER SUPPLIED L1 PE POWER ON PILOT LIGHT T2 T2 T2 T1 T1 PE T2 T1 T1 FPS 1 FAN 1 MTR2 START RELAY SR SR L3 L3 M 6 5 S CAPACITOR 4 OVERLOAD 3 1 3 MTR1 COMPRESSOR R C S 120 VAC POWER COR...

Page 17: ...GROUND STUD PE FAN 1 HARNESS C 1 FAN 1 MTR2 FPS 1 COMPRESSOR MTR1 DRAIN NEUTRAL COMPRESSOR ON L1 L1 N L1 1 1 N L1 1L1 N 1 N GROUND STUD 6 7 J5 3 5 4 1 2 N N COMPRESSOR CONTACTOR N TO GROUND STUD PE N...

Page 18: ...HARNESS 1L2 L3 TB2 TB2 PE T3 T2 H1 HEATER 1 for 500 600 models only FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 18 REF SHEET 01 LINE 19 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE TB1 L1...

Page 19: ...M SHEET 01 X X X X THERMISTER IC2 LEVEL BOARD DRAIN NEUTRAL DRAIN LINE THERMISTER NEUTRAL 3 N N HPS 1 LINE 1 1 1 TB2 DRAIN HARNESS GRN YELLOW GRN YELLOW DRAIN HARNESS DRAIN HARNESS PE PE TB2 X PE 3 BR...

Page 20: ...ESS 1L2 L3 TB2 TB2 PE T3 T2 H1 HEATER 1 FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 12 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE L1 L1 L1 L3 L2 TB1 L1 L3 L2 CONT 1...

Page 21: ...EET 01 X X X X THERMISTER IC2 LEVEL BOARD DRAIN NEUTRAL DRAIN LINE THERMISTER NEUTRAL 3 N N HPS 1 LINE 1 TB2 DRAIN HARNESS GRN YELLOW GRN YELLOW DRAIN HARNESS DRAIN HARNESS PE PE TB2 X PE 3 BROWN BLUE...

Page 22: ...RNESS 1L2 L3 TB2 TB2 PE T3 T2 H1 HEATER 1 for 500 600 models only FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 11 REF SHEET 02 LINE 10 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2...

Page 23: ...larm A N O W15 W13 W14 W11 W10 W9 W8 W21 W19 Alarm B N C Alarm B Com Drain Test Output Alarm B N O Drain Test Output Compressor 1 Output Compressor 1 Output W27 W18 W17 W16 N A N A W25 W23 FROM SHEET...

Page 24: ...T3 T2 H1 HEATER 1 FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 11 REF SHEET 02 LINE 10 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE L1 L1 L1 L2 L3 TB1 L1 L3 L2 CONT 1 D...

Page 25: ...rm A N O W15 W13 W14 W11 W10 W9 W8 W21 W19 Alarm B N C Alarm B Com Drain Test Output Alarm B N O Drain Test Output Compressor 1 Output Compressor 1 Output W27 W18 W17 W16 N A N A W25 W23 FROM SHEET 01...

Page 26: ...X2 X3 X4 PE L3 L2 L1 TB2 FU1 M FU2 M FU3 M FU1 P FU2 P FU3 P 575V VOLTAGE OPTION 575V 460V TRANSFORMER BANK 460V CONNECTION 460 3 60 CUSTOMER CONNECTION PRIMARY FUSE ENCLOSURE 575 3 60 CONNECTION CUS...

Page 27: ...ss dryer 1 Excessive air flow 2 Freezing of moisture in evaporator because of refrigeration system fault 3 Separator or optional Oil Removal filter element clogged Check flow rate See D below Replace...

Page 28: ...ant a Lack of condenser cooling Air cooled Ambient temperature too high clogged condenser fins obstructed flow across condenser faulty fan motor or fan control switch Water cooled Cooling temperature...

Page 29: ...l Right Lower G5002271 G5002271 G5002271 REPLACEMENT CABINET PARTS Models RNC200 through RNC750 2 5 3 6 1 4 ID PARTS DESCRIPTION 200 250 300 400 500 600 750 1 Cabinet Panel Top G5002276 G5002276 G5002...

Page 30: ...ON REFERENCE RIGHT REAR VIEW A covers and center support shelf removed for clarity 2 9 12 7 8 10 11 15 18 16 17 1 3 4 RIGHT FRONT VIEW B covers and center support shelf removed for clarity 7 8 10 2 9...

Page 31: ...ot Gas Bypass Valve G5002350 G5002350 G5002350 G5002350 G5002350 G5002350 G5002350 G5002350 G5002350 10 Condenser G5002249 G5002249 G5002249 G3232828 G3232828 G3232828 G3232828 G3232828 G3232828 11 Fi...

Page 32: ...EFERENCE RIGHT REAR VIEW A covers and center support shelf removed for clarity 33F 39F 1C 4C 23 7 2 8 1 24 3 25 IC2 Control Panel RIGHT FRONT VIEW B covers and center support shelf removed for clarity...

Page 33: ...G3227172 G3227172 G3227172 G3227172 G3227172 G3227172 G3227172 G3227172 19 Digital PC Board IC 4 G3227156 G3227156 G3227156 G3227156 G3227156 G3227156 G3227156 G3227156 G3227156 G3227145 20 Digital P...

Page 34: ...ORIENTATION REFERENCE RIGHT REAR VIEW A covers and center support shelf removed for clarity 33F 39F 1C 4C 18 4 2 3 1 7 5 19 20 IC2 Control Panel RIGHT FRONT VIEW B covers and center support shelf rem...

Page 35: ...erature Sensor IC 2 G3210926 G3210926 G3210926 G3210926 G3210926 G3210926 G3210926 G3210926 G3210926 G3210926 17 Temperature Sensor IC 4 G3210926 G3210926 G3210926 G3210926 G3210926 G3210926 G3210926...

Page 36: ...ED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN MANU...

Reviews: