background image

6

3.0 Operation

3.1 Start-up and Shut down Procedures

A.   Pre-start-up Procedure

After making sure Master switch is OFF (Pushed in),
energize dryer.  Power on light will illuminate.

CAUTlON:

 do not turn Master switch to ON at this

time. Dryer must be energized twenty-four (24)
hours before refrigerant compressor is started.

NOTE:

 Start-up should be done only under the

supervision of a qualified refrigeration mechanic who
is familiar with accepted operational practices for
refrigeration systems.

1. 

 Water-Cooled models

 - Open main water supply

valve and allow water to flow through the condenser.
Check for water leaks.  Water will not flow through
water valve unless head pressure is over 196 psig, 13.8
kgf/cm

2

.

2.  Open refrigeration valves

a.  Backseat (by turning counterclockwise as far as

possible) hot gas by-pass line manual shut off
valve.

b.  Open compressor high side (discharge) service

valve by first back seating (turning counterclock-
wise as far as possible) then (water-cooled models
only) turning clockwise two (2) complete turns.

c.  Back seat (by turning counterclockwise as far as

possible) liquid line shut-off valve, then turn
clockwise two (2) complete turns.

d.  Back seat (by turning counterclockwise as far as

possible) compressor suction service valve.

e.  Refrigerant leak test all refrigerant connections

and refrigeration system components using a
halogen leak detector, General Electric Model H-11
or equal. Pay particular attention to control lines
which may have loosened during shipment or
handling. Refrigerant leaks are normally evidenced
by the presence of oil at the leak.

3.  Check compressor for correct oil level.  (Oil should be

visible in sight glass).

4.  Check electrical voltage to be sure it is within the limits

shown in Technical Data Section or 10% of nameplate
voltage.

5.  Check that automatic condensate drain valve isolation

valves are open.

6.  

Air-Cooled models 

- Check that any isolation valves

between dryer and condenser are open.

B.  Start-Up Procedure - (Dryer energized; master switch

off)

     

CAUTlON:

 DRYER MUST BE ENERGIZED (POWER ON

LIGHT ILLUMINATED) TWENTY-FOUR (24) HOURS BEFORE
START-UP OF THE REFRIGERATION COMPRESSOR.

1.  After dryer has been energized at least twenty-four

(24) hours pull Master switch to on position.  Dryer will
automatically pump down.  Allow dryer to cycle until
display on Operator Interface indicates Stand-by.

2. Turn Stand-by/Auto Selector Switch to AUTO position.

3.  While keeping the air by-pass valve open and air outlet

valve closed, SLOWLY open the dryer inlet valve to
pressurize the dryer.

4.  Leak test all air piping, flanges, and drains for possible

air leaks.

5.  

Air-Cooled Models

 - Fan(s) in compressor section

should start up after unit has been running for several
minutes.  Fan(s) may not start up immediately upon
introducing power to the condensing unit since they
are controlled by means of a refrigerant pressure
switch.  This switch may cycle fan(s) off and on in order
to adjust to varying load conditions in refrigerant
system.

    

 IMPORTANT:

  

Air-Cooled Models

 - Check for proper

fan rotation.  Air should be pulled through condenser.

6.  After dryer has operated about fifteen (15) minutes,

slowly open the dryer air outlet valve.

7.  Close the dryer air by-pass valve.

8.  Make a general inspection of the dryer. Tighten all

bolts, nuts, and fittings.

9.  Remove all service gauges and test instruments.

Replace all seal caps on valves.  Retest connections for
leaks with leak detector.

10. Allow the dryer to operate normally for at least three

(3) hours. Recheck operation of all controls, safety
switches, instrumentation and condensate drains.

11. Review Operational Check Points as listed in
      Section 3.5.

C.  Standard Shut-Down Procedure

Turn Stand-by/Auto Selector Switch to STAND-BY position.
Allow dryer to operate in this mode during shutdown
period.  (Master switch remains in on position).

D.  Maintenance Shut-Down Procedure

This procedure is used to shut unit down for extended
maintenance periods.

1. Turn Stand-by/Auto Selector Switch to STAND-BY

position. Allow unit to cycle several times.

2.  Push the Master switch to OFF position.

     

NOTE:

  Except for maintenance reasons, leave dryer

energized.  This allows the crankcase heater to func-
tion.

     WARNING:

  De-energize dryer at disconnect if working

on electrical or rotating components.

Summary of Contents for RHC Series

Page 1: ...sed air system 4 2 3 Mounting 4 2 4 Piping 4 2 5 Electrical 4 2 6 Air Cooled Models 5 2 7 Compressor tiedown nuts 7 1 2 and 10 horsepower units only 5 3 0 OPERATION 6 3 1 Start up and Shut down Proced...

Page 2: ...When a shipment has been delivered to you in apparent good order but concealed damage is found upon unpacking notify the carrier immediately and insist on his agent inspecting the shipment Fifteen day...

Page 3: ...rature no more water vapor will condense into troublesome liquid In addition the air is filtered of all solid particles three microns and larger Clean dry compressed air leaving the dryer minimizes ma...

Page 4: ...y hole in electrical enclosure If optional disconnect supplied use entry hole in disconnect enclosure 2 0 Installation 2 1 Location A A moderately heated well ventilated area is the best location for...

Page 5: ...sure that voltage to unit is as marked on unit nameplate and on condensing unit baseplate E Air Cooled models remote condensers wire condenser to terminals in dryer electrical enclosure identified on...

Page 6: ...ENERGIZED POWER ON LIGHT ILLUMINATED TWENTY FOUR 24 HOURS BEFORE START UP OF THE REFRIGERATION COMPRESSOR 1 After dryer has been energized at least twenty four 24 hours pull Master switch to on positi...

Page 7: ...ic drains F5 shift F1 Sensor calibration low pressure cutout setting password required F6 shift F2 English or metric unit selection F7 shift F3 Refrigerant low pressure cutout override F8 shift F4 Ele...

Page 8: ...mpressor Solid State Motor SSMP 2MTR Protector Open 2nd Compressor Motor Starter Protector Open MTR STARTER 1MTR Motor Starter Protector Open 2nd Compressor MTR STARTER 2MTR Low oil pressure OIL PRESS...

Page 9: ...9 Typical Wiring Schematic...

Page 10: ...INLET AIR TEMP Optional Indicates inlet air tempera ture is greater than 120 F 49 C 5 LOW EVAP AIR TEMP Optional Indicates air tempera ture in evaporator is below the set point 6 DRAIN LEVEL HIGH Opti...

Page 11: ...ld detergent using a long handled brush or a clean rag attached to a rod Manifold face must be free of dirt and grease to ensure proper O ring seal between top cap and manifold 6 Remove nut 3 and cap...

Page 12: ...on System Check system pressure after unit has been OFF for one 1 hour Com pare this pressure with the refrigeration pressure at ambient temperature They should be the same If system pressure is high...

Page 13: ...scharge valve Check to see that it is fully open 2 Low or high water temperatures at the condenser outlet The condenser is regulated by a pressure actuated water regulating valve supplied by the facto...

Page 14: ...after flushing and wiping further cleaning is desirable The color of this coating varies with water conditions but roughness indicates cleaning tools should be used A set of recommended cleaning tool...

Page 15: ...5 9 3 195 200 34 8 15 1 20 1 1 4 166 160 30 8 9 8 206 880 36 9 18 6 25 1 1 2 213 440 39 5 11 4 278 620 49 7 20 0 30 1 1 2 247 340 45 8 16 6 306 680 54 7 26 0 35 2 1 2 315 820 58 4 11 9 395 460 70 5 15...

Page 16: ...ts kit Reassemble float arm assembly to valve stem assembly using new pivot pin and retainer clip from repair parts kit f Remove valve sleeve 5 from valve stem assembly and replace valve disc 4 with n...

Page 17: ...s positioned in open area of seal ring retainer For 506 series models make sure rod on top of float assembly fits into hole in seal ring retainer as shown in Detail C n Before reassembling shell make...

Page 18: ...efrigerant 4 Water cooled units A Insufficient water flow thru condenser 1 Water regulating valve not adjusted Adjust water regulating valve 2 Dirty water strainer Clean water strainer 3 Water lines t...

Page 19: ...nsor bulb for looseness and correct location 5 Piping vibration Support pipes as required check pipe connections 6 Hissing insufficient refrigerant flow thru Reclaim refrigerant replace strainer expan...

Page 20: ...turer Normal maintenance items requiring routine replacement are not warranted Unauthorized service voids the warranty and any resulting charge or subsequent claim will not be paid Products repaired o...

Reviews: