HYD-7-600    Page  8 

SECTION 2 
INSTALLATION 

 

MOUNTING 

 

Drilling clearance holes for ½

” bolt size is required to mount the Hydrapak (see bolt pattern on page 11).  

Mounting hardware includes rubber isolation washers, flat washers, lock washers, and hex huts.   
 

HYDRAULIC HOSES & FITTINGS 

 

 

 

All high pressure hoses & fittings must have a working pressure rating equal to or higher thank 
the hydraulic system relief valve setting. 

 
 

 

 

·

 

Suction line rotation must not rise above the oil level height in reservoir at any location.  
This may cause severe hydraulic pump cavitation which will reduce the hydraulic pump life 

·

 

Do not use thread tape or sealant on hydraulic fittings as this can contaminate hydraulic 
system

 
 

NOTICE 

SUCTION LINE SIZING & ROUTING 

·

 

Pressure drop calculations must be performed on the specific system and corresponding 
tractor unit to insure acceptable suction conditions.

 

·

 

The routing of the suction line must be done to avoid excessive pressure drop.  Elbows, 
reducers, and line rises above the bottom of Hydrapak reservoir will cause excessive 
pressure drop in suction line.

 

·

 

The maximum recommended vacuum at the hydraulic pump inlet is 5” Hg.  For gear pumps 
and 2” Hg. for piston pumps.

 

·

 

The suction hose must be capable of operating under 28” Hg. Vacuum.

 

 

 
 

Special attention should be given to applications utilizing a double suction or large diameter piping. When 
excessive loading or insufficient support of the suction piping exists, reservoir fatigue fractures, loss of oil, 
and decreased hose life are likely to occur. 

 

1.  For double suction applications, if weight and length of pipe work (fittings) is excessive, shorten 

the piping to reduce vibration and add support brackets to compensate for the added weight. 
Additional support brackets should be attached to a common point with the Hyrdrapak so that 
flexing of the truck frame and vibration does not induce additional stress on the Hydrapak.   

 

2.  . On direct coupled double suction piping, if mounting conditions do not accommodate additional 

support brackets, consider line mounting a pipe "Y" to fill the need for a double suction. When line 
mounting the "Y", a single section of large diameter hose can be fitted to the reservoir suction 
fitting leading into the "Y" downstream.  Appropriately sized piping can then exit the "Y" and lead 
into the pump inlet sections. Always make sure the "Y" pipe is supported and consideration is 
given to the remaining points. 

Summary of Contents for MH-C2 HYDRAPAK

Page 1: ...PARTS LIST OPERATING AND SERVICE MANUAL MOBILE HYDRAULIC COOLING SYSTEM 30 G P M 3500 PSI 5000 PSI optional HYD 7 600 Version 01 September 17 2014 MH C2 HYDRAPAK...

Page 2: ......

Page 3: ...e 3 Maintain Hydrapak Reliability And Performance 4 Instructions For Ordering Repair Parts 4 Foreword 5 Safety Instructions 6 Section 1 Equipment Check 7 Section 2 Installation 8 Section 3 Initial Sta...

Page 4: ...e Section 3 12 Installation Section 2 8 Introduction Your Key To Trouble Free Service 3 Maintenance Section 4 13 Mounting 8 Parts List Section 5 14 Safety Instructions 6 Storage 7 Warranty 16 LIST OF...

Page 5: ...must observe to assure optimum cooler performance There is no guesswork in the manufacture of your highly advanced Gardner Denver Hydrapak and there must be none in preparing the cooler to get the job...

Page 6: ...our state of the art factory under exacting quality standards Your AUTHORIZED DISTRIBUTOR offers all the backup you require A worldwide network of authorized distributors provides the finest product...

Page 7: ...tion for day to day operation maintenance and adjustment Careful adherence to these instructions will result in economical operation and minimum downtime Danger indicate a hazardous situation that if...

Page 8: ...eath If injured seek emergency medical help immediately Immediate surgery is required to remove oil Do not use finger or skin to check for leaks Lower load and or relieve hydraulic pressure before loo...

Page 9: ...ion and operation of this equipment in the system or facility STORAGE Your Gardner Denver Hydrapak was packaged at the factory with adequate protection to permit normal storage for up to six 6 months...

Page 10: ...uum at the hydraulic pump inlet is 5 Hg For gear pumps and 2 Hg for piston pumps The suction hose must be capable of operating under 28 Hg Vacuum Special attention should be given to applications util...

Page 11: ...allation of the hoses should include a slight bend in the hoses near the connections This allows them to flex reduce vibration stress and hose shrinkage under load 5 All hoses should use the largest b...

Page 12: ...HYD 7 600 Page 10 FIGURE 2 1 AIR FLOW DIRECTION AND OUTLINE...

Page 13: ...HYD 7 600 Page 11 FIGURE 2 2 AIR FLOW DIRECTION AND OUTLINE...

Page 14: ...reservoir with Shell Tellus T series ISO 32 hydraulic oil or equivalent until oil appears in sight glass 3 Replace filter element and cap 4 Slowly raise clutch while engine is running to engage P T O...

Page 15: ...l level each week with system OFF Oil should be visible in lower of sight glass 3 Visually check the system each week all fittings hoses and Hydrapak mounting 4 Grease P T O Pump spline every 3 months...

Page 16: ...HYD 7 600 Page 14 SECTION 5 PARTS LIST MH C2 See page 15 for Parts List...

Page 17: ...ALVE 1 303000008 303000008 BB1132940 25 FITTING HYD ADAPTER 1 302065207 302065207 302065207 26 FITTING HYD TEE 1 302005200 302005200 302005200 27 FAN 1 VP1118078 VP1118078 VP1118078 28 FITTING HYD PLU...

Page 18: ...e personnel is not provided for by this warranty Transportation of Company s choice within the continental United States is covered by this warranty for replacement of any blower which in the Company...

Page 19: ......

Page 20: ...For additional information contact your local representative or visit www contactgd com blowers 2014 Gardner Denver Inc Printed in U S A...

Reviews: