13-17-625 v00
Figure 19: IO Module DIP Switch Settings at RS485-1 Port
4.2 Communication Configuration
The RS485 communications will need to be configured in the settings and the sequence mode will
need to be selected. Delcos sequencing requires a baud rate of 9600, which will be set
automatically once the protocol has been selected. Navigate to the communication settings by
selecting Menu, Settings, Configuration, and then Communication, shown in Figure 20. Select the
RS485-1 tab, and then change the mode to
Sequence
– Delcos.
Machines which have RS485-2
at X03 populated will show an additional tab called “
RS485-2
” in the menu with the same settings
available. Use the port that corresponds to the physical location of the wiring connections on the
machine.
Figure 20: Menu Navigation to Communications Screen
Please note that the controller may prompt the user to reboot following the mode change of the
communication parameters. Select OK and allow the controller to reboot before continuing with
the additional settings.