13-17-621 Page 46
Figure 58: Active Alarms Screen
3.8 Jogging the Motors
If this is the first time that the machine has been started after being connected to power, the motors must
be jogged to verify correct rotation. To do this, you must be logged in as a Technician. After logging in,
navigate to Diagnostics > Jog Motors. The Jog Motors screen is shown in Figure 59.
Figure 59: Jog Motors Screen
Select the desired jog duration and select Compressor Motor or Fan Motor from the dropdown as shown.
You will need to jog both individually to verify correct rotation. The Jog Delay field allows you to delay the
start of the jog from the time that you press the
Start Jog
button. This is to allow you time to get into a
position to view the rotation before the motor is started. Note that the controller will only allow one jog every
10 seconds and will disable the
Start Jog
button during this time period.
After correct rotation has been verified, return to the Home screen and proceed to operate the compressor.