13-21-608 Page 19
HEAT EXCHANGER (INTERNATIONAL)
Water Temperature to Heat
Exchanger
(l/s)
Maximum
Water Flow
(l/s) *
Approximate Water
Pressure Drop @ 32
°
C
Water Temperature
(bar)
KW
Model
16
°
C
21
°
C
27
°
C
32
°
C
75
EAQ99W
0.51
0.64
0.85
1.28
2.52
Less than .15 bar for any
flow rate shown in the table
93
EAQ99W,
EBQ99R
0.68
0.85
1.14
1.70
2.52
112
EAQ99W,
EBQ99R
0.81
1.02
1.35
2.03
2.52
175
EBU99F
1.00
1.26
1.68
2.52
7.0
* Flows exceeding "Maximum Water Flow" will cause severe erosion and will void unit warranty.
Figure 2-5 – HEAT EXCHANGER (OIL COOLER) APPROXIMATE WATER FLOW
AFTERCOOLER (DOMESTIC)
Water Temperature to Heat
Exchanger
(gpm)
Maximum
Water Flow
(gpm) *
Approximate Water Pressure
Drop @ 90
°
F Water
Temperature
(psi)
HP
Model
60
°
F
70
°
F
80
°
F
90
°
F
125 HP
EAQ99W
1.9
2.4
3.2
4.8
55
Less than 1 PSI for any flow
rate shown in the table
125 HP
EBQ99R
1.8
2.2
3.0
4.5
55
150 HP
EAQ99W
2.3
2.9
3.9
5.8
55
150 HP
EBQ99R
2.1
2.6
3.4
5.2
55
200 HP
EAQ99W
2.9
3.6
4.9
7.3
110
200 HP
EAU99Y
3.0
3.7
5.0
7.5
110
200 HP
EBU99F
3.0
3.7
5.0
7.5
110
200 HP
EBQ99R
2.6
3.3
4.3
6.5
110
* Flows exceeding "Maximum Water Flow" will cause severe erosion and will void unit warranty.
AFTERCOOLER (INTERNATIONAL)
Water Temperature to Heat
Exchanger
(l/s)
Maximum
Water Flow
(l/s) *
Approximate Water Pressure
Drop @ 32
°
C Water
Temperature
(bar)
kw
Model
16
°
C
21
°
C
27
°
C
32
°
C
75
EAQ99W
0.08
0.10
0.14
0.20
3.47
Less than .1 bar for any flow
rate shown in the table
93
EAQ99W,
EBQ99R
0.11
0.13
0.18
0.27
3.47
112
EAQ99W,
EBQ99R
0.13
0.16
0.21
0.32
3.47
130
EBU99F
0.16
0.20
0.26
0.40
7.0
* Flows exceeding "Maximum Water Flow" will cause severe erosion and will void unit warranty.
Figure 2-6 – AFTERCOOLER APPROXIMATE WATER FLOW