Programming Overview
Mapping Overview
5.3.3 Event Mapping
There are 11 types of zone events, 14 types of panel events, and 6 types of site events that can be mapped (see Table 5.2). For each event
type, you can activate the output groups with specific the output patterns. Mapping examples are shown in Figures 5.4, 5.5, & 5.6.
System
Zone
Panel
Site
Fire
Manual Pull Alarm
System Aux 1 Alarm
Fire Drill
Water Flow Alarm
System Aux 2 Alarm
General Fire Alarm
Detector Alarm (heat or smoke detectors)
General Fire Supervisory
Zone Aux 1 Alarm
General Fire Pre-Alarm
Zone Aux 2 Alarm
Interlock Alert
Interlock Release
Pre-Alarm
Fire Supervisory
Status Point
CO Alarm
CO Supervisory
1
1
Temporal 4 coding cannot not be used for NAC circuits on CO Supervisory events.
Emergency
Advisory
Trouble
SBUS Expander Trouble
General Trouble
Status Point Active
SBUS Class A Trouble
Site Silenced
SLC Loop Trouble
AC Loss Trouble
F1 Key Active
Battery Trouble
F2 Key Active
Ground Fault Trouble
F3 Key Active
Phone Line Trouble
F4 Key Active
Reporting Account Trouble
Table 5.2 Event Types
Zone 1:
manual pull alarm
pattern 00
constant
pattern 02
ANSI 3.41
This example shows Zone 1 manual pull alarm event mapped to:
• Group 1 using constant output.
• Group 5 using ANSI 3.41 output pattern.
group 1
group 2
group 3
group 4
group 5
group 6
through
group 125
Figure 5.4 Example of Zone Events Mapped to Output Groups and Patterns