![Gamewell Honeywell GWF-7075 Manual Download Page 33](http://html1.mh-extra.com/html/gamewell/honeywell-gwf-7075/honeywell-gwf-7075_manual_3358294033.webp)
GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
33
Class A Notification Wiring
Control Panel Installation
4.13 Class A Notification Wiring
You must use an appliance from the list of compatible appliances listed in the
Device Compatibility Document
, P/N: 9000-0427-L8.
To install a Class A notification appliance circuit:
1.
Wire the Class A notification appliances as shown in Figure 4.23.
2.
Configure the circuit for Class A in programming (see Section 6.5).
.
4.13.1 Auxiliary Power Installation
NAC Circuits 1 and 2 on the control panel can be used as auxiliary power circuits. The four types of auxiliary power available are:
•
Door Holder
•
Constant
•
Resettable Power
•
Sounder Sync Power
Auxiliary power circuits are power-limited. Each circuit can source up to 2.5A in an alarm condition (total current for system must not
exceed 2.5A in alarm or 1.0A for all other conditions).
To install an auxiliary power circuit:
1.
Wire the NAC circuit(s) that will be used for auxiliary power.
2.
Configure the auxiliary power output through programming (see Section 6).
Door Holder Power
Door holder power is intended for fire door applications. When there are no alarms in the system and the panel has AC power, door holder
circuits have 27.4 volt power present at their terminals. Any alarm will cause power to disconnect. Power will be re-applied when the system
is reset. If AC power is off for more than 15 seconds, the auxiliary door holder power will be disconnected to conserve the battery backup.
When AC power is restored, power is immediately restored to the door holder circuits.
!
CAUTION: SYSTEM SUPERVISION
FOR PROPER SYSTEM SUPERVISION DO NOT USE LOOPED WIRE UNDER TERMINALS MARKED – AND + OF THE
NAC CIRCUIT. BREAK WIRE RUNS TO PROVIDE SUPERVISION OF CONNECTIONS.
Figure 4.23 Class A Notification Appliance Circuit Configuration
NO
NC
C
TROUBLE
SLCIN
+
_
SLCOUT
SLCPROG
+
_
+
_
SBUS
A
B
+
_
NAC 1
NAC 2
+
+
+
+
+
+
Class A
supervised,
regulated NAC
circuits
shown in alarm
condition
supervised,
power-limited
NAC wiring
NO
NC
C
TROUBLE
SLCIN
+
_
SLCOUT
SLCPROG
+
_
+
_
SBUS
A
B
+
_
NAC 1
NAC 2
Figure 4.24 Example of an Auxiliary Power For Door Holder
non-supervised,
power-limited,
Class B
optional noise
suppression