NFPA Standard-Specific Requirements
Ademco Contact ID Typical Printout
134
GF505 & GF510 Series PN 53164:A 3/26/2007
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP30 on the GF505/GF510 main circuit board to supervise placement of 4XTMF module
and circuit.
3. Cut JP24 on the GF505/GF510 main circuit board to enable FACP Supervisory relay.
4. Refer to "4XTMF Transmitter Module Installation" on page 35 for detailed information.
FIRE
Gamewell Model M34-
56 Local Energy
Municipal Box
Polarities shown in alarm condition
+
Nonpower-limited
Municipal Box
Circuit
+
-
-
4XTMF
Figure B.2 Municipal Box Connected to 4XTMF Transmitter Module