7100 Series Installation/Operating Manual —
P/N 9000-0447:J 08/28/08
47
MAIN Menu Selections
System Programming
5.1.1 Addresses/Default Settings After Auto configuration
Sensors occupy Addresses 01-99 on the signaling line circuits. Sensors are ion, photoelectronic, or
thermal. They are latching and non-verified when auto configured. Monitor/Control modules
occupy Addresses 101-198. The type of device assigned to a monitor module during auto
configuration depends on the address as shown in Table 5.1.2.
5.1.2 Main Menu Programming
Table 5.1.3 lists the Menu Tree and display selections for the Config Menu.
Address Device
100-149 Manual
station
150-159 Supervisory
switch
160-169 Waterflow
switch
170 Silence
switch
171 Reset
switch
172
Fire Drill switch
173 Alarm/Acknowledge
switch
174
Trouble/Supv. Acknowledge switch
175 Aux
switch
176-179 Tamper
switch
180-184 Control
panel
185-189 Remote
zone
190-198 Normally
open
contacts
AOM modules are silenceable and activate on general alarm (day or night). AOM
modules modified by breaking off tabs are non-silenceable and activate on general alarm
(day or night).
Table 5.1.2 Address/Default Settings
Menu Tree
Display and Selections
Main
Any selection
(Only opens if adequate access
has not already been obtained)
[GAIN ] Type password for level 3:
[ACCESS] 000000
keypad: enters password (shows as “XXX…” on display)
OK: if password is valid for desired level (or higher),
opens access, logs the event, and continues to next
menu. If not, returns to Main Menu.
Main
Config
Password
[CHANGE ] Level 1, User 1 111111
[PASSWORD] select key in password
keypad: enters new password for specified level and
user
<>: scrolls through levels and users.
If current access level is lower than selection, password
is shown as XXXXXX, otherwise as digits.
Table 5.1.3 Main Menu Tree Display and Selections