Optional Modules
System Overview
1.4 Optional Modules
The following optional modules and features are available with the 7100 Series:
1.4.1 Digital Alarm Communicator (DACT)
The Model 7100-D provides an integral digital communicator (DACT), fully programmable from
the keypad, which is compatible with Digital Alarm Receivers (DACRs) that can receive the
following formats:
•
SIA DC8
•
SIA DCS20
•
Ademco Contact ID
•
3+1 1400 Hz
•
3+1 2300 Hz
•
4+2 1400 Hz
•
4+2 2300 Hz
1.4.2 Class A Option Module (CAOM)
All 7100 Models are supplied with Class B Notification Appliance Circuits and Class B Signaling
Line Circuits. For Class A operation, the addition of a CAOM Module is required. This module
operates with all 7100 Models and enables the signaling line circuits to operate as Class A, Style 6
or 7 and enables the notification appliance circuits to operate as Class A, Style Z. It supplies the
additional terminals for these circuits.
1.4.3 Municipal Circuit Option Module (MCOM)
The MCOM Module can trip a Local Energy City Master Box or operate in reverse polarity mode
for leased line connection. It can also energize a solenoid for releasing.
1.4.4 Printer Transient Module (PTRM)
The serial output on the BSM is connected via an existing RS-232 RJ-11 connector, J3. This
connection can be used to communicate directly from the panel to the control using a laptop
computer. The PTRM Module is intended for systems where a permanent connection is required.
This type of connection requires the RS-232 port to have sufficient transient protection to comply
with the applicable codes for wiring leaving the confines of the control box, as well as the proper
isolation of the signal to prevent damage or interference caused by the connection to certain EDP
devices. Connections are limited to the same room. The PTRM supplies supervision and transient
protection as well as the necessary isolation.
1.4.5 LCD-7100 Remote Serial Annunciator Module
The LCD-7100 Serial Remote Annunciator Module provides an 80-character display and the
function keys for the following:
The 80-character display shows all pertinent information except for menus.
•
Alarm Acknowledge
•
System Reset/Lamp Test
•
Trouble Acknowledge
•
System Drill Test
•
Signal Silence