COMMISSIONING

 

Upon completion of the installation, the TMV must be tested and commissioned as per the procedure outlined below. 
The entire procedure should be read through thoroughly prior to the commissioning of the TMV.  A calibrated digital 
thermometer having rapid response time with maximum temperature hold, a small flat bladed screwdriver, adjustable 
spanner and the adjusting key (supplied with the TMV) will be required to check and set out the outlet mixed temperature 
of the TMV. 

 

Ensure all outlets that will be serviced by the TMV have adequate warning signs posted to ensure that no outlet 
is used during commissioning. 

 

Open the cold supply line to the valve, and then open the hot water supply line, ensuring there are no leaks. 

 

Open the outlet that is serviced by the shortest length of pipe work between the mixing valve and outlet fixture. 

 

Allow the mixed outlet to flow for at least 60 seconds to allow the temperature to stabilise before taking a 
temperature reading at the outlet with a digital thermometer. The flow rate should be at least 6 L/min. The flow 
rate can be checked with the aid of a known size container and a stopwatch.  

 

If the outlet temperature requires adjustment the following steps are requires; 

TEMPERATURE ADJUSTMENT

 

 

 

1.  Using a small flat bladed screwdriver lever the 

protected cover off the Thermostatic Mixing Valve. 

2.  Release the Temperature Locking Nut with an 

adjustable spanner. 

 

 

3.  Fit the supplied key over the adjusting spindle 

(figure 3). 

 

To increase the mixed outlet temperature, rotate the 
spindle anti-clockwise. 

 

To decrease the mixed outlet temperature, rotate 
the spindle clockwise. 

 

 

4.  Allow the mixed outlet temperature to stabilize for 60 

seconds and once again take a temperature reading. 
Repeat the procedure until the desired temperature has 
been reached. 

Summary of Contents for CliniMix Lead Safe TMV SS

Page 1: ...ng tempered water to the desired outlets This stainless steel hinged cabinet kit is a lockable cabinet with 20mm copper fittings 2 in and 1 out which allows secure installation and safe simple mainten...

Page 2: ...es 3 0 DESCRIPTION This manual covers the CliniMix Lead SafeTM TMV SS Cabinet Assembly with Universal Door 20 Bottom In Out These are designed to provide tempered water to the desired outlets This mix...

Page 3: ...APH The Galvin Engineering CliniMix Thermostatic Mixing Valve is suitable for many applications The Head loss Characteristic for Mixed Outlet Flow rate versus Balanced Inlet Pressure is shown below in...

Page 4: ...ction within specification on unequal pressures up to 6 1 The mixer has integral isolating valves which permit servicing of the strainer check valve flow regulator and thermostatic cartridge They are...

Page 5: ...ure to do this may void the warranty 3 Connect water lines Before connecting to water lines all lines must be flushed Remove protective vinyl cap from copper tubes Join each copper tube to the correct...

Page 6: ...rtest length of pipe work between the mixing valve and outlet fixture Allow the mixed outlet to flow for at least 60 seconds to allow the temperature to stabilise before taking a temperature reading a...

Page 7: ...Restore the cold water to the TMV After the mixed water temperature has stabilized note the outlet temperature ensuring the outlet temperature has reestablished Now repeat the above test except this t...

Page 8: ...st plugs in the top of the inlet fittings are tight and that there is no evidence of water leakage The TMV must then be recommissioned as per Section 7 0 including temperature adjustment and the shutd...

Page 9: ...rass top assembly screw out the plastic spindle and replace the smaller O ring 5 Carefully remove the spindle from the center of the body 6 Remove O ring from spindle Replace with O ring supplied in t...

Page 10: ...OR WM TMV1 1 2 WM ISO 1 INLET ISOLATOR ELBOWS PAIR FOR WM TMV1 1 3 WM NRV 1 INLET NON RETURN VALVE FOR WM TMV1 PAIR 1 4 WM STR 1 INLET STRAINERS FOR WM TMV1 PAIR 1 5 WM TPKIT 1 THERMOSTAT PISTON SHUTT...

Page 11: ...r s recommendation the ode and all relevant statutory and local tate or erritory requirements 4 The TMV must be returned to Galvin Engineering together with a fully and correctly completed Galvin Engi...

Page 12: ...ntrol valves to ensure inlet conditions are within range Clean strainers ensuring debris is removed Either full hot or cold flowing from the outlet fixture Valve is incorrectly set Hot Cold water has...

Page 13: ...___________________ Model No ________________________ Size _________ Valve Location Building _____________________________________________________________________ Valve Identification No _____________...

Page 14: ...k It is hereby certified that all the commissioning work has been carried out by the undersigned in accordance with the requirements of the Codes of Practice indicated prior Date of Valve Commissioned...

Page 15: ...Outlets in Use One Outlet in Use All Req d Outlets in Use 1 2 3 4 5 6 7 8 9 10 11 Give details of brand and model designation Commensurate with the design flow rate for the mixing valve Note An accura...

Page 16: ...e ______________________ Date _______________________ Maintenance Tests Yes Date of Previous Service ______________________________________________________________________ Previous Service carried out...

Reviews: