Version 1, 15 June 2020, 2 of 16 

2.0 

SAFETY

 

The CliniMix

®

 Lead Safe

TM

 TMV SS Cabinet Assembly is a high-performance valve designed to give stable and 

dependable operation, provided it is installed, commissioned, operated and maintained as per the 
recommendations outlined in this manual. It should be noted, however, that this valve should not be considered 
as an alternative to adequate supervision and duty of care during its use and operation. 

Note: The mixing valve, inlet controls, pipe work and the surrounding area may become hot when 
installed which may cause burn injuries. Precautions should be taken to ensure that these surfaces 
cannot cause such injuries.

 

 

3.0  

DESCRIPTION 

This manual covers the CliniMix

®

 Lead Safe

TM

 TMV SS Cabinet Assembly with Universal Door 20 Bottom In 

& Out. These are designed to provide tempered water to the desired outlets. This mixing valve cabinet 
assembly is supplied with integral isolating valves, strainers and check valves and is provided with a facility 
for thermal disinfecting of the cold inlet side and mixed water outlet. 

Avoid using heat for soldering near the mixer inlets to prevent damage to internal components.

 

 

4.0  

DIMENSIONS 

 

Cabinet to suit rough-in wall opening area 
310mm width x 310mm height x minimum 75mm 

– maximum 105mm depth. 
 

 

Cabinet secured using back mount or side 
mount. 
 

 

Measure and mark the cabinet mounting holes 
locations at the dimenions shown in below 
mounting details image. 
 

 

Suitable fasteners will need to be sourced by the 
installer.

 

 

BACK MOUNT               SIDE MOUNT 

 

 

 

 

 

   

   

   

   

      

        

      

   

  

      

        

Summary of Contents for 101.10.70.10

Page 1: ...ng tempered water to the desired outlets This stainless steel hinged cabinet kit is a lockable cabinet with 20mm copper fittings 2 in and 1 out which allows secure installation and safe simple mainten...

Page 2: ...es 3 0 DESCRIPTION This manual covers the CliniMix Lead SafeTM TMV SS Cabinet Assembly with Universal Door 20 Bottom In Out These are designed to provide tempered water to the desired outlets This mix...

Page 3: ...APH The Galvin Engineering CliniMix Thermostatic Mixing Valve is suitable for many applications The Head loss Characteristic for Mixed Outlet Flow rate versus Balanced Inlet Pressure is shown below in...

Page 4: ...ction within specification on unequal pressures up to 6 1 The mixer has integral isolating valves which permit servicing of the strainer check valve flow regulator and thermostatic cartridge They are...

Page 5: ...ure to do this may void the warranty 3 Connect water lines Before connecting to water lines all lines must be flushed Remove protective vinyl cap from copper tubes Join each copper tube to the correct...

Page 6: ...rtest length of pipe work between the mixing valve and outlet fixture Allow the mixed outlet to flow for at least 60 seconds to allow the temperature to stabilise before taking a temperature reading a...

Page 7: ...Restore the cold water to the TMV After the mixed water temperature has stabilized note the outlet temperature ensuring the outlet temperature has reestablished Now repeat the above test except this t...

Page 8: ...st plugs in the top of the inlet fittings are tight and that there is no evidence of water leakage The TMV must then be recommissioned as per Section 7 0 including temperature adjustment and the shutd...

Page 9: ...rass top assembly screw out the plastic spindle and replace the smaller O ring 5 Carefully remove the spindle from the center of the body 6 Remove O ring from spindle Replace with O ring supplied in t...

Page 10: ...OR WM TMV1 1 2 WM ISO 1 INLET ISOLATOR ELBOWS PAIR FOR WM TMV1 1 3 WM NRV 1 INLET NON RETURN VALVE FOR WM TMV1 PAIR 1 4 WM STR 1 INLET STRAINERS FOR WM TMV1 PAIR 1 5 WM TPKIT 1 THERMOSTAT PISTON SHUTT...

Page 11: ...r s recommendation the ode and all relevant statutory and local tate or erritory requirements 4 The TMV must be returned to Galvin Engineering together with a fully and correctly completed Galvin Engi...

Page 12: ...ntrol valves to ensure inlet conditions are within range Clean strainers ensuring debris is removed Either full hot or cold flowing from the outlet fixture Valve is incorrectly set Hot Cold water has...

Page 13: ...___________________ Model No ________________________ Size _________ Valve Location Building _____________________________________________________________________ Valve Identification No _____________...

Page 14: ...k It is hereby certified that all the commissioning work has been carried out by the undersigned in accordance with the requirements of the Codes of Practice indicated prior Date of Valve Commissioned...

Page 15: ...Outlets in Use One Outlet in Use All Req d Outlets in Use 1 2 3 4 5 6 7 8 9 10 11 Give details of brand and model designation Commensurate with the design flow rate for the mixing valve Note An accura...

Page 16: ...e ______________________ Date _______________________ Maintenance Tests Yes Date of Previous Service ______________________________________________________________________ Previous Service carried out...