8.8 - External water circulator for MCI__X unit

Units without an integrated pump allow driving an external 

one. The signal (1ph ~ 230V, 2A max) is supplied between 

PINS 16 and N of the terminal strip (see fig 17).

8.9 - External alarm input

On PIN 21 of the terminal strip (see Fig. 17) an alarm input 

(dry contact) is available to force of the unit.

When the contact is closed (Between pin 21 and 3) the whole 

system is turned OFF (Unit OFF, WP OFF, GMC alarm n° 2). 

When the dry contact open the system turns ON and works 

in the last configuration. 

It is possible to use this feature connected with different 

external control systems and/or safety devices. For example 

in case of danger an external safety device could send an 

output alarm signal to close the contact. So the outdoor unit 

turns off and remains in that condition until the dry contact is 

reopened. 

8.10 - Backup heater needed for sanitary hot water

When OAT < Temperature set in NUI code 148 (default value 

-20°C), if Par 108 is set to 1, on pin 11 of the terminal strip a 

signal is available to activate a backup source for SHW 

production.

8.7 -  Signal for requesting an External Heat Source (EHS)

Between PINS 4 and N of the terminal strip (see Fig. 17), there 

is an output (1ph ~ 230V, 2A max) that can be programmed 

using the remote User Comfort Interface (see the control 

manual, Installation Menu code 106).

Two different strategies are possible based on Outdoor Air 

Temperature:

1)   Turn off heat pump and activate backup heat source. 

This function is activated when OAT < Temperature set 

in NUI code 148 (default value -20°C). In this region heat 

pump turns off and external backup is activated 

following one of below logic (NUI CODE 154):

•  

Output always on (NUI CODE 154=0) assumes 

backup has its own regulation.

•  

ON/OFF based on room temperature set point (NUI 

CODE 154=1)

•  

ON/OFF based on water temperature set point 

(CODE 154=2) in case NUI is not installed/available.

2)   Both heat pump and backup heat source activated in 

case Heat Pump delivered power is not enough. This 

function is activated when OAT < Temperature set in NUI 

code 150 (but OAT > temperature set in NUI code 148). 

In this region HP keeps working and backup heater turns 

on if set point on water is not reached by 5°C (value can 

be set with NUI CODE 152) for 10 minutes (value can be 

set with NUI CODE 151). Backup heater turns off when 

set point on water is reached again.

IMPORTANT NOTICE: In case of SHW activation (pins 13-15 

closed) heat pump will turn on and backup heater will turn 

off. This will happen in both the above strategies.
WARNING: In case of EHS installation, it is mandatory to 

install a thermal switch on the water circuit to protect the 

system from too high water temperatures. This protection 

item has to be located immediately downstream the EHS.

8.11 - Terminal strip pin

MCI__H

Description

PIN

Signal

Limits

33AW-CS1B Installation Menu 

Code

Additional external temperature probe

23 - 24

Input (NTC 3kΩ @25°C)

N.A.

126

Sanitary Water Request

13 - 15

Input (contact switch quality>25mA@12V)

N.A.

153

Maximum Frequency Reduction Compressor 

13 - 14

Input (contact switch quality >25mA@12V)

N.A.

5 - 6

3-way valve

10 - 18 - N

Output 230Vac (18-N: Power supply, 10 signal)

1 ph ~ 230V, 2A

N.A.

1- External Heat Source Request

2- Defrost

4 - N

Relay Output Contact

1 ph ~ 230V, 2A

106 - 148 -150

-151 - 152 -154

-155

1- Alarm

2- Ambient temperature reached

5 - N

Relay Output Contact

1 ph ~ 230V, 2A

147

1- Backup heater needed for SHW

2- Humidifier

11 - N

Relay Output Contact

1 ph ~ 230V, 2A

107 - 108

1- Trace heater

2- Additional WP

12 - N

Relay Output Contact

1 ph ~ 230V, 2A

156 - 157

Alarm input

21 - 3

Input (contact switch quality >25mA@12V)

N.A.

N.A.

ON / OFF

6 - 3

Dry contact

N.A.

N.A.

NORMAL / ECO Mode

8 - 3

Dry contact

N.A.

N.A.

Heating / Cooling Mode

7 - 3

Dry contact

N.A.

N.A.

Summary of Contents for MCI

Page 1: ...Installation instructions EN POMPE À CHALEUR À CYCLE AIR EAU Manuel d installation FR LUFT WASSER WÄRMEPUMPE Installationanweisungen DE POMPA DI CALORE ARIA ACQUA Manuale d installazione IT BOMBA DE CALOR CICLO DE AIRE AGUA Manual de instalación ES LUCHT WATERCYCLUS WARMTEPOMP Montagehandleiding NL verter technology A class RG66012647 ...

Page 2: ...ES FIG 17 35 8 1 Vanne à 3 voies 35 8 2 Limitation de fréquence 35 8 3 Signaux Stop Unité ou Dégivrage 35 8 4 Sonde de température extérieure 35 8 5 Déshumidificateur ou Humidificateur 35 8 6 Pompe à eau supplémentaire ADD WP 36 8 7 Signal pour demande d une source de chaleur extérieure EHS 36 8 8 Circulateur d eau extérieur pour unité MCI__X 36 8 9 Entrée alarme extérieure 36 8 10 Chauffage d app...

Page 3: ... 15 73 6 1 Esquema Hidráulico Recomendado Fig 12 13 74 7 CONEXIONES ELÉCTRICAS FIG 17 75 8 CONEXIÓN ACCESORIOS AUXILIARES FIG 17 76 8 1 Válvula de 3 vías 76 8 2 Limitación frecuencia 76 8 3 Señales de Stop Unidad o Desempañado 76 8 4 Sonda de Temperaturas Exteriores 76 8 5 Déshumidificateur ou Humidificateur 76 8 6 Bomba de agua adicional ADD WP 76 8 7 Señal para pedido de una Fuente de Calor Exte...

Page 4: ...4 2 3 1 150 500 1000 1000 150 150 300 300 300 200 1000 300 200 300 1000 1000 1500 2000 200 300 150 200 150 300 500 1000 150 ...

Page 5: ...600 150 150 430 400 363 6 5 4 B A 37 7 8 A B 0 2 4 6 8 10 12 14 16 18 20 5 0 5 10 15 20 25 30 35 40 45 50 008 012 015 004 006 10 15 20 25 30 35 40 45 50 55 60 65 70 25 20 15 10 5 0 5 10 15 20 25 30 35 A B ...

Page 6: ...6 10 11 1 1 2 4 2 3 4 3 1 2 4 6 7 3 6 5 5 2 4 1 7 3 9 1 2 3 1 2 3 7 6 5 2 1 4 3 4 7 1 2 3 6 5 ...

Page 7: ...7 12 1 2 3 3 10 4 6 1 5 7 8 9 11 13 1 1 2 3 3 4 6 5 7 8 9 ...

Page 8: ...5 40 45 50 55 0 0 1 0 2 0 3 0 4 0 5 0 6 MCI 006X 004X 012X 015X 30AWH008X 0 5 10 15 20 25 30 35 40 0 0 1 0 2 0 3 0 4 0 5 0 6 008X B B B B B A A A A B B B A A A A A A A A B B B B 012H 015H 008H 006H MCI MCI MCI MCI MCI MCI MCI MCI 004H 0 0 0 1 0 2 0 3 0 4 0 5 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 0 0 0 1 0 2 0 3 0 4 0 5 0 6 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 0 0 0 1 0 2 0 3 0 4 0 5 0...

Page 9: ...9 16 C B 12 kW 1Ph 4 6 8 kW 1Ph 12 15 kW 3Ph 15 kW 3Ph C D A D C E A C E A D C ...

Page 10: ...W CS1 Remote control C W G Y 13 14 15 7 6 3 2 1 8 21 23 24 C W G Y 13 14 15 7 6 3 2 1 8 21 23 24 Remote control Remote control MCI__H MCI__X 1 4 2 6 5 8 9 3 1 4 2 5 10 3 7 6 9 8 7 S1 S2 S3 S1 S2 S3 Ν Ν 1 8 1 0 1 1 1 2 4 5 1 6 3Ph 11 10 10 10 10 L N 30 40 40 50 1Ph 15 kW1Ph 12 15 kW 3Ph ...

Page 11: ... valve 5 System drain valve at the lowest points of the circuit 6 Air flushing valve in the highest parts of the circuit 7 3 way valve 8 Sanitary water accumulation tank 9 Inside system 14 Water connections A Water flow rate l s B Available static pressure kPa 15 Water connections A Water flow rate l s B Pressure drop kPa 16 Board position inverter board alarm codes only for MCI 012_ A Position 4 ...

Page 12: ...zpumpe 4 Einfüllventil 5 Ablassventil der Anlage an den tiefsten Kreislaufpunkten 6 Entlüftungsventil an den höchsten Kreislaufpunkten 7 3 Wegeventil 8 Brauchwasserspeicher 9 Interne Anlage 14 Hydraulischen Anschlüsse A Wassermenge l s B Statischer Nutzdruck kPa 15 Hydraulischen Anschlüsse A Wassermenge l s B Wasserdruckabfall kPa 16 Position Platine Fehlercodes Inverter nur für MCI012_ A Position...

Page 13: ...de recirculación agua 11 Vaso de expansión 13 Esquema típico del circuito de agua de la unidad MCI__H 1 Válvulas de cierre 2 Filtro de línea para agua 10 mallas cm 2 3 Bomba aceleradora de agua 4 Válvula de llenado 5 Válvula de descarga en los puntos más altos del circuito 6 Válvula de purga aire en los puntos más altos del circuito 7 Válvula de 3 vías 8 Depósito de acumulación agua sanitaria 9 Si...

Page 14: ...higher pressures than R 22 Be sure that servicing equipment and replacement components are designed to operate with R 410A t R 410A refrigerant cylinders have a dip tube which allows liquid to low out with the cylinder in a vertical position with the valve at the top t R 410A systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose in order to va...

Page 15: ...ive equipment is used Inspect equipment for damage due to improper transportation or handling File an immediate claim with the shipping company Dispose of the packaging material in accordance with local requirements When lifting the unit absolutely do not use hooks inserted in the side handles use special equipment e g lifting devices trolleys etc Do not step or put anything on the outdoor unit It...

Page 16: ...y overvoltage class III CAUTION Connect the connecting cable correctly If the connecting cable is connected in a wrong way electric parts may be damaged Connection to the mains supply is of the Y type therefore the cable must only be replaced by the technical support in order to prevent any risk Use the specified cables for wiring and connect them firmly to the terminals WARNING Be sure to provide...

Page 17: ...e anchor bolts Anchor bolt nut M10 x 2 pairs If the outdoor unit is installed in a very windy place protect the fan with a wind protection screen and check that it works correctly 5 1 Opening cable knockouts Fig 4 There is a pre cut part that can be removed for running wires Do not remove the unit front panel for easier drilling of the knockouts The pre cut section of the sheet can be removed by p...

Page 18: ... flow 1 Max flow 3 Set Up procedure Set Up procedure Factory pre setting Δp c 8 All functions can be set activated or deactivated by using the operating red knob The control mode Δp v is set on the left of the middle position from 1 to 8 The control mode Δp c is set on the right of the middle position from 1 to 8 For venting the pump turn the knob in its middle position the venting function is act...

Page 19: ...ssary components using material which will guarantee that the screwed joints are leak proof The figures 12 and 13 show a typical water circuit installation For an application with a water circuit the following recommendations must be taken into account 1 The external circulation pump must be installed in the return water pipe work immediately before the heat pump unit without hydraulic module 2 It...

Page 20: ... l Total content l Consult the technical data table Consult the pipe water content table Consult the manual for the installed uses The water content of the system must be between the minimum and maximum values for the units with hydronic kit and greater than the minimum value for units without hydronic kit The minimum value is necessary to provide optimal comfort For units without hydronic kit add...

Page 21: ...nnections refer to Figure 17 while for use refer to the respective manuals NOTE The quality of the contacts must be greater than 25mA 12V Remove the front panel the electric parts appear at the front side The power supply cables can be inserted into the pipe holes Be sure to fix the power cable with bundling band sold in the market so that they do not make contact with the compressor and the hot p...

Page 22: ...rage tank The operating logic provides that in case of a request for sanitary water by an accumulation tank the system controls a 3 way valve to direct the hot water only to the tank and to operate at the maximum capacity to provide water at 60 C compatible with the operating envelope For operation connect the 3 way valve between PINS 18 N and 10 of the terminal strip see Fig 17 PINS 18 Line and N...

Page 23: ...ackup has its own regulation ON OFF based on room temperature set point NUI CODE 154 1 ON OFF based on water temperature set point CODE 154 2 in case NUI is not installed available 2 Both heat pump and backup heat source activated in case Heat Pump delivered power is not enough This function is activated when OAT Temperature set in NUI code 150 but OAT temperature set in NUI code 148 In this regio...

Page 24: ...6 3 Dry contact N A N A NORMAL ECO Mode 8 3 Dry contact N A N A Heating Cooling Mode 7 3 Dry contact N A N A 9 SYSTEM TEST 9 1 Inverter board alarm codes only for MCI012_ Fig 16 Troubles of the inverter can be diagnosed by LED indications on the cycle control P C board of the outdoor unit Utilize them for various checks Before a check confirm each bit of the DIP switch is set to OFF position LED i...

Page 25: ...hich generated before latest error information including present is displayed ON 1 2 3 4 ON 1 2 3 4 Present error SW803 Legend D800 Yellow D801 Yellow D802 Yellow D803 Yellow D804 Yellow D805 Green Latest error SW803 Go off Go on Flash Display 1 Initial display Display 2 SW800 operation Error contents Normal Discharge temp sensor TD error Heat exchanger temp sensor TE error Heat exchanger temp sen...

Page 26: ...or 21 Inverter Current Sensor error 22 Heat Exchanger Sensors TE TS 23 Discharge Temperature Sensor TD 24 Outdoor Fan motor error 26 Other unit error 27 Compressor Lock 28 Discharge Temperature error 29 Compressor Breakdown 30 Low pressure system error 31 High pressure system error 10 UNIT PROTECTION DEVICES Type of safety device Switch on pressure Release Pressure switch on water 300kPa N A Anti ...

Reviews: