LCA
RG66000986 – Rev.00
35
14.3 WATER PUMPING AND STORAGE SYSTEMS
LCA units may be equipped with 4 types of pumping systems, complete with expansion tank, and inertial
storage reservoirs:
- single standard pump
- single uprated pump
- standard pump and back-up pump
- uprated pump and back-up pump.
In the case of pump systems including a back-up pump, the microprocessor controls the pumps in such a
way as to equally divide the hours of operation, changing over the pumps in the event of a fault.
14.4 WATER PUMPING AND STORAGE SYSTEMS
LCA units may be equipped with 4 types of pumping systems, complete with expansion tank, and inertial
storage reservoirs:
- single standard pump
- single uprated pump
- standard pump and back-up pump
- uprated pump and back-up pump.
In the case of pump systems including a back-up pump, the microprocessor controls the pumps in such a
way as to equally divide the hours of operation, changing over the pumps in the event of a fault.
LCA
045 050 060 070 080 090
Standard pump type
A
A
B
B
B
C
Available head, LCA with standard pump (nominal flow rate)
kPa
79
74
123
117
116
159
Rated electrical output, standard pump
kW 0,55 0,55 0,75 0,75 0,75 1,50
Operating current, standard pump
A 1,7 1,7 2,3 2,3 2,3 4,3
Uprated
pump
type
kW
C C D D D E
Available head, LCA with uprated pump (nominal flow rate)
kPa
183
178
138
224
221
229
Rated electrical output, uprated pump
kW 1,50 1,50 2,20 2,20 2,20 3,00
Operating current, uprated pump
A 4,3 4,3 5,3 5,3 5,3 6,6
Inertial storage reservoir capacity
dm
3
218 218 315 315 315 485
Expansion tank
dm
3
8
8 8 8 8 12
LCA
115 130 150 180 205 220
Standard pump type
C
C
D
D
E
E
Available head, LCA with standard pump (nominal flow rate)
kPa
131
126
143
138
146
139
Rated electrical output, standard pump
kW 1,50 1,50 2,20 2,20 3,00 3,00
Operating current, standard pump
A 4,3 4,3 5,3 5,3 6,6 6,6
Uprated pump type (see diagram)
kW
F
F
F
G
G
G
Available head, LCA with uprated pump (nominal flow rate)
kPa
264
258
238
279
281
278
Rated electrical output, uprated pump
kW 4,00 4,00 4,00 7,50 7,50 7,50
Operating current, uprated pump A
9,6
9,6
9,6
16,0
16,0
16,0
Inertial storage reservoir capacity
dm
3
600 600 600 600 850 850
Expansion tank
dm
3
20 20 20 20 20 20