FC66004073- 00
FLAT S
All copying, even partial, of this manual is strictly forbidden
14
FC66004073- 00
EN
FLAT S
10
20
30
40
Speeds
3x
min
med
Max
min
med
Max
min
med
Max
min
med
Max
6x
n°
1
2
3
1
2
3
1
2
3
1
2
3
Air flow rate
m3/h
115
135
170
135
170
225
200
250
340
250
310
420
Power supply
230-1-50
230-1-50
230-1-50
230-1-50
Power input (E)
W
12
17
23
14
20
27
23
28
37
25
31
42
Maximum absorbed current
A
0,06
0,09
0,12
0,07
0,11
0,14
0,12
0,15
0,20
0,13
0,17
0,22
Total cooling capacity (1)
kW
0,86
0,98
1,24
1,09
1,34
1,75
1,41
1,76
2,32
1,76
2,14
2,78
Sensible cooling capacity (1)
kW
0,61
0,7
0,89
0,75
0,93
1,22
1,02
1,27
1,69
1,27
1,55
2,03
Total cooling capacity (5) (E)
kW
0,85
0,96
1,22
1,08
1,32
1,72
1,39
1,73
2,28
1,74
2,11
2,74
Sensible cooling capacity (5) (E)
kW
0,60
0,68
0,87
0,74
0,91
1,19
1
1,24
1,65
1,25
1,52
1,99
Water flow rate in cooling mode (1)
l/h
148
168
213
186
230
300
243
303
399
303
368
477
Pressure drop in cooling mode (1) (E)
kPa
3
3
5
5
7
11
3
5
7
5
6
10
FCEER (E)
D
D
D
D
Heating capacity (2) (E)
kW
1,07
1,21
1,52
1,21
1,47
1,93
1,81
2,21
2,88
2,21
2,66
3,42
Pressure drop (2) (E)
kPa
2
3
4
4
6
9
3
4
6
4
5
8
Heating capacity (3)
kW
1,8
2,05
2,57
2,02
2,45
3,21
3,07
3,73
4,84
3,73
4,48
5,76
Water flow (3)
l/h
158
180
225
177
215
282
269
327
425
327
394
505
Pressure drop (3)
kPa
2
3
4
3
5
7
3
4
6
4
6
9
FCCOP (E)
C
C
C
C
Sound power level (4) (E)
dB/A
30
35
40
35
40
46
32
38
46
37
42
49
Sound pressure level (6)
dB/A
8
13
18
13
18
24
10
16
24
15
20
27
Number of fans
nr.
1
1
2
2
Water connections
std
“
1 / 2
1 / 2
1 / 2
1 / 2
Water content
std
dm3
0,81
1,11
1,41
1,41
Weight
kg
17,0
21,0
22,8
22,8
10
RATED TECHNICAL DATA
1
WATER 7-12 °C, AIR 27°C-19°C
2
WATER 50 °C, SAME FLOW RATE AS COOLING, AIR 20°C
3
WATER 70-60, AIR 20°C
4
Sound power measured according to standards ISO3741 and ISO3742
5
According to EN1397
6
Measured as Q=2 and at a distance of 5 m from the source and in an open field
(E)
EUROVENT certified data
4-PIPE VERSIONS AVAILABLE ON REQUEST