SITING
It is important to bear in mind the following aspects when choosing the best
site for installing the unit:
- size and origin of water pipes;
- location of the power supply;
- solidity of the supporting surface;
- avoid obstacles to the outflow of air from the fan which could cause back
suction (see section on “installation clearance requirements”);
- direction of prevalent winds: (position the unit so that prevalent winds do
not alter the fan air flow).
A prevalent wind blowing from a direction opposite to the fan air flow will
reduce the maximum air temperature to a lower value than specified in the
operating limits,
a wind blowing in the same direction as the fan air flow will increase the minimum
air temperature to a higher value than specified in the operating limits.
Also in the heat pump mode, wind may have the effect of reducing the unit’s
operating range.
- avoid the possible reverberation of sound waves (do not install the unit in
narrow or cramped spaces).
- ensure adequate accessibility for maintenance or repairs (see section on
“installation clearance requirements”).
16.1
POSITIONING OF VIBRATION DAMPERS (ACCESSORY)
Dampers
MXE
CODE
NO. OF VIBRATION DAMPERS
09 -16
RYPAMCA10
4
19 - 21
RYPAMCA10
4