635-SERIES HARDWARE M ANUAL
Chapter-Page
2-8
REQUIREMENTS:
These notes apply to 635-model & 600-model Controllers (and their boards). Please read and follow.
1. Controller Power Source:
System Galaxy Controller requires a continuous power source from a 110VAC non-
switchable outlet*
2. CPU COMMUNICATIONS
a.
635 CPU
=
Auto-sensing 10/100 Mb /Full Duplex at the port side
.
b.
600 CPU
= 10 Mb Ethernet/Full Duplex at the port side.
3. 635-model BOARD IDs
a) CPU number is 1 – factory default
b) Daughter boards must have a valid ID on the CPU data buss (
1-16, no duplicates
). DRM, DIO, DSI.
(635-Models use dipswitches to set Board IDs. You MUST set the ID before you install the board.)
(600-model boards must set the internal values using a terminal emulator)
c) All devices must have a valid ID on the 485-Channel/Section (1-16; no duplicates).
d)
Wireless readers such as Salto Salis, Assa Aperio, Schlage AD400 and legacy readers must be
within the WiFi communication range of their host PIM and also must have a valid ID within the RS-
485 section (1-16, no duplicates, no out of sequencing or overlaps – you can skip a number but you
cannot use it later on a different PIM.
* Exception for IDs in the case of 600 Output Relay Boards …
•
600 General Output Relays valid ids = 1-3 (limit 3 boards per 485-section)
•
600 Elevator Control Relays valid ids = 1-15 (limit 15 boards per 485-section)
(note: standard elevator control uses output relay boards, at least 1 DSI board, and 1 DRM
(elevator reader). Destination-driven or destination-based systems do not use relay boards)
4. WIRING SPECIFICATIONS: Chapter-1 also has complete information about wiring.
Table 13: WIRING SPECIFICATIONS
Connection Type
Max Distance
Wire Gauge & Specifications
Controller to IP Switch
100 meters (328 ft.)
Cat 5e
Unshielded, twisted-pair (UTP)
Reader Hardware
500 ft. from controller
22 AWG, 10-conductor, stranded / shielded
SIGMA Reader
500 ft. from controller
20-24 AWG, single-conductor, non-stranded / shielded
Lock Hardware
500 ft. from controller
18 AWG 2-conductor minimum, stranded
Composite Cable
500 ft. from controller
18 AWG & 22 AWG Card Access 4-Element
RS-485 Multi-drop
(PIM, 635-DRM or Input or
Output Relay Module)
4,000 ft to last node
*
22 AWG, shielded, twisted pair
120-ohm resistors must be installed at both extreme ends as close to the node as
possible for signal termination.
Wireless Readers
within signal range
n/a – this can vary based on the topography of the site.
635 Input Relay Board
4,000 ft to last node
*
22 AWG, shielded, twisted pair
*
total line distance
to the
last
device/node (e.g. PIM, DRM…) on the RS-485 multi-drop is max. 4,000 ft
WARNING! Observe Local Fire and Electrical Codes for wire insulation jackets (i.e. PVC-rated vs. Plenum-rated). Use
Plenum-rated cable when appropriate.
!
IMPORTANT:
Properly ground the DRAIN WIRE on only one end
.
Connect the drain wire to the
GND on the
board
(
Reader Port
).
NEVER ground a drain wire at a Reader (or device-end of the wire-run).
Failure to properly
ground the drain wire can result in undesirable equipment operation.