Testing and Troubleshooting
Generating Audio Test Signals
The Model LE300 is capable of generating several test waveforms onto the audio lines of the Page/Party
®
system to aid in system testing and troubleshooting. Rotary switch SW1 on the main PCBA determines
which Page/Party
®
audio line will receive the test waveform. DIP switch SW2 determines which testing
waveform is generated. Closing DIP switch SW2-8 enables the test waveform. Switches SW2-5 through
SW2-7 select a test waveform. Note that the frequency selections are different on the selected audio party
line. Refer to tables below for valid switch settings.
Table 48. Audio Test Signals
SW1
Selected
Page/Party
®
Line
Selected Tone
SW2-5 SW2-6 SW2-7 SW2-8
1
Party Line #1
7 kHz (sine wave)
Open
Open
Open
Closed
6
Page Line
4 kHz (sine wave) Closed
Open
Open
Closed
2 kHz (sine wave)
Open
Closed
Open
Closed
1 kHz (sine wave)
Closed
Closed
Open
Closed
500 Hz (sine wave)
Open
Open
Closed
Closed
125 Hz (sine wave)
Closed
Open
Closed
Closed
1 kHz (saw tooth wave)
Open Closed Closed Closed
31 Hz pulses
Closed Closed Closed Closed
SW1
Selected
Page/Party
®
Line
Selected Tone
SW2-5 SW2-6 SW2-7 SW2-8
2
Party Line #2
3.5 kHz (sine wave)
Open
Open
Open
Closed
3
Party Line #3
2.0 kHz (sine wave) Closed Open Open Closed
4
Party Line #4
1.0 kHz (sine wave) Open Closed Open Closed
5
Party Line #5
500 Hz (sine wave) Closed
Closed
Open
Closed
250 Hz (sine wave)
Open
Open
Closed
Closed
125 Hz (sine wave)
Closed
Open
Closed
Closed
1 kHz (saw tooth wave)
Open Closed Closed Closed
31 Hz Pulses
Closed Closed Closed Closed
N
OTE
:
Remember to restore SW1 to “0” and SW2 to its initial setting when no longer generating test