Power 

A separate power feed is recommended for stations in Div. 1 areas so that the stations can be de-energized 
for maintenance without disrupting the power supply to the other equipment in the Div. 1 area.  Refer to 
Figure 4 and Figure 5 for wiring details.  Remove the termination enclosure cover and pull all wiring into 
the termination enclosure.  Terminal block TB2 is provided for connection of power to the station.  
Terminate all conductor ends using #6-32 screws lugs. 

AC Models 

Terminate the 120-240 V ac 50/60 Hz feed on TB2.  This terminal block can also be used to connect 120-
240 V ac 50/60 Hz to the next station.  The maximum current of the ac feed shall not exceed 20 amperes.  
Refer to Figure 5 for more details. 

DC Models 

Refer to Figure 4.  Terminate the 24 V dc feed on TB2.  This terminal block can also be used to connect 
24 V dc to the next station.  The maximum current of the dc feed shall not exceed 20 amperes.  Power 
must be supplied by an isolated 24 V dc power source.  Additional power feeds may be required to 
increase the system distance and/or the number of stations. 

N

OTE

:

  Isolated dc power sources must be used for this installation.  The 24 V dc source should be 

located as close to the system center as possible. 

Grounding the negative side of the power source at one point is recommended to ensure hum and noise-
free operation.  Noise present on dc power lines can negatively affect station operation.  Therefore, noise 
should be limited to 10 mV or less. 

When installing this equipment, the power cable length is an important consideration.  Refer to Table 1 
for the recommended wire sizing details and the maximum cable lengths.  This table is a guideline that is 
useful in most applications; however, the installer must take into consideration any parameters specific to 
their application. 

Table 1. Maximum Distance between 

Driller’s Intercom Stations (in feet)* (DC) 
# of 

AWG Wire 

Stations 

12 

14 

16 

18 

906 570 358 225 

302 190 119  75 

151 95 59 37 

90 57 35 

------- 

60 38 

------- 

------- 

43 27 

------- 

------- 

32  ------- ------- ------- 

25  ------- ------- ------- 

*This chart is based on the following 
parameters: 

1.

 

V(max) = 27 V 

2.

 

V(min) = 21 V 

3.

 

Cable temperature rating = 90º C 

4.

 

The American Wire Gauge 
resistance table 

For V(max) of 24 V, multiply the 
distance shown by a factor of 0.47. 

Summary of Contents for DEX-202

Page 1: ...rview 1 System Requirements and Limitations 1 Features and Functions 2 Available Models 2 Description of Major Components 2 Installation 3 General Information 3 Mounting 5 Conduit Installation 5 Field...

Page 2: ...ng platforms especially in hazardous areas It provides all call group call and point to point communications and is available in digital and analog versions The enclosure is rated NEMA 4X and is facto...

Page 3: ...keypad 24 V dc UL DEX 202 Digital Intercom Station with keypad 120 V ac UL Description of Major Components The Driller s Intercom stations consist of a factory sealed enclosure top and a termination...

Page 4: ...authorized personnel Refer to the Maintenance section for more details WARNING After installing station and before applying power verify that the bolts on the factory sealed section of the station are...

Page 5: ...Pub 42004 679L2D MODEL DEX 10X AND DEX 20X DRILLER S INTERCOM STATIONS Page 4 of 13 f standard ioms current release 42004 instr manuals 42004 679l2d doc 10 10 Figure 2 Driller s Intercom Outline...

Page 6: ...y fasten the factory sealed and termination enclosures to the mounting location using steel mounting bolts and washers or washer head bolts hardware not included Conduit Installation Install the condu...

Page 7: ...o be completed in the termination enclosure bottom enclosure only NOTE Consult the National Electrical Code NFPA 70 Canadian Standards Association CSA 22 1 and local codes for the specific requirement...

Page 8: ...r must be supplied by an isolated 24 V dc power source Additional power feeds may be required to increase the system distance and or the number of stations NOTE Isolated dc power sources must be used...

Page 9: ...ions require termination of a 2 conductor twisted pair cable on system terminals A and B only Analog stations require termination of a 4 conductor twisted pair cable A B twist C D twist on system term...

Page 10: ...rd ioms current release 42004 instr manuals 42004 679l2d doc 10 10 System Interconnection Refer to Figure 6 for a typical system wiring diagram Consult the Central Switch manual for further details on...

Page 11: ...o from the slave station is broadcast over this station s speaker when the T button or footswitch is released Point to Point Communication Refer to the Direct Dialing section of the Central Switch man...

Page 12: ...nication Communication with this station can be enabled when another station dials the extension of this station 1 The LED on the front panel illuminates to indicate a call is in progress NOTE The bea...

Page 13: ...ion Refer to the Volume Configuration section of the Central Manual for details High speaker volume Decrease the actual and or maximum volume settings in the configuration Refer to the Volume Configur...

Page 14: ...e amplifier Frequency response 200 4 000 Hz 3 dB ref 1 kHz Speaker amplifier Output Class AB 18 watts min into 8 ohms with nominal supply voltage Frequency response 200 10 000 Hz 3 dB ref 1 kHz Distor...

Reviews: