Pub.  42004-101C 

Model 9974 Junction Box 

Page: 

3 of 4

 

f:\standard ioms - current release\42004 instr. manuals\42004-101c.doc 

11/12 

Figure 2.  Wiring Diagram (Typical) 

Wiring 

Figure 2 is the wiring diagram for Model 9974.  The wire color code is based on GAI-Tronics 60038 or 
60029 inter-station cable, and 60021 speaker cable.  Power connections should be made with No. 14 
AWG conductors while signal connections should be made with No. 18 AWG conductors.  Use of 
GAI-Tronics cable, following the correct wire color designations, will ensure that power and signal 
connections are made with the proper gauge wire. 

N

OTE

:

 

 

The installer must crimp a round lug onto the earth ground wire, and bolt it to the ground 

stud at the top of the enclosure.

 

Any single screw terminal is large enough to accept up to two No. 12 AWG conductors.

 

WARNING

 

  -

  Explosion hazard - Substitution of components may impair suitability for 

Class 1, Division 2. 

AVERTISSEMENT

  -  

Risque d’explosion - La substitution de composants peut rendre ce 

materiel inacceptable pour les emplacements de Class I, Division 2. 

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, and D; Class II, Division 2, 
Groups F and G; Class III, Div. 2, or non-hazardous locations only. 