background image

Pub.  42004-139D 

GAI-Tronics 700 Series Page/Party

®

 Systems 

Page:  3 of 10 

\\s_eng\gtcproddocs\standard ioms - current release\42004 instr. manuals\42004-139d.doc 
11/99 

Step 2 — Mounting of Station and Speaker Amplifier Enclosure 

Each Page/Party

®

 system station includes a plug-in amplifier, that mates with a fabricated steel, cast 

aluminum, or molded reinforced non-metallic enclosure.  Each enclosure provides a terminal strip for 
connecting inter-station cable.  Enclosures are packed separately from the plug-in amplifiers at the 
factory, allowing the amplifiers to remain protected while the enclosures are installed and wired — 
particularly important during system installation in areas under construction. 

The 16-gauge steel enclosures do not provide any openings for conduits or cables because the location of 
these will vary with each installation.  Drill or punch the necessary openings before mounting the 
enclosure.  Locate the openings either along the top or bottom of the enclosure and near the rear surface.  
Avoid the top center because of possible interference with the plug-in amplifier receptacle.  A drill 
template is supplied with each enclosure. 

Cast aluminum enclosures are drilled and tapped on the top and bottom for specially-designed hub plates.  
Unless special arrangements are made, the enclosures include plates for single 1¼-inch conduit.  Plates 
for single ½-inch or 1½-inch, or dual inch are available.  The molded enclosures are supplied without any 
conduit openings.  Sealed threaded hubs, such as Myers “Scru-tite”, are recommended.  A drill template is 
supplied with each enclosure. 

CAUTION

 

Use caution when drilling holes to avoid damaging internal electrical components and wiring. 

Suggested mounting height for all station enclosures is 54 inches (137 cm).  Subsets used with remote 
subset amplifiers are supplied with 8-foot (244 cm) cables.  Enclosures for remote subset amplifiers must 
be mounted within reach of the 8-foot cable.  Desktop or desk-edge stations enclosures are often mounted 
in the knee-well of the desk. 

Step 3 — Mounting of Line Balance Assembly 

Each GAI-Tronics Page/Party

®

 system requires one line balance assembly.  Its function is to properly 

load the page and party line circuits.  When using GAI-Tronics standard cable, select a location that is: 

 

near the electrical center of the system 

 

adjacent to an indoor station in a relatively quiet area 

 

no more than 5250 feet (1600m) from the most distant station 

For larger systems or when using other types of cable, contact a GAI-Tronics representative for further 
information.  The line balance assembly has one electrical adjustment that must be made while using a 
station (see below).  The following is the preferred method for mounting the line balance assembly: 

1.

 

Suspend the assembly from the lower side of the indoor wall station using a 1-inch conduit nipple 
(not supplied). 

2.

 

Connect one twisted pair wire for the page circuit and another for each of the party lines between the 
terminal blocks of the line balance assembly and the associated indoor wall station. 

3.

 

Make the wiring connections between the 305 Series Line Balance Assembly and the Model 702 and 
703 Indoor Wall Station enclosures in accordance with the wiring diagrams at the end of this 
publication. 

Summary of Contents for 700 Series

Page 1: ...ation of paging speakers must be carefully considered particularly in areas of high ambient noise or reverberation The speaker amplifier built into each station drives one horn loaded page speaker If...

Page 2: ...elded cables reduce capacitive coupling between SCR power supply cables and Page Party audio cables 3 Isolation Two methods of power source isolation can be used to avoid electrical noise A Use a low...

Page 3: ...te are recommended A drill template is supplied with each enclosure CAUTION Use caution when drilling holes to avoid damaging internal electrical components and wiring Suggested mounting height for al...

Page 4: ...to the terminal strip s in the enclosures GAI Tronics cable is considered to be a Class 1 cable maximum voltage is less than 600 V In a cable tray Class 1 cable may only be grouped with other Class 1...

Page 5: ...the handset from the adjacent handset hook and press the push to page button 3 From the normal speaking distance approximately inch blow steadily into the handset microphone and adjust the control to...

Page 6: ...e Party line circuits Remove these resistors after completion of the tests FeedbackorDistortionontheSystem Each page and party circuit must be loaded to the optimum 33 ohms using the line balance asse...

Page 7: ...uipment does not in normal operation produce arcs sparks or heat that would ignite industrial gases or dusts Many standard GAI Tonics products are approved by Factory Mutual USA and certified by CSA C...

Page 8: ...disconnect switch can be located in a non hazardous area outside the Division 2 area Either method will allow the use of the switch at all times Connect field wiring as detailed in instructions for t...

Page 9: ...Pub 42004 139D GAI Tronics 700 Series Page Party Systems Page 9 of 10 s_eng gtcproddocs standard ioms current release 42004 instr manuals 42004 139d doc 11 99...

Page 10: ...Pub 42004 139D GAI Tronics 700 Series Page Party Systems Page 10 of 10 s_eng gtcproddocs standard ioms current release 42004 instr manuals 42004 139d doc 11 99...