Pub. 42004-451A
Model 13314-004 Div. 2 Hazardous Area 100-Volt Horn Driver
Page:
4 of 4
f:\standard ioms - current release\42004 instr. manuals\42004-451a.doc
05/11
Driver Specifications
Power handling ...................... 30 W
RMS
300–3000 Hz; pink noise 6 dB crest factor; ref. ANSI S4.26–1984
Frequency response..................................................................................... 300–4500 Hz (depends on horn)
Input taps for 100 V line................................................ 3.7, 7.5, 15, and 30 watts (factory set for 30 watts)
Sensitivity ........................................... 109 dB spl @ 1 watt, 1 meter; swept sine average with 13304 Horn
Horn coupling ...........................................................................................Standard 1.375–18 UNEF threads
Housing................................................................ Black; glass and fiber reinforced polyester thermoplastic
Bushing .......................................................................................... Nylon body with neoprene sealing gland
Cable ......................................Extra hard usage flexible cord (Type SO, 18/3) 42 inches (1066.8 mm) long
Impedance ...................................................................................................................Variable (transformer)
Shipping weight .................................................................................................................... 4.3 lbs. (1.9 kg)
Dimensions ....................................................5.0 inches (127 mm) in diameter
×
5.5 inches (140 mm) long
Approvals...................UL & cUL Listed for Class I, Div. 2 Groups A, B, C, D – Temp Code T2C at +40C
Class I, Div. 2 Groups A, B, C, D – Temp Code T2B at +55C
Class II, Div. 2 Groups F & G – Temp Code T4 at +55C
Class III, Div. 2
Weatherproof rating.......................................................................................................................... Type 4X