background image

6.2 Installation

WARNING - TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK, OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:

a.) Installation work and electrical wiring must be

done by qualified person(s) in accordance with
all applicable codes and standards, including
fire-rated construction.

b.) Sufficient air is needed for proper combustion

end exhausting of gases through the flue
(chimney) of fuel burning equipment to prevent
back drafting. Follow the heating equipment
manufacturer’s guideline and safety standards
such as those published by the National Fire
Protection Association (NFPA), and the American
Society for Heating, Refrigeration and Air
Conditioning (ASHRAE), and the local code
authorities.

c.) When cutting or drilling into wall or ceiling, do

not damage electrical wiring and other hidden
utilities.

d.) Ducted fans must always be vented to the

outdoors.

e.) If this unit is to be installed over a tub or shower,

it must be marked as appropriate for the appli-
cation and be connected to a GFCI (Ground
Fault Circuit Interrupter) - protected branch
circuit.

f.) NEVER place a switch where it can be reached

from a tub or shower.

WARNING:

To reduce the risk of fire, use only metal ductwork.

The applicable regulations of the energy supply
companies and the 

regional construction

regulations

must be observed when installing 

the hood.

The

minimum distance

from the worktop to the

bottom edge of the wall hood is for electrical
appliances 25

10

/

16

´ ´ / 650 mm and for gas appliances 

30 ´ ´ / 762 mm.

The wall hood was conceived for the 

exhaust air

mode

. The exhaust air can be routed into a

separate exhaust air shaft or directly into the open
through the outside wall.

It is not allowed to pass the exhaust air into a flue 
or exhaust air chimney that is in operation or into a
shaft that is linked to the heating basement. Consult
the chimney sweep responsible for your district
whenever you wish to pass the exhaust air into a
chimney that is not in operation.

During the course of planning

, a chimney sweep

must be consulted if a room air-dependent hearth 
is operated in the same room as the one in which a
hood is operated in the exhaust air mode. Adequate
incoming air must be ensured. The applicable
construction and safety regulations must be
observed.

Adequate incoming air must be ensured if a wood,
coal, gas or oil heater or an open hearth is operated
in the same room as the one in which the hood is
installed.

Safe operation is possible whenever the partial
vacuum in the place where the firing equipment 
is installed does not exceed 4 Pa (0.04 mbar). 
This can be achieved whenever the air needed for
combustion is able to enter through openings that
cannot be sealed, for example in doors, windows,
incoming/exhaust air wall boxes or other technical
means.

14

Summary of Contents for AH 360-720

Page 1: ...Operating and assembly instructions AH 360 720 Extractor hood...

Page 2: ...ime Page 5 1 3 About use Page 5 2 Structure and operating principle Page 6 7 2 1 Structure of the appliance Page 6 2 2 Accessories special accessories Page 6 2 3 Operating principle Page 7 3 Operation...

Page 3: ...e of the appliance On the following page you will find important notes on safety and operation These will serve to ensure your personal safety and the lasting value of your appliance You will find not...

Page 4: ...dium settings b Always turn hood ON when cooking at high heat or when cooking flaming foods c Clean ventilating fans frequently Grease should not be allowed to accumulate on fan or filter d Use proper...

Page 5: ...ects on the appliance this will have a detrimental effect on functioning Do not clean the appliance with a steam cleaning apparatus or with water pressure because this poses a risk of short circuits I...

Page 6: ...he fact that there are accessories in the packaging Keep packaging elements out of the reach of children Thoroughly clean the appliance before using it for the first time see chapter entitled Cleaning...

Page 7: ...splay 2 Glass plates 3 Air duct 4 Control panel 5 Grease filter key 6 Ventilation level display 7 Coanda level key 8 Light control knob 9 Ventilation level control knob 10 Delayed shut off key 11 Dela...

Page 8: ...orbs the greasy components in the kitchen vapours see Fig 4 The Coanda effect Kitchen vapours are extracted even better with the Coanda effect By means of an additional motor kitchen vapours are passe...

Page 9: ...is displayed for a few seconds Note The light can be switched on and off at any time To do this turn the Light control knob to the Light position Switching on the Coanda level Turn the Ventilation lev...

Page 10: ...sive level for a few minutes and then switches off automatically Ending the intensive level prematurely Turn the Ventilation level knob to the 0 position or turn the Ventilation level knob to any leve...

Page 11: ...ers vertically in the dishwasher to ensure that no food remainders will stay on them Slight discoloration can occur when cleaning the grease filters in a dishwasher When replacing the grease filters w...

Page 12: ...soiled the glass plates can be cleaned in a dishwasher at a maximum temperature of 130 F 55 C Cleaning the aluminium panel Clean the aluminium panel with a soft cloth only Do not use any strong or ca...

Page 13: ...the safety of the appliance Unauthorised tampering with the appliance will invalidate any warranty claims Only ever use original spare parts Lamp replacement Caution Disconnect the power supply before...

Page 14: ...ains whenever required Connection possibilities It must be possible to isolate all poles of the appliance from the mains by way of the domestic fuse or by means of accessible isolating device with a c...

Page 15: ...ations must be observed when installing the hood The minimum distance from the worktop to the bottom edge of the wall hood is for electrical appliances 2510 16 650 mm and for gas appliances 30 762 mm...

Page 16: ...covered exhaust air shaft our condensate separator RV 060 150 must be installed in the exhaust air line The condensate separator must still be acciessible after installation Planning note When install...

Page 17: ...he two hooks d with the countersunk screws c Fit the included dowels a in the other drill holes Note Pay attention to any special accessories that you may have to fit Screw on the retaining bracket fo...

Page 18: ...y into the base Make sure that the fastening holes on the side are at the top Secure the top duct unit with 2 screws on the ceiling holder Pull the shoe down into its final position Fig 19 Note Avoid...

Page 19: ...1 McFADDEN AVENUE HUNTINGTON BEACH CA 92649 USA Y 800 828 9165 FAX 714 901 0979 www gaggenau com us GAGGENAU HAUSGER TE GMBH P O BOX 10 02 50 D 80076 M NCHEN GERMANY Y 0 89 45 90 01 FAX 0 89 45 90 23...

Reviews: