GAC SYC6714 Quick Start Manual Download Page 4

4

Governors America Corp. © 2021 Copyright All Rights Reserved

SYC6714  03-2021-B2      PIB4030

5

SetUp anD SYnCHrOniZatiOn

After connecting your system as detailed in the Wiring diagram, adjust synchronizer performance.  This mode allows for the generator set 

to synchronize to the mains without paralleling occurring.
1.  Add a jumper or remove relay wires at one of the following locations:

• 

Add a jumper between Terminals 7 and 10 

              OR 

• 

disconnect the relay wires at Terminals  13 and 14 or Terminals 14 and 15 

2. 

Confirm the generators governed frequency is set within 0.1 Hz of the mains or other generator. 

3.  Close the connections between the synchronizer and the speed controller.
4.  Trim the speed controller setting so that the generator frequency is within 0.1 Hz of the mains (or other generator) frequency. 
5.  Note the status of the LEDs on the SYC1674.  The MAINS, GEN, and  DC POWER LEDs should show RED. 
6.  Close the connections between the synchronizer and the speed controller.
7.  Close the switch connected from Terminals 5 and 6 between the governing system and the SYC6714. 
8.  Close auxiliary contacts [Parallel Cable +/-] . 
9.  The RED SYNC ENABLED LED should illuminate and the SYC6714 will attempt to synchronize.

A measurement of the phase relationship between the two AC inputs is continuously available as an analog voltage at Terminal 11, 

where 5.1 V indicates phase condition. The SYC6714 controls include GAIN, Stability, to adjust synchronization and performance. 

• 

GAIN adjusts the sensitivity of the synchronization to the speed controller, where CW rotation increases the sensitivity. 

• 

STABILITY adjusts the rate of response time of the synchronizers output. 

• 

BREAKER CLOSURE ANGLE provides a Sync Check circuit with its own variable phase angle window for controlling breaker clo-

sure, Window phase angle may be adjusted between 0 

°

 and 25 

°

.

INITIAl ADJUSTMENT

ADJUSTING AND OPTIMIZING GAIN 

ADJUSTING STABIlITy

ADJUSTING PhASE ERROR

On the SYC6714, adjust GAIN by turning GAIN Adjustment. as far clockwise (CW) as possible without causing instability in the system, 

then turn the GAIN adjustment one division counterclockwise (CCW). When the system is unstable, the main breaker is inhibited from 

closing.

To optimize GAIN, desynchronize the system by opening the switch between Terminals 5 and 6 or momentarily move the engine throttle.   

Reinstate the synchronizer and observe the speed and stability of the synchronization with a synchronizer or a phase meter.  Readjust 

GAIN as necessary.

If necessary, adjust STABILITY for fast, smooth synchronization without instability. A CCW setting will result in a slower (more damped) 

but smoother response.

Set the PHASE ERROR ADjUSTMENT for exact zero phase error. Verify this on a synchroscope, as a measurement of near zero AC 

voltage or a null in AC voltage between Terminals 1 and 3 when the mains and generator voltage are equal.

BREAKER ClOSURE ANGlE

Rotate the BREAKER CLOSURE ANGLE  adjustment clockwise to reduce the window to near 0, inhibiting the breaker closure. The 

phase angle must stay within the angle setting for at least .5 s for synchronization to occur; system stability is very important during 

this time or the setting will need to be set again until the angle is saved. 

To make further adjustment, with the system operating and synchronized, set the breaker closure angle to 0 (fully CW). Adjust 

BREAKER CLOSURE CCW until the BREAKER CLOSURE RELAY LED lights.  The relay should open. Turn the adjustment CCW 

one additional division. The following approximate phase angle window values may be used for setting the breaker closure angle. 

 

BREAKER ClOSURE ANGlE ADJUSTMENT

Adjustment Setting

Breaker Closure Angle

100

0

°

70

6

°

50

12

°

20

18

°

0

25

°