ESD5200 Series Speed Control Unit

   

1-2021-C3

   

PIB1030

ESD5200 Series

Speed Control Unit

2

SPECIFICATIONS

Performance

Isochronous Operation

± 0.25% or better

Speed Range / Governor

1 - 7.5 kHz continuous

Speed Drift with Temperature

±1% MAX

Idle Adjust Clockwise

Minimum 1200 Hz below set speed

Idle Adjust Counterclockwise

Minimum 4100 Hz below set speed

Droop Range

1 - 5% regulation

Droop Adj. Maximum

(K-L Jumpered)

875 Hz., ±75 Hz per 1.0 A change

Droop Adj. Minimum

(K-L Jumpered)

15 Hz., ±6 Hz per 1.0 A change

Speed Trim Range

± 200 Hz

Remote Variable Speed Range

500 - 7.5 kHz

Terminal Sensitivity   

J

L

N

P

100 Hz ±15 Hz/V @ 5.0 kΩ Impedance

735 Hz ±60 Hz/V @ 65 kΩ Impedance

 

148 Hz ±10 Hz/V @1 MΩ Impedance

10 V DC Supply @ 20 mA MAX

InPUT / oUTPUT

DC Supply

12 V DC and 24 V DC Battery Systems 

Transient and Reverse Voltage 

Protected

Polarity

Negative Ground (Case Isolated)

Power Consumption

50 mA (Continuous plus actuator 

current)

Actuator Current Range

@ 77°F (25°C)

10  A Continuous

Speed Sensor Signal

1.0 - 120.0 V AC

Speed Switch Relay Contacts

MAX 10 A (N.O. and N.C.)

Speed Switch Adjustment 

Range

1000-10000 Hz

1

INTRODUCTION

reLIaBILITY

Vibration

5 g @ 20 -500 Hz

Testing

100% Functional Testing

envIronmenTaL

Operating Temperature Range

-40° to 85°C [-40° to 185°F]

Relative Humidity

up to 95%

Vibration

5 g @ 20-500 Hz

All Surface Finishes

Fungus Proof, Corrosion Resistant

comPLIance / STanDarDS

Agency

CE and RoHS Requirements

PHYSIcaL

Dimension

See Outline Diagram

Weight

1.8 lbf [0.82 kgf]

Mounting

Any position, vertical preferred

The ESD5200 Series speed control unit is designed to precisely con-

trol engine speed with rapid responses to transient load changes. The 

ESD5221 is compatible with all GAC proportional actuators except the 

ACB2001 electric actuator. 

Ruggedly built to withstand all engine environments, the ESD can 

control a wide variety of engines in an isochronous or droop mode.  

Capabilities include:

• 

Overspeed Switch and LED Indicator

• 

Selectable Droop Operation

• 

Adjustable Idle Current

• 

Auxiliary Accessory Input

• 

Reverse Voltage Protection

• 

Single Element Speed Switch

• 

Speed Anticipation

Summary of Contents for ESD5200 Series

Page 1: ...Actuator Current Range 77 F 25 C 10 A Continuous Speed Sensor Signal 1 0 120 0 V AC Speed Switch Relay Contacts MAX 10 A N O and N C Speed Switch Adjustment Range 1000 10000 Hz 1 INTRODUCTION RELIABIL...

Page 2: ...peed Control Unit 1 2021 C3 PIB1030 4 Wiring 3 Installation Mount in a cabinet engine enclosure or sealed metal box Vertical orientation allows fluids to drain in moist environments Dimensions Avoid e...

Page 3: ...rs Terminals C and D must be twisted and or shielded for the entire length 6 The gap between the speed sensor and the ring gear teeth should be smaller than 0 20 in 0 45 mm usually obtained by backing...

Page 4: ...ame adjustment procedure steps 1 3 as the GAIN parameter Normally adjustments made at no load achieve satisfactory performance If further performance improvements are required refer to section 10 SYST...

Page 5: ...not in conjunction with a load sharing module a 3 resister should be connected between Terminals N and P This is required to match the voltage levels between the speed control unit and the synchroniz...

Page 6: ...between speed sensor and gear teeth too great Check Gap 2 Improper or defective wiring to the speed sensor Resistance between D and C should be 160 to 1200 See specific mag pickup data for resistance...

Page 7: ...tive actuator Fuse opens Check for short in actuator or harness Engine remains below desired governed speed 1 Measure the actuator output Ter minals A B while running under governor control If voltage...

Reviews: