3
Governors America Corp. © 2021 Copyright All Rights Reserved
EEG7500 Enhanced Electric Governor 8-2021-A8 PIB5115
5
EEG7500 WIRING DIAGRAMS
TermInaL
DefInITIon
connecTIon
GaUGe fIXeD SPeeD varIaBLe SPeeD
PoSITIon
conTroL
A
Actuator (+)
Actuator
16
REQUIRED
REQUIRED
REQUIRED
B
Actuator (-)
16
REQUIRED
REQUIRED
REQUIRED
Battery Ground (-)
12 or 24 V DC Battery
16
REQUIRED
REQUIRED
REQUIRED
Battery Power (+)
16
REQUIRED
REQUIRED
REQUIRED
1
Magnetic Pick-up (+) Mag Pick-up speed sensor
input is not polarity sensi-
tive
20
REQUIRED
REQUIRED
2
Magnetic Pick-up (-)
20
REQUIRED
REQUIRED
3
Digital Input 1
Switch or jumper wire to
Terminal 5
20
REQUIRED with
more than 2 speed
settings
REQUIRED with Idle
speed setting used
REQUIRED with
position select
4
Digital Input 2
Switch or jumper wire to
Terminal 5
20
REQUIRED with
3 speed settings
REQUIRED when
using additional fixed
settings
REQUIRED when
using additional
positions
5
Digital Ground
(GND)
20
REQUIRED with
Terminals 3 and 4
REQUIRED with
Terminals 3 and 4
REQUIRED with
Terminals 3 and 4
6
Analog Ground
(GND)
20
REQUIRED
REQUIRED
7
Analog Input 1
0 - 5 V DC, potentiometer
or 4-20 mA (200 Ω resistor
required)
20
REQUIRED
REQUIRED IF using
Position Control
(Position 4)
8
Analog Input 2
AUX
0 - 10 V DC (5 V Nominal)
OR ±3 V DC (0 V Nominal).
Selectable polarity.
20
9
Analog Input 3
4 - 20 mA
20
10
Analog Input 4
0 - 5 V DC (4 - 20 mA with
200 Ω external resistor)
20
11
+ 5 V Excitation
20
REQUIRED with
potentiometer on
Terminal 7
REQUIRED with
potentiometer on
Terminal 7
12
+ 5 V Excitation
Actuator Position
Feedback Sensor
20
REQUIRED with
Position Control
REQUIRED with
Position Control
REQUIRED
13
Analog Input 5
REQUIRED
14
Analog Reference
Ground
REQUIRED
15
Analog Output
0 - 5 V DC
(25 mA MAX)
20
16
Digital Switch
Output 1
Switch output 2 A MAX
20
17
Digital Switch
Output 2
Switch output 2 A MAX
20
18
Digital Switch
Output 3
Switch output 2 A MAX
20
19
CAN Low
J1939 BUS, Non Terminat
-
ed
(
20
20
CAN High
20
21
RS232
(2)
Ground Reference
20
22
RS232 TX
20
23
RS232 RX
20
recommenDaTIonS
1.
Use shielded cable on all external connections. Ground one end of each shield, including speed sensor shield, to a single point on the EEG case.
2.
Ground controller case to battery (-)
3.
For magnetic pickups and CAN bus, use twisted wires at 14 turns per foot in wire length.
Wire the EEG7500 for either
, detailed in this sections following figures. Items highlighted in the following
table are the minimum connections required before starting. Read this entire manual before starting.
Determine what hardware devices
will be involved in the installation and ensure you know where they are being mapped to on this speed controller. Document your wiring
setup to make setup easier with the GAConfig Tool.