*If the default codes do not work they have been changed by previous installer. We 
cannot default these codes and you must follow procedure with UTC to reset the panel. 

Connecting ZP3 panel to Planner

On the panel

Panel Number 

Select 3 [Setup] > 6 [System Configuration] > 1 [Panel Options] > 2 [Panel Numbers]

Panel number can also be changed

Software Version

Select 1 [Operator] > 2 [Reports to display] >2 [Software Version]

Panel Type

Panel type is best found by opening the door and counting the loops – it will be a 
ZP3 EN4 either 1, 2 or 4 loop.

Set Z-Port 1 to work with Planner

Select 3 [Setup] > 6 [System Configuration]> 3 [Peripheral Comms] > 1 [Comms Parameters]

Set Protocol

Down arrow > Enter > Type 11 on number keys or use up/down arrows until display is [11] – 
ZCP3 then enter.

Set Baud Rate

Down arrow > Enter > Up / Down arrows until you select 9600 > Escape > Home

Connect RS232 cable to port inside door of panel. Commissioning key must be 
set to ON (test light will flash on panel front)