G.M. International D5231E Instruction Manual Download Page 4

 

D5231 

- SIL 2 Switch/Proximity Detector Repeater, O.C. Output 

G.M. International ISM0172-1 

Parameters Table 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D5231 Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

Uo / Voc = 11.2 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5231 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, 
check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the 
effective group. See parameters indicated in the table below: 

D5231 Terminals 

21-13, 21-14, 

22-15, 22-16, 23-17, 

23-18, 24-19, 24-20 

 

D5231 Terminals 

D5231 Associated Apparatus 

Parameters Cenelec (US) 

Ci / Ci  C cable 

 

IIC (A, B) 

Co / Ca = 1.84 µF 
Co / Ca = 12.6 µF 

Co / Ca = 54 µF 

IIB (C) 
IIA (D) 

 

Co / Ca = 49 µF 

Co / Ca = 12.6 µF 

iaD (E, F, G) 

IIC (A, B) 

Lo / La = 253 mH 

Lo / La = 1009 mH 
Lo / La = 2017 mH 

IIB (C) 
IIA (D) 

Lo / La = 3309 mH 
Lo / La = 1009 mH 

iaD (E, F, G) 

Io / Isc = 12 mA 

Ii/ Imax 

 

Po / Po = 34 mW 

Pi / Pi 

 

21-13, 21-14, 

22-15, 22-16, 23-17, 

23-18, 24-19, 24-20 

Li / Li L cable 

 

IIC (A, B) 

Lo / Ro = 1070 µH/

 

Lo / Ro = 4277 µH/

 

Lo / Ro = 8554 µH/

 

IIB (C) 
IIA (D) 

Lo / Ro = 14033 µH/

 

Lo / Ro = 4277 µH/

 

iaD (E, F, G) 

Li / Ri device and 

L cable / R cable 

 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 180pF per meter (60pF per foot), Inductance 0.60µH per meter (0.20µH per foot). 

Summary of Contents for D5231E

Page 1: ...h Proximity Detector Repeater O C Output G M International ISM0172 1 SIL 2 Switch Proximity Detector Repeater Open Collector Output DIN Rail and Termination Board Model D5231E D5231E INSTRUCTION MANUAL INSTRUCTION MANUAL ...

Page 2: ...y 500 V Input switching current levels ON 2 1 mA 1 9 to 6 2 mA range OFF 1 2 mA 0 4 to 1 3 mA range switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA Input equivalent source 8 V 1 KΩ typical 8 V no load 8 mA short circuit Output voltage free SPST optocoupled open collector transistor solid state relay photo MOS Open collector rating 100 mA at 35 V 1...

Page 3: ...y or Voltage free Contact Terminal block connections HAZARDOUS AREA SAFE AREA Input Ch 2 for Proximity or Voltage free Contact Input Ch 3 for Proximity or Voltage free Contact Input Ch 4 for Proximity or Voltage free Contact 13 14 15 16 Output 1 1 Output 2 2 Model D5231 8 channels E Power Bus and DIN Rail accessories Connector JDFT049 Cover and fix MCHP196 Terminal block male MOR017 Terminal block...

Page 4: ... effective group See parameters indicated in the table below D5231 Terminals 21 13 21 14 22 15 22 16 23 17 23 18 24 19 24 20 D5231 Terminals D5231 Associated Apparatus Parameters Cenelec US Ci Ci device C cable IIC A B Co Ca 1 84 µF Co Ca 12 6 µF Co Ca 54 µF IIB C IIA D Co Ca 49 µF Co Ca 12 6 µF I iaD E F G IIC A B Lo La 253 mH Lo La 1009 mH Lo La 2017 mH IIB C IIA D Lo La 3309 mH Lo La 1009 mH I ...

Page 5: ...tact required for line fault detection 23 17 18 24 19 20 In 5 In 6 In 7 In 8 Termination board connector MODEL D5231E 14 2 Out 2 3 Out 3 22 15 16 Common positive connection In 2 In 3 In 4 21 13 11 1 Out 1 In 1 Proximity voltage free Contact 5 6 Out 6 Out 7 Out 8 7 8 Out 4 4 9 10 Supply 24 Vdc Common Ch 1 to 8 Out 5 F Power and Fault Bus Modbus RS485 A B Modbus 12 R2 R1 R2 R1 R2 R1 R2 R1 R2 R1 R2 R...

Page 6: ...5 KΩ range resistor in parallel to the contacts in order to allow the fault detection circuit to distinguish between a condition of contact close open and a line open short circuit fault Installation D5231 series modules are housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022 with or without Power Bus or on customized Termination Board D5231 unit can be mou...

Page 7: ...ected Inputs NO On AND On Close On AND Off Open Off AND Off Open NC On AND On Open On AND Off Close Off AND Off Close OR Output represents OR logical function of selected Inputs NO On OR On Close On OR Off Close Off OR Off Open NC On OR On Open On OR Off Open Off OR Off Close MONITOR Allows the real time monitoring of every Input and Output status Note that configuration is disabled when Monitorin...

Page 8: ...535 65535 65535 65535 65535 65535 65535 65535 3 Tags are composed of 16 characters Each address contains 2 chars starting from left 4 All configurations must be confirmed via Addr 464 see details on the right Notes Supported functions Code Name Notes 03 read holding registers reads a stream of words from memory 04 read input registers reads a stream of words from memory 06 write single register wr...