D1033
- SIL 2 Switch / Proximity Detector Repeater Transistor Output
G.M. International ISM0043-11
5
Parameters Table
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D1033 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check
that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective
gas group. See parameters on
enclosure side and the ones indicated in the table below:
Must
be
Hazardous Area/
Hazardous Locations
Device Parameters
D1033 Associated
Apparatus Parameters
Uo / Voc = 9.6 V
Ui / Vmax
D1033 Terminals
Ch1
Ch2
13 -14
15 -16
Ch3
Ch4
9 - 10
11 - 12
≤
Io / Isc = 10 mA
li / Imax
Ch1
Ch2
13 -14
15 -16
Ch3
Ch4
9 - 10
11 - 12
≤
Po / Po = 24 mW
Pi / Pi
Ch1
Ch2
13 -14
15 -16
Ch3
Ch4
9 - 10
11 - 12
≤
Must
be
Hazardous Area/
Hazardous Locations
Cable Parameters
D1033 Terminals
D1033 Associated
Apparatus Parameters
(IIC-A, B)
Co / Ca = 3.599 µF
Co / Ca = 209.999 µF
(IIB-C)
(IIA-D)
Ci / Ci C cable
Ch1
Ch2
13 -14
15 -16
Ch3
Ch4
9 - 10
11 - 12
≥
Li / Li L cable
Ch1
Ch2
13 -14
15 -16
Ch3
Ch4
9 - 10
11 - 12
≥
Li / Ri device and
L cable / R cable
Ch1
Ch2
13 -14
15 -16
Ch3
Ch4
9 - 10
11 - 12
≥
Co / Ca = 25.999 µF
(IIC-A,
B)
Lo / La = 379 mH
Lo / La = 3035 mH
(IIB-C)
(IIA-D)
Lo / La = 1517 mH
(IIC-A, B)
Lo / Ro = 1530 µH/
Ω
Lo / Ro = 12310 µH/
Ω
(IIB-C)
(IIA-D)
Lo / Ro = 6150 µH/
Ω
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable),
then 50 % of Co and Lo parameters are applicable and shall not be exceeded
(50 % of the Co and Lo become the limits which must include the cable such that
Ci C cable
≤
50 % of Co and Li L cable
≤
50 % of Lo).
If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter).
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system when
the above conditions are respected.
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved);
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved).
NOTE for USA and Canada:
IIC equal to Gas Groups A, B, C, D, E, F and G,
IIB equal to Gas Groups C, D, E, F and G,
IIA equal to Gas Groups D, E, F and G