D1033 

- SIL 2 Switch / Proximity Detector Repeater Transistor Output 

G.M. International ISM0043-11 

Parameters Table 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D1033 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check 
that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective 
gas group. See parameters on

 

enclosure side and the ones indicated in the table below: 

 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D1033 Associated 

Apparatus Parameters 

Uo / Voc = 9.6 V 

Ui / Vmax 

D1033 Terminals 

Ch1 

Ch2 

13 -14 

15 -16 

Ch3 

Ch4 

9 - 10 

11 - 12 

 

Io / Isc = 10 mA 

li / Imax 

Ch1 

Ch2 

13 -14 

15 -16 

Ch3 

Ch4 

9 - 10 

11 - 12 

 

Po / Po = 24 mW 

Pi / Pi 

Ch1 

Ch2 

13 -14 

15 -16 

Ch3 

Ch4 

9 - 10 

11 - 12 

 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

D1033 Terminals 

D1033 Associated 

Apparatus Parameters 

(IIC-A, B) 

Co / Ca = 3.599 µF 

Co / Ca = 209.999 µF 

(IIB-C) 

(IIA-D) 

Ci / Ci  C cable 

Ch1 

Ch2 

13 -14 

15 -16 

Ch3 

Ch4 

9 - 10 

11 - 12 

 

Li / Li L cable 

Ch1 

Ch2 

13 -14 

15 -16 

Ch3 

Ch4 

9 - 10 

11 - 12 

 

Li / Ri device and 

L cable / R cable 

Ch1 

Ch2 

13 -14 

15 -16 

Ch3 

Ch4 

9 - 10 

11 - 12 

 

Co / Ca = 25.999 µF 

(IIC-A, 

B) 

Lo / La = 379 mH 

Lo / La = 3035 mH 

(IIB-C) 

(IIA-D) 

Lo / La = 1517 mH 

(IIC-A, B) 

Lo / Ro = 1530 µH/

 

Lo / Ro = 12310 µH/

 

(IIB-C) 

(IIA-D) 

Lo / Ro = 6150 µH/

 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter). 
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system when 
the above conditions are respected. 
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved); 
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved). 

NOTE for USA and Canada: 

IIC equal to Gas Groups A, B, C, D, E, F and G, 
IIB equal to Gas Groups C, D, E, F and G, 

IIA equal to Gas Groups D, E, F and G 

Summary of Contents for D1033D

Page 1: ...L 2 Switch Proximity Detector Repeater Transistor Output ISM0043 11 D1033D D1033Q INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 2 Switch Proximity Detector Repeater Transistor Output DIN Rail Models D1033...

Page 2: ...zed 1 5 W for 4 channels D1033Q 1 1 W for 2 channels D1033D Isolation Test Voltage I S In Out 1 5 KV I S In Supply 1 5 KV I S In I S In 500 V Out Supply 500 V Out 1 3 Out 2 4 500 V Input switching cur...

Page 3: ...on negative or positive output both accepted in standard version D1033 Transistor Output for fault detection on dual channel version Line fault detection with common signalling available when using Po...

Page 4: ...Ch 3 7 Output Ch 4 8 D1033D Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1...

Page 5: ...F IIB C IIA D Ci Ci device C cable Ch1 Ch2 13 14 15 16 Ch3 Ch4 9 10 11 12 Li Li device L cable Ch1 Ch2 13 14 15 16 Ch3 Ch4 9 10 11 12 Li Ri device and L cable R cable Ch1 Ch2 13 14 15 16 Ch3 Ch4 9 10...

Page 6: ...N HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1033Q 13 14 3 4 1 2 Common Channels 1 3 Supply 24 Vdc Out 1 5 6 Common Channels 2 4 Out 2 7 Out 3 8...

Page 7: ...d actuates the corresponding output transistor two actuation modes can be independently DIP switch configured for each input channel Normally open input Normally close transistor or Normally close inp...

Page 8: ...5 V resistive load The enclosure provides according to EN60529 an IP20 minimum degree of mechanical protection or similar to NEMA Standard 250 type 1 for indoor installation outdoor installation requi...

Page 9: ...4 4 3 3 Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON CH2 Setting Line fault detection ON IN OUT Operation NO NC or NC NO NO NO or NC NC ON O...

Page 10: ...roximity sensor or contact with terminating line resistor OFF Input Output Input Output Output Input Output Input 9 NO 10 OR NC 9 10 9 NO 10 OR NC 9 10 7 NO 2 NC 7 2 7 NO 2 NC 7 2 Input Output Input O...

Page 11: ...witch 8 positions Fault Output 1 OFF ON OFF ON OFF Side B Panel View ON ON NO NC or NC NO NO NO or NC NC Input Output Input Output Output Input Output Input 13 NO 14 OR NC 13 14 13 NO 14 OR NC 13 14 1...

Page 12: ...NO 6 NC 5 6 NO Mode NC Mode No Fault No Fault 8 NO 6 NC 8 6 Switch 4 positions Input Output Input Output 15 NO 16 NC 15 16 8 NC 6 NO 8 6 Switch 8 positions Input Output Input Output 15 NO 16 OR NC 15...

Reviews: