G.M. International D1014S Instruction & Safety Manual Download Page 11

 

D1014 

- SIL 2 Repeater Power Supply Hart compatible 

G.M. International ISM0052-16 

11 



Set multimeter (DMM) for the reading in DC supply, 10 V range. 



Set calibrator (CAL) at 20.000 mA and power supply (PS) at 9.0 V; verify that output voltage (20 mA current on the 250 

 shunt resistance) read by multimeter (DMM) is 

5.000 V ± 10 mV. 



Check that dip switch in the unit is in 1-5 V mode (see “Configuration” section for dip switch position). Connect the unit as shown below: 

(2) 

For voltage output please follow step 2 

 

Calibration instruction and Troubleshooting 

In case a calibration check or readjustment is necessary the following equipment is required: 



Set power supply (PS) at 24.0 V at terminals 3 (+) and 4 (-), the calibrator (CAL) in the function “mA” 20 mA range at terminals 14 (-) and 15 (+), the multimeter (V1) for the reading in 
DC supply 30 V range at terminals 14 (+) and 15 (-), the multimeter (DMM) for the reading in DC supply 20 mA range at terminals 1 (+) and 2 (-). 



Execute the next test to verify D1014S unit channel or execute it twice to verified both D1014D unit channels. 



Check that dip switch in the unit is in 4-20 mA Source Mode (see “Configuration” section for dip switch position). Connect the unit as shown below: 

If the power ON Leds are off, check supply voltage, polarity and wiring. 



Set calibrator (CAL) at 4.000 mA and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation presented in the section “Technical Data”. 



Set calibrator (CAL) at 20.000 mA and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation presented in the section “Technical Data”. 

(1) 

For current output please follow step 1 

Out 2

PS

Supply

=

_

Out 1

+

DMM

+

V1

CAL

In 2

V1

CAL

In 1

DMM

mA

mA

mA

mA

MODEL D1014D

=

=

=

14

15

3 +

4 -

1

2

=

=

=

10

11

5

6

7 +

8 -

=

=

=

=

V

V

Out 2

PS

Supply

=

_

Out 1

+

DMM

+

V1

CAL

In 2

V1

CAL

In 1

DMM

mA

mA

MODEL D1014D

=

=

=

14

15

3 +

4 -

1

2

=

=

=

10

11

5

6

7 +

8 -

=

=

=

=

If the maximum deviation is exceeded, repeat the board calibration and proceed in the following way: 



Set the calibrator (CAL) at 20.000 mA and regulate the current, read by multimeter (DMM), by turning the span trimmer of the unit (see “Configuration” section) until reading 
20.000 mA ± 5 µA value. 



Set the calibrator (CAL) at 4.000 mA and regulate the current, read by multimeter (DMM), by turning the zero trimmer of the unit (see “Configuration” section) until reading 
4.000 mA ± 5 µA value. 



Repeat the last two steps to verify that the span trimmer’ s movement has not significantly modified the value of zero (a dragging of 1/5 exists when moving span and zero values. 



To execute a linearity test: set the calibrator (CAL) at 4.000, 8.000, 12.000, 16.000, 20.000 mA and verify current output is correspondent with a maximum deviation presented in 
the section “Technical Data”. 



Set calibrator (CAL) at 20.000 mA and verify that the transmitter voltage, simulated by calibrator (CAL) and read by multimeter (V1), is correspondent at 15.30 V ± 0.1 V. 

If the transmitter voltage is not correct, regulate it by turning the Vtx trimmer of the unit (see “Configuration” section) until reading the correct value. 

Adjustable Power Supply Range 0-35 V Resolution 0.1 V, 
Accuracy 1% Output Capability 200 mA 
Current Meter range 20 mA, Resolution 1 µA Accuracy 0.01% 
or Voltage Meter Range 10 V, Resolution 1 mV Accuracy 0.01% 

Voltage Meter range 30 V, Resolution 1 mV Accuracy 0.05 % 

Current Calibrator range 20 mA, Resolution 1 µA Accuracy 0.01 % 

Agilent  

E3611A 

Agilent 

34410A 

Fluke  

Yokogawa 

7651 

Equipment Required 

Instrument 

PS 

DMM 

V1 

CAL 

Identification 

Summary of Contents for D1014S

Page 1: ...D1014 SIL 2 Repeater Power Supply Hart compatible ISM0052 16 D1014S D1014D INSTRUCTION SAFETY MANUAL SIL 2 Repeater Power Supply Hart compatible DIN Rail Models D1014S D1014D...

Page 2: ...uracy 0 1 of full scale Linearity error 0 1 of full scale Supply voltage influence 0 05 of full scale for a min to max supply change Load influence 0 05 of full scale for a 0 to 100 load resistance ch...

Page 3: ...locks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Not used Terminal block connections HAZARDOUS AREA SAFE AREA Input Ch 2 for 2 wire Transmitters Input Ch 2 for 2 wi...

Page 4: ...IB C IIA D NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to Gas Groups D E F and G For installations in which both the Ci and Li of...

Page 5: ...SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1014D 14 15 3 4 1 2 RL mA mA V HHT Ch 1 Supply 12 24 Vdc Source I...

Page 6: ...solver is configured to detect High failures and does not automatically trip on these failures this failure mode has been classified as a dangerous detected DD failure Fail Low failure mode that caus...

Page 7: ...shed via conduit connections or another acceptable Division 2 Zone 2 wiring method according to the NEC and the CEC Not to be connected to control equipment that uses or generates more than 250 Vrms o...

Page 8: ...esponding section as an example Connect 12 24 Vdc power supply positive at terminal 3 and negative at terminal 4 for channel 1 For Model D1014D connect 12 24 Vdc power supply positive at terminal 7 an...

Page 9: ...allows the mA sink or source mode or Volt operating mode configuration Configuration Side A Panel View Span Trimmer CH1 Screwdriver for Trimmers 1 x 0 5 mm Dip switch configuration Vtx Adjust Ch1 Scr...

Page 10: ...ly is the same for all channels there for don t separate the terminals because one channel remains switched off Different power supply Cut both pins of the connector to open the wiring between the ter...

Page 11: ...llow step 1 Out 2 PS Supply _ Out 1 DMM V1 CAL In 2 V1 CAL In 1 DMM mA mA mA mA MODEL D1014D 14 15 3 4 1 2 10 11 5 6 7 8 V V Out 2 PS Supply _ Out 1 DMM V1 CAL In 2 V1 CAL In 1 DMM mA mA MODEL D1014D...

Reviews: