5.4.2 DISCHARGE, CHARGE
Application
:
Cyclic measurement of cell voltages of a battery system during
controlled charging or discharging. The desired program is called up
before each cell voltage measurement.
As opposed to a
FLOAT
a
DISCHARGE
, or
CHARGE
is measured here during a charging
or discharging process. An essential difference to a
FLOAT
is that in the testing procedure
the cell/block voltages of a battery system are measured several times. In order to be able
to make a statement concerning a test, a minimum of two measuring sequences are
required (measuring of all cell/block voltages).
If a test has less than two measuring sequences the recorded values are not stored.
Please do refer to the function
Float
for the use of the display and keys.
To be sure of the measurements the measured values can be viewed once again and
when required also re-measured under [DATA] - [SHOW DATA].
5.4.3 RESISTANCE
Application
:
Measuring of the internal block resistances and voltages
Measuring Range
1,00V - 24.0VDC
Connections
[P+] and [S+] must be connected to the +Pole of the battery block
[P-] and [S-] must be connected to the -Pole of the battery block
Key Functions
Interruption of this routine without storage. Can be reactivated in the [DATA] -
[SHOW DATA] menu.
Go back to the block from which the new measurement should be carried out. The
block number will change.
End of the function with
measured value memory store
. The storage is done
automatically if the battery was selected from the internal database before!
The cells of a battery system are measured after ending of the following run sequence:
Press the measuring probes firmly on the cell poles.
Wait for the "high" pitched tone, perhaps the tone sequence for alarm
signals will sound (recording of the measured values).
Remove the measuring probes from the cell poles.
Wait for the single tone (ready for the next measurement).
This procedure is repeated until all cells of the battery system have been measured.
To be sure of the measurements the measured values can be viewed once again and
when required also re-measured under [DATA] - [SHOW DATA].