background image

8. Turn on the A.C. power.  The green A.C. Power On Indicator should be lit when the alarm is

operating from A.C. power.

FIGURE 2. SELECT CORRECT MOUNTING HOLES ON TRIM RING

TAMPER RESIST LOCKING PIN:   To make your smoke alarm somewhat tamper resistant, a locking
pin has been provided with your alarm.  Using this pin will deter children and others from removing
the alarm from trim ring.  To use the pin, insert it into the hole in the side of the alarm after the
alarm has been installed on the trim ring (see Figure 5)

NOTE the tamper resist pin will have to be removed in order to change the batteries.  Use a long
nose pliers to pull the pin out of the hole. It is now possible to remove the detector from the trim
ring.

After installation, TEST your alarm by pressing and holding the test button for several seconds, or
by blowing smoke into the alarm.  This should sound the alarm.

CAUTION! Early warning fire detection is best achieved by the installation of fire detection equip-
ment in all rooms and areas of the household as follows:  A smoke alarm installed in each separate
sleeping area (in the vicinity of - but outside of the bedroom), and heat or smoke alarms in the liv-
ing room, dining room, kitchen, hallways, attic, furnace room, closets, utility storage room, base-
ment, and attached garage.

4. OPERATION AND TESTING

OPERATION: The smoke alarm is operating once A.C. power is applied, fresh batteries are
installed and testing is complete.  When the smoke alarm’s photoelectric chamber senses products
of combustion, the horn will sound a loud (85db) pulsing alarm until the sensing chamber is
cleared of smoke particles.

Rectangular Plaster Ring

Circular Plaster Ring

Octagonal Electrical Box

To remove A.C. 
connector, 
squeeze 
locking arms 
and pull

Alignment
marks

Install

Remove

Tamper resistant
locking pin

FIGURE 3

FIGURE 4

FIGURE 5

FLASHING LED LIGHT: This smoke alarm is equipped with a flashing red indicator LED.  The LED
is located under the test button and has three modes of operation.

Standby Condition

The red LED will flash every 30-40 seconds to indicate that the smoke 
alarm is operating properly.

Alarm Condition

When the alarm senses products of combustion and goes into alarm, 
the red LED will flash rapidly (2-3 times per second). The rapid flashing 
LED and pulsating alarm will continue until the air is cleared.

Low Battery Condition

The LED flash will be accompanied by an audible chirp. Replace the 
battery when this condition occurs.

SMOKE SENSING CHAMBER OPERATION: This alarm will “chirp” if any of the components in the
smoke sensing chamber fail. This chirp will occur 

between

the flashes of the red LED indicator

light. (If the chirp occurs 

at the same time as the red LED flash, see Section 6 for low battery infor-

mation.)

WHEN UNITS ARE INTERCONNECTED, only the red LED of the unit which senses the smoke or is
being tested (the originating unit) will flash rapidly.  All other units in the interconnect system will
sound an alarm but their red LED’s will NOT flash rapidly.

TESTING: Test by pushing the test button on the cover and hold it down for a minimum of 5 sec-
onds.  This will sound the alarm if all the electronic circuitry, horn and battery are working.  If no
alarm sounds, check the fuse or circuit breaker supplying power to the alarm circuit.  If the alarm
still does not sound, the unit has defective batteries or other failure.  You can also test the alarm by
blowing smoke into it.

TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION. Erratic or low sound coming from
your alarm may indicate a defective alarm, and it should be returned for service (see Section 11).

5. NUISANCE ALARMS

Smoke alarms are designed to minimize nuisance alarms.  Cigarette smoke will not normally set off
the alarm, unless the smoke is blown directly into the alarm.  Combustion particles from cooking
may set off the alarm if the alarm is located close to the cooking area.  Large quantities of com-
bustible particles are generated from spills or when broiling.  Using the fan on a range hood which
vents to the outside (non-recirculating type) will also help remove these combustible products from
the kitchen.

If the alarm does sound, check for fires first.  If a fire is discovered, get out and call the fire depart-
ment.  If no fire is present, check to see if one of the reasons listed in Section 2 may have caused
the alarm.

6. MAINTENANCE

ALARM REMOVAL

IF TAMPER RESIST PIN HAS BEEN USED, REFER TO TAMPER RESIST LOCKING PIN IN 
SECTION 3 FOR PIN REMOVAL INSTRUCTIONS.

Summary of Contents for PE120

Page 1: ...an You can trust Fyrnetics to provide the highest quality safety products We know you expect nothing less when the lives of your family are at stake For your convenience write down the following information If you call our Consumer Hotline these are the first questions you will be asked Smoke Alarm Model Number located on back of detector Date Code located on back of detector Manufacturer recommen...

Page 2: ...tallation select locations carefully to avoid thermal barriers that may form at the ceiling For more details see MOBILE HOME INSTALLATION below When mounting an alarm on the ceiling locate it at a minimum of 4 10 cm from the side wall and 2 feet 60 96 cm from any inside corner see Diagram A When mounting the alarm on the wall it is best to use an inside wall with the top edge of the alarm at a min...

Page 3: ...will result in damage to the alarm failure to operate or a shock hazard Make certain alarms are wired to a continuous non switched power line NOTE Use standard UL listed household wire 18 gauge or larger as required by local codes available at all electri cal supply stores and most hardware stores FIGURE 1 INTERCONNECT WIRING DIAGRAM WIRES ON DETECTOR HARNESS CONNECTED TO Black Hot Side of A C Lin...

Page 4: ...e alarm senses products of combustion and goes into alarm the red LED will flash rapidly 2 3 times per second The rapid flashing LED and pulsating alarm will continue until the air is cleared Low Battery Condition The LED flash will be accompanied by an audible chirp Replace the battery when this condition occurs SMOKE SENSING CHAMBER OPERATION This alarm will chirp if any of the components in the...

Page 5: ...alarms offer a broad range of fire sensing capabilities but are better at detecting fast flaming fires than slow smoldering fires Photoelectric alarms sense smoldering fires better than flaming fires Home fires develop in dif ferent ways and are often unpredictable Neither type of alarm photoelectric or ionization is always best and a given alarm may not always provide warning of a fire A battery ...

Page 6: ...unit Return it for servicing to Fyrnetics 1394 South Third St Mebane N C 27302 See Warranty for in warranty returns FIVE YEAR LIMITED WARRANTY Fyrnetics warrants to the original purchaser that the enclosed smoke alarm but not the bat tery will be free from defects in material and workmanship or design under normal use and service for a period of five years from the date of purchase The obligation ...

Reviews: