FXLuminaire LR Installation Notes Download Page 2

WWW.FXL.COM

SYSTEM LAYOUT

We  have  developed  this  series  of  field  installation  guidelines  to  assist  you  in  correctly 

installing fixtures and transformers insuring customer satisfaction and trouble free service.    

If you have any questions please call your local distributor or the FX TechLine at 

800-688-1269

 before proceeding. Follow all NEC guidelines and local electrical codes.  

For further info see our website: www.FXL.com

Single Transformer:

Multiple Transformers:

Circuiting Guidelines:

Lamp Life:

Custom 

Home 

When using only one transformer, it is very important to center the transformer on the  wattage 

load.  If the project calls for 135 watts in both front and back yard, the PX-300 or PX-600 should 

be centered on the side of the house that will receive the most lighting. A common mistake is to 

locate the single transformer on the service side of the house or in the garage, which might result 

in excessively long cable runs to reach lighted areas. The primary goal in laying out low voltage 

systems is to minimize cable runs because of the negative effect voltage drop has on lamp output 

performance.

A common mistake in laying out multiple transformer circuits is to group several transformers in 

one location because of utility or visual considerations only.  As with any low voltage layout, the 

prime directive should be to locate the transformers as close to the fixtures as possible in order to 

minimize cable runs and resulting voltage drop.  The other multi-transformer layout consideration is 

“use zoning”.  Having several transformers allows the client to selectively control light in separate 

areas.  This approach is similar to irrigation design in that the goal is to individually control areas 

that have similar needs. In lighting, a recreation area has different lighting needs than does a front 

entry.  Therefore, the lights that serve these different lighting use areas need to be on separate 

transformers and switch controls.

Loads 

PER CABLE

A

dd cable r

uns as necessar

y

T

T

Close-Zone 0-40’

Mid-Zone 40-80’

Far-Zone 80-120’

Out There-Zone 120-160’

T

T

12 Gauge-160 watts max. 10 Gauge- 220 watts max. 8 Gauge 280 watts max.

12 Gauge-120 watts max. 10 Gauge- 200 watts max. 8 Gauge 280 watts max.

12 Gauge- 80 watts max. 10 Gauge- 140 watts max. 8 Gauge 200 watts max.

12 Gauge-60 watts max. 10 Gauge- 100 watts max. 8 Gauge 160 watts max.

Volts at

Lamp

Lamp Life 

of Rate

Lumen Output 

of Rated

13.0*
12.5*
12.0
11.5
11.0
10.5
10.0

50%
75%
100%
200%
300%
500%
900%

350%
175%
100%
80%
75%
65%
50%

* This voltage is not recommended

• Lamp life is rated in hours of operation. If lamps are rated for 4000 hours               

  at 12 volts it means that at 4000 hours, 50% of the lamps are still work 

  ing and 50% are not.

• For maximum light output, tune lighting circuits to provide between 11.5  

  and 12.0 volts as measured at lamp terminals when all of the lamps on  

  the circuit are operating.

• For longer lamp life, adjust voltage down so lamps receive between 10.5  

  and 11.5 volts at the lamp terminals.

• Voltage can be regulated by adjusting circuit load/run by using FX Po 

  tenxaX Transformers.

• To determine circuit voltage, use FX Digital Voltmeter.

Sample diagram of home with transformer 

and lamp placement