Future Design FDC-C22 Quick Operation User Manual Download Page 2

FDC_C-Series_Quick_Operation_User_Manual_UMQOC621A.doc Page 

2

 of 

20

 

 
 

 

Quick Operation Manual C22/C62/C82/C83/C72/C42/R22 

 

1. DISPLAY AND KEYS: 

 

During power-up, the upper display will show PROG and the lower display will show the Firmware version for 6 seconds. 

SCROLL/ENTER KEY:

 

  

This key is used to select a parameter to be viewed or adjusted. 

 Press 

 for the next parameter. Press 

 and 

 key for return to the previous parameter. 

UP KEY: 

 

This key is used to increase the value of the selected parameter. 

DOWN KEY:

 

 This key is used to decrease the value of the selected parameter. 

RESET KEY:

 

This key is used to: 

1.  Revert the display to the home screen. 

2.  Reset a latching alarm once the alarm condition is removed. 
3.  Stop manual control mode, auto-tuning mode or calibration mode. 

4.  Clear an auto-tuning or communication error message. 

5.  Restart the dwell timer when the dwell timer has timed out. 

6.  Enter the manual control menu if failure mode occurs. 

 

2. MENU FLOWCHART: 

 
 

 

 

       

        

         

 

   

              

5 Sec 

 

    6.2 Sec 

     7.4 Sec 

      8.6 Sec 

 

9.8 Sec           

 

       

 

        

       

       

           

 

 

 

 

5 Sec 

 

5 Sec 

                  2~3 Sec 

User Menu 

Setup Menu 

Manual  Mode  Auto-Tuning Mode  

Calibration Mode  

SCROLL/ENTER KEY:

   1. Press and hold 

 for 5 seconds, display will show

. Press 

 to enter the Setup Menu.  

2. Press and hold

 

 

for 6.2 seconds, display will show

. Press and hold 

 for 5 seconds to enter Manual Mode.  

3. Press and hold 

 for 7.4 seconds, display will show

. Press and hold 

 for 5 seconds to enter Auto-Tuning Mode. 

4. Press and hold 

 for 8.6 seconds, display will show

. Press and hold 

 for 2~3 seconds to enter Calibration Mode. 

 

2.1 User Menu: 

The below user menu 

parameters are available depends on 
user’s selection. 

2.2 Setup Menu: 

The setup menu has 

been categorized into eight categories 
as below. 

1. bASE:

 Basic Menu

  

2. oUT: 

Output Menu

  

3. ALRM: 

Alarm Menu 

 

4. EI: 

Event Input Menu 

2.2.1 Basic Menu (bASE): 

Use 

 or 

 key to get bASE in the lower 

display, then use 

 key to enter basic 

menu parameters. 

Summary of Contents for FDC-C22

Page 1: ...FDC_C Series_Quick_Operation_User_Manual_UMQOC621A doc Page 1 of 20 PID Fuzzy Logic Process Controller C22 C62 C82 C83 C72 C42 R22 Quick Operation User Manual UMQOC621A September 2018...

Page 2: ...rt the dwell timer when the dwell timer has timed out 6 Enter the manual control menu if failure mode occurs 2 MENU FLOWCHART 5 Sec 6 2 Sec 7 4 Sec 8 6 Sec 9 8 Sec 5 Sec 5 Sec 2 3 Sec User Menu Setup...

Page 3: ...2 2 Output Menu oUT Use or key to get oUT in the lower display then use key to enter output menu parameters or SET OUT OUT1 O1TY O1FT O1HY CYC1 OFST OUT2 O2TY O2FT CYC2 CPB DB PL1L PL1H PL2L PL2H 2 2...

Page 4: ...parameters or SET PRoF PROF TSP7 RMPU RPT7 STAR SKT7 END TSP8 PFR RPT8 HBLO SKT8 HBHI TSP9 HBT RPT9 CYCL SKT9 CYCR TSPA STEP RPTA TIMR SKTA STAT TSPB TSP1 RPTB RPT1 SKTB SKT1 TSPC TSP2 RPTC RPT2 SKTC...

Page 5: ...rrent input 0 5V 0 5VDC linear voltage input 1 5V 1 5VDC linear voltage input 0 10 0 10VDC linear voltage input 9 UNIT Input unit selection oC C unit oF F unit Pu Process unit 10 DP Decimal point sele...

Page 6: ...Relay output SSrd Solid state relay drive output 4 20 4 20mA linear current 0 20 0 20mA linear current 0 5V 0 5VDClinear voltage 1 5V 1 5VDC linear voltage 0 10 0 10VDC linear voltage 30 O2FT Output 2...

Page 7: ...Output 48 A3FN Alarm 3 function for alarm 3 output NoNE No alarm function dtMR Dwell timer action dE HI Deviation high alarm dE Lo Deviation low alarm db HI Deviation band out of band alarm db Lo Devi...

Page 8: ...535 71 PROG71 Program code C22 22 XX C62 62 XX C82 82 XX C83 83 XX C72 72 XX C42 42 XX R22 23 XX 72 CMND Command code Low 0 High 65535 73 JOB1 Job code Low 0 High 65535 74 JOB2 Job code Low 0 High 655...

Page 9: ...A3SP is moved to USER Menu A3dV A3DV is moved to USER Menu A4HY A4HY is moved to USER Menu A4SP A4SP is moved to USER Menu A4dV A4DV is moved to USER Menu PL1L PL1L is moved to USER Menu PL1H PL1H is...

Page 10: ...ission output Remote SP 1 5V 1 5VDC retransmission output Remote SP 0 10 0 10VDC retransmission output Remote SP A 4 20 Alarm 4 4 20mA retransmission output Remote SP A 0 20 Alarm 4 0 20mA retransmiss...

Page 11: ...nt for heater short 1 Low 0 0 High 120 0 123 HS2T Triple point current for heater short 2 Low 0 0 High 120 0 124 RMSP Remote SP type None No Remote SP 4 20 4 20mA retransmission output 0 20 0 20mA ret...

Page 12: ...CoNt Run Profile as RUN CONT PV Run Profile as RUN PV HoLd Run Profile as RUN HOLD StoP Run Profile as RUN STOP 144 E4FN Event input 4 function SP5 SP5 activated to replace SP1 Others Same as E3FN 14...

Page 13: ...13 of 20 161 222 For Profiler parameters description please refer to full version user manual 4 WIRING DIAGRAM C22 Terminal Connection C62 Terminal Connection C82 C42 Terminal Connection C83 Terminal...

Page 14: ...MD and A4MD available for each alarm function A1FN A2FN A3FN and A4FN In addition to the alarm output output 2 can also be configured as an alarm But output 2 has only provides 8 different alarm funct...

Page 15: ...t type will be stored in the memory If the input type is changed a calibration error will occur and an error code is displayed 5 10 Digital Filter In certain applications the process value is too unst...

Page 16: ...nsmission option installed RELO and REHI are adjusted to specify the low scale and high scale values of retransmission 10 HEATER CURRENT MONITORING A current transformer CT98 1 is required to measure...

Page 17: ...data to the slave 15 ER15 Communication error write a value which is out of range to a register Do not write an over range data to the slave register 16 EIER Event Input Error Two or more event input...

Page 18: ...FDC_C Series_Quick_Operation_User_Manual_UMQOC621A doc Page 18 of 20 Page Left Intentionally Blank...

Page 19: ...rnians about significant exposures to chemicals that cause cancer birth defects or other reproductive harm These chemicals can be in the products that Californians purchase in their homes or workplace...

Page 20: ...s or losses whether direct indirect incidental special consequential or any other damages costs or expenses excepting only the cost or expense of repair or replacement of Future Design Control product...