After installation and testing of this product it is essential that the INSTRUCTION LEAFLET is available for reference 

 

RTMA RCBO MINI 2POLE  
Instruction Leaflet 

DOC:RCBOMINI2020

 

 
 
 

4     Testing  

4a   

CONNECTIONS TO THE MINI RCBO DO NOT REQUIRE TO BE DISCONNECTED IF THE LEVER IS IN THE 

OFF

 POSITION.

 

4b   On completion of the installation, it must be tested in accordance with the latest edition of the IET Wiring Regulations for 

Electrical Installations (BS 7671). 

 

 

Operation of the TEST button on RCBO 

When newly fitted systems do not trip on the TEST button or using the RCD tester the problem is normally caused by an earth to 
neutral fault on the circuit (PME supply). 
Installers can easily check the RCBO by removing the LOAD connections on the RCBO and applying power.  If the TEST button 
works the fault is in the circuit.  
 

RCBO TEST  

RCBOs ARE MANUFACTURED IN ACCORDANCE WITH 

IEC 61009-1

 AND MUST BE TESTED TO THIS SPECIFICATION USING A 

CALIBRATED TEST METER. 
General type 

0.5IΔn

   

RCBO will not trip 

1Δn

 

 

RCBO must trip within 300ms 

5IΔn

 

 

RCBO must trip within 40ms 

 
What to do if a RCBO trips

 

Reset tripped RCBO to 

ON

 position 

If RCBO trips again then disconnect all appliances connected to this circuit. 

Switch RCBO to 

ON

 position and connect 1 appliance at a time to see which one trips the RCBO. 

Once the faulty appliance has been identified, DO NOT USE appliance until it has been checked. 

Switch RCBO to 

ON

 position. 

If fault does not clear phone a qualified electrician to check installation

 

 
 
 

 