Furrion ATS series Manual Download Page 6

WIRING YOUR F50-ATS:

50amp 125/240VAC Wiring

Ground = Bare copper wire or green

Neutral = White

Live/Hot L1 = Black

Live/Hot L2 = Red

50amp 120VAC Wiring

Ground = Bare copper wire or green

Neutral = White

Live/Hot = Black

Using the quick reference wiring guide on the lid of the ATS box, arrange the wires to be 

fed into the ATS for connection at the corresponding terminals. 

Generator in

Shore Power in

Line/feed out

Ensure to feed the wires through the cable strains when they enter to ATS box.

Shore power and generator cables should be fed into the ATS from the side marked

on the box sticker.  

The line out wires will enter the ATS from the opposite side.

See below diagram for wiring layout.

 

Strip 4” of outer jacket from each of the incoming cables.

Strip ½” of jacket from each of the wire conductors.

Connect the colored wires to the ATS terminals using the diagram above

Using your #2 (Robertson’s) square head torque Screwdriver, tighten the terminal screws 

to 20in-lb minimum and 25in-lb maximum

Connect the chassis grounding 8AWG wire to the grounding terminal block on the inside 

of the transfer switch box. Use the 3/8” through hole to feed the wire through from the 

outside of the box directly to the terminal block.

Using your #2 Square Head Torque Screwdriver, tighten the grounding block terminal 

screws to 20in-lb minimum and 25in-lb maximum.

 

Summary of Contents for ATS series

Page 1: ...50amp 125 250V Automatic Transfer Switch F50 ATS Furrions ATS is used to safely switch automatically between mutiple power sources...

Page 2: ...terminals this will start a timer and automatically switch over to generator power supply after a 20 30 second delay which ensures the generator has sufficient time to run up to speed before electrica...

Page 3: ...LL SMART PLUG FEATURED BELOW GENERATOR 50Amp 125 250 VAC 12KW Generator Configuration 2 Triple power feed same rating This configuration is used when a inverter is added to the system and requires aut...

Page 4: ...0 20 20 DISTRIBUTION PANEL 1 Input 2 Input 1 F30 ATS Transfer switch Output feed POWER INVERTER MAX 3000W EXAMPLE 3 100 100 50 50 75 75 50 50 50 50 70 70 15 20 20 15 15 20 20 50 50 20 30 20 30 75 75 2...

Page 5: ...nt of entry or generator output Typical examples of mounting locations are Inside seat or bed compartments Above or behind cabinets Under floor storage compartments etc To mount the ATS box the 4 scre...

Page 6: ...the box sticker The line out wires will enter the ATS from the opposite side See below diagram for wiring layout Strip 4 of outer jacket from each of the incoming cables Strip of jacket from each of...

Page 7: ...rom the generator the green LED indicator light on the internal ATS PCB will illuminate the ATS has a 20 30 second time delay before engaging the internal contactor to allow for the generator to warm...

Page 8: ...N OBJECTS INSIDE ENCLOSURE Reasons Poor installation can cause wood chippings sawdust metal filings or other foreign matter to enter the case Unsuitable mounting position can cause condensation moistu...

Page 9: ...ption One Using the external lugs which are located on the outside of the box Mounting dimensions for the external lugs are Outer Lugs 189 x 220mm 7 x 8 11 16 7 16 Option Two Using the 4 x internal ho...

Reviews: