Furman PWRPORT Owner'S Manual Download Page 2

A  simple  connection  of  the  REM  IN  terminal  to  the  +12V 

terminal initiates an OFF sequence. Disconnecting it initiates an 

ON sequence. If the cable run is long, it is recommended that the 

REM IN wire be tied to the PowerPort’s GND terminal during ON 

operation rather than leaving it floating. This will require the use 

of a third conductor and a double-throw switch.

Momentary Mode

In Momentary Mode, the PowerPort has “memory” — it only 

needs a momentary signal from the remote switch to change its 

state from ON to OFF.

When  first  plugged  in  (or  after  power  is  lost  and  reapplied 

for any reason) the “memory” state is OFF. This means the unit 

will  be  off.  It  will  stay  off  until  sequenced  on  by  a  momentary 

connection of the REM IN terminal to +12V. The sequence starts 

on the rising edge of the signal. The “memorized” state will track 

the input, so that the PowerPort will stay in synch with any other 

units controlled by the same remote signal.

Because  it  is  a  maintained-contact  switch,  the  RS-1  is  not 

an  appropriate  remote  switch  for  the  PowerPort  when  it  is  in 

momentary mode. Use the RS-2 momentary switch instead.

Front Panel Slide Switch 

If the PowerPort’s front panel slide switch has been moved 

to either OFF or ON, and then back to REMOTE, the unit will be 

OFF until it receives a remote actuation signal.

Status Output 

The  STATUS  terminal  is  an  output  that  may  be  used  to 

illuminate an LED at the remote location to indicate that power is 

available at the PowerPort’s outlets. If it is high (+5V), the unit is 

ON (or at least in the process of sequencing ON); if low, the unit 

is OFF (or sequencing OFF). Simply connect the indicator LED 

between STATUS and ground (do not use a series resistor). If the 

LED does not light when the switch is in the ON position, check 

the polarity and reverse the LED leads (if it is wrong). If a Furman 

RS-1  is  the  controlling  switch,  contact  Furman’s Tech  Support 

department for the proper wiring diagrams.

Multiple Units

Use  one  PowerPort  for  each  20-amp  circuit.  To  control 

multiple PowerPorts with one or more remote switches, connect 

the REM IN, +12V and GND terminals of all units together. Be 

sure that the mode (momentary or maintained) of all units is set 

the  same.  Connect  a  single  maintained  switch  or  one  or  more 

momentary switches to the PowerPort nearest the switch.

If  multiple  PowerPorts  are  controlled  by  one  or  more 

momentary  remote  switches,  they  will  all  switch  at  each  rising 

edge of the voltage on the REM IN terminal. Any remote switch 

will toggle all the units. The slide switch on each unit's front panel 

will turn off that unit without affecting the other units.

The STATUS outputs work the same in either momentary or 

maintained mode. Each reflects the true state of the outlets of 

its unit, and is affected by both the “memorized” state or by the 

front panel slide switch. A separate LED and wire must be used 

to indicate the status of each PowerPort.

To  take  care  of  the  special  (hopefully  rare)  case  of  having 

several  PowerPorts  in  parallel  that  somehow  get  out  of  sync 

such  that  every  time  a  remote  button  is  pushed,  some  units 

turn  on  and  others  turn  off,  there  is  a  special  feature  of  the 

remote  signal  line:  Keeping  a  remote  switch  pushed  in  for  at 

least 4 seconds will force all units to the OFF state, and put them 

back  in  sync. This  is  the  only  way  to  re-sync  units  other  than 

disconnecting AC power to all the units. Remember — operating 

the front panel slide switch does NOT affect the stored state of the 

unit, even though it does temporarily turn the outputs off. 

Shutdown Terminal

Shutdown is a dual function terminal. It can be an INPUT or 

an OUTPUT. As shipped, it is an OUTPUT. An LED connected 

between this terminal and ground displays the same information 

as the PowerPort's front panel Power Status LED. This is useful 

for remote visual monitoring of each unit's operating status.

As  an  alternative,  the  Shutdown  Terminal  can  be  used 

as  a  Force  Off  INPUT.  Force  Off  is  a  function  that  allows  the 

PowerPort  to  be  switched  off  instantly. This  is  useful  as  an

 emergency “kill switch”. In this mode, grounding the shutdown 

terminal  forces  the  unit  off  with  no  time  delay. To  change  the 

Shutdown Terminal from an LED OUTPUT, to a Force Off INPUT:

Now  your  PowerPort  is  set  for  remote  Force  Off  INPUT 

operation.

Note: If you are using the Shutdown Terminal as a Force Off 

INPUT,  and  have  multiple  PowerPorts  connected  together,  be 

sure that all Shutdown Terminals are wired together, and that the 

jumpers in all units are set the same. Once the system has been 

forced  off,  it  will  stay  off  even  after  the  Shutdown Terminal  is 

ungrounded. To  turn  the  PowerPort(s)  back  on,  the  Shutdown 

Terminal must be ungrounded and a maintained remote switch 

must be turned off then on again, or a momentary switch must 

be pushed twice. The Shutdown Terminal is pulled to +5 VDC by 

an Internal 10K resistor. It must be pulled down to <300 millivolts 

DC for at least 50 milliseconds to initiate a shutdown.

Symptom:             PROTECTION OK Indicator not lit after ON delay has elapsed.  
Possible Cause:    Protection devices have been damaged.  
Action Needed:     Factory service.

Symptom:             GROUND OK Indicator not lit. 
Possible Cause:    No building ground, bad outlet.  
Action Needed:     Locate good ground, run ground wire.

Symptom:             OUTLET ON Indicator not lit after ON delay has elapsed.  

Possible Cause:    An abnormal condition exists.  
Action Needed:     Verify that line voltage and earth ground are okay. 
                             If both are okay, contact factory service.

Symptom:             MAINS OK Indicator flashing.  
Possible Cause:    PowerPort is receiving either 80-90 or 130-140 volts.  
Action Needed:    Correct line voltage. Consider installing a Furman AR-PRO or 
                             AR-1215 voltage regulator.

Symptom:             POWER STATUS Indicator flashes (and therefore power 
                             to the outlets does not switch on).  
Possible Causes: (1): The input voltage is nearly out of or not within the 
                             acceptable range. 
                             2): The front panel REMOTE (NORMAL)/ON/OFF (OVERRIDE) 
                             switch is not positioned to REMOTE (NORMAL), making the  
                             PowerPort unable to accept a remote command.  
Action Needed:     (1) Check and correct incoming voltage.
                             (2) Check the switch and make sure it is positioned to 
                             REMOTE (NORMAL). 

Symptom:             EXTREME VOLTAGE Indicator flashing.  
Possible Cause:    Input voltage is below 80 or above 140 volts, causing power to  
                             PowerPort’s outlet to be shut down.  

Troubleshooting

1. Disconnect the unit from AC power.

2. Remove the four screws that secure the top cover.

3. Near the left rear corner of the circuit board there are two  

    pairs of terminals labeled J3 FORCE OFF, and J4 

    SHUTDOWN/POWER STATUS. Slide the jumper off of J4  

    and then slide it onto J3.

4. Reattach the top cover.

5. Connect a remote switch or automated shutdown system 

    between the Shutdown Terminal and ground.

Summary of Contents for PWRPORT

Page 1: ...nal barrier strip provides for a number of remote control and LED monitoring options A PowerPort can be unobtrusively installed in the front or rear of a rack see back page For permanent installations the AC cord may be removed and replaced with a standard 1 2 conduit fitting Safety Information To obtain best results from your Furman PowerPort please be sure to read this manual carefully prior to ...

Page 2: ...l units to the OFF state and put them back in sync This is the only way to re sync units other than disconnecting AC power to all the units Remember operating the front panel slide switch does NOT affect the stored state of the unit even though it does temporarily turn the outputs off Shutdown Terminal Shutdown is a dual function terminal It can be an INPUT or an OUTPUT As shipped it is an OUTPUT ...

Page 3: ...intained Mode or push the Momentary button twice in Momentary mode If the switch is moved from the REMOTE position to the OFF position power will be immediately removed from the outlet ON DELAY Screwdriver adjustment to set ON time delay from 0 to 60 seconds POWER STATUS This LED will light and remain lit only for the duration of an ON or OFF delay sequence It will flash continuously if either of ...

Page 4: ...tions This warranty shall be cancelable by Furman at its sole discretion if the PowerPort unit has been subjected to physical abuse or has been modified in any way without written authorization from Furman Furman s liability under this warranty is limited to repair or replacement of the defective unit Furman will not be responsible for incidental or consequential damages resulting from the use or ...

Reviews: