Verkstadsvägen 2, 931 61 SKELLEFTEÅ, Sweden

Skellefteå: 

Tel.Int. +46 910-361 80, Fax.Int. +46 910-130  22

DRIFTSINSTRUKTIONER

OPERATION INSTRUCTIONS

0522

Produktion: 

Autotech SPS 

AB Boliden

S   GB

D

W2

U1

U2

V1

V2

W1

L1

L2

L3

(L3)

(L1)

Y

W2

U1

U2

V1

V2

W1

L1

L2

L3

(L3)

(L1)

Z2

U1

U2

Z1

L1

N

Z2

U1

U2

Z1

L1

N

3

Temperature

Warning!

When the fan operates the fanhousing takes the

temperature of the conveyed media. If that temperature

exceeds 50°C the fan must be protected from direct

contact to prevent burninjury.

4

Electrical connection

Warning!

Electrical connection must be made by skilled labour

only. The drivemotor should be protected with an

overload switch.

5

Permitted applications

Warning!

F-fans are not to be used for conveying aggressive, toxic

or air with high humidity or gas or explosive air-gas

mix.

6

Sound level

The sound pressure level is not the same over the fans

whole range. In some cases it is necessary to use a

silencer. We recommend the user to check the sound

pressure level.

D

Installation

1

Transportation

Check all parts for damage during transportation and

that the impeller runs free inside the housing. The

blowers are to be installed in weather-protected places

and are not to be stored outdoors unprotected. Mount

hoisting hook carefully, and do only use lifting

arrangements with sufficient strength.

2

Arrangements and assembling

Mount the fan horizontally or vertically in a weather-

protected place. Make sure that the fan is protected from

vibration and shock. Supply open inlet and dis-charge

openings with guards according to valid regulations.

Make sure that the drive motor is supplied with sufficient

ventilation. The permitted maximum temperature of

surroun-dings is 40°C.

3

Electrical connection

Attention

!

The operations described in this part is to be made by

skilled labour only. Connect the fan in accordance with

the wiring diagram in the terminal box. The respec-tive

VDE regulations and the directions of the local power

supply company are to be complied with.

The fan is equipped with a drivemotor for single- or

three-phase AC. The motor should be protected with an

over-load switch. Connection to earth is to be found in

the terminal box.

Connection of three-phase AC unit

 (Low voltage 

D

-connection)    (High voltage Y-connnection)

Connection of single-phase AC unit

The arrows are seen from the inlet side

4

Inspection of rotation direction

Start up the fan for a short moment, inspect the rotation

direction. The rotation direction on the impeller must

be in accordance with the arrows on the motor. If not,

move the L1 and L3 phases for three-phase operation

or check the wiring circuit in the terminal box for single-

phase operation. Incorrect rotation direction will cause

reduced capa-city of the fan.

E

Start of operation

If the rated current indicated on the rating plate is being

exceeded during opera-tion, it should be checked whether

the available supply voltage and frequency are in

accordance with the embossed data. Some blowers

cannot be ope-rated with free airflow (see catalogue).

The drivemotor is sized for the power requirements

when the fan operates in the filled part of the capacity

curve. At lower resistance the working range moves out

to the pointed part of the capacity curve and the airvolume

and current increase. The motor will be overloaded with

possible overheating as a consequence. To avoid overload

it is possible to fit a throttle flap on the inlet- or

dischargeside. Do not expose the fan to vibrations and

shock.

F

Maintenance

F blowers are equipped with enclosed grooved ball

bearings which do not need lubrication. The grease

filling is sufficient for the whole service life of the

bearings.

Attention!

Repair work on blowers should be done in the factory

only. We do not take any responsibility for repairs made

by third parties.

G

Spare parts  list

When ordering spare parts please state size of blower

and part number in ac-cordance with the spare parts list.

H

EC Manufacturer Declaration

Manufacturer:

Fumex AB

Verkstadsvägen 2

S-931 61  Skellefteå

Sweden

We certify that the product to which this certificate

relates, is in conformity with the standards or standard-

setting documents listed below. If a modification of the

unit (s) is made without our approval, this declaration

becomes invalid.

Description of the product:

High pressure fans type F

Relevant regulations to which these products

correspond:

EC Machine directive 98/37/EG

EC Low voltage directive LVD 73/23/EEC

Electromagnetic compability EMC 89/336/EEC,

92/31/EEC, 93/68/EEC

Source references of harmonized standards:

LVD

EN 60034

EMC EN 55014-1, EN 60555-1

MD

EN 292-1, EN 60204-1 (safety of Machinery)

Starting operation of this machinery part is not allowed

as long as it is not assembled into the main installation

respectively not all necessary safety devices have been

installed which fulfil the requirements of the EC directive

for machines with regard to safety and health.