background image

0359-CPR-00438

3. Connection Details

1. Mounting Base

2. Sounder/ Beacon Assembly

Table 1. Specification

Technical Data 25-12947-A

                   September 2014

Supply Voltage (Conventional)  18~35 Vdc

Cable Size/type 

 

  

0.5~2.5mm

 /

 FIRETUF, FP200  or MICC

Current (High Volume) 

  11mA

Current (Low Volume) 

  8.7mA

Sound Output (High Volume)    90 +/- 3dB(A) 

Sound Output (Low Volume)    80 +/- 3dB(A)

Operating Temperature 

  -10 to +55ºC (95%RH)

Material   

 

  ABS FR Plastic

Environmental Category 

  Type A= IP21C

Tones 

 

 

  3, See section 4.

Flash Rate 

 

  0.5Hz (

Not applicable to FXN5023S

)

Feature

Value

Feature

Value

 SQG3-23 Base Sounder VAD

Compliance EN54-3; EN54-23:2010

14

OUT IN

SCREEN

ZONE OUT

ZONE IN

+VE  -VE

+VE  -VE

ZONE IN

ZONE OUT

Screen must be continuous 

along entire length of loop.

50
60
70
80

(i) Knock-out the required

fixing holes.

(ii) Fix to mounting surface

using two suitable screws.

(iii) Please ensure all cable 

entry points are sealed 

appropriately.

If the base deforms on an 

uneven surface, loosen the 

screws or move to a flatter 

position.

Flash On Period                        60ms

www.acornfiresecurity.com

www.acornfiresecurity.com

Reviews: