
F39 - Fan cut off due to high temperature in the evaporator (S2 sensor):
This is intended to disconnect the evaporator fan when the room temperature is not within the design
range for the refrigeration device, avoiding high temperatures and suction pressures that could damage
the compressor. If the evaporator temperature exceeds the set value, the fan is turned off and will be
restarted at a fixed hysteresis of 2°C (3.6°F). This is a useful function to use when, for example, a
refrigerator is used that has been idle for days or when restocking units or counters with products.
F40 - Temperature in the evaporator to switch the fan back on after draining:
After drainage is complete, it starts a fan-delay cycle. The compressor will start up immediately,
because the temperature in the evaporator is high, but the fan will only start after the temperature in the
evaporator falls below the set value. This function is used to remove the heat that still exists in the
evaporator due to the defrost, avoiding throwing it into the environment.
F41 -Maximum length of time until the fan is switched back on after drainage (fan-delay):
For safety, if the temperature in the evaporator does not reach the value set by function
[F40]
or the S2
sensor is disconnected, the fan will only come on after the time set for this function has expired.
F42 - Function mode of the digital input:
[,,,0]
: Digital input disabled;
[,,,1]
: Contact NO - Door sensor;
[,,,2]
: Contact NC - Door sensor;
[,,,3]
: Contact NO - External alarm (indication only);
[,,,4]
: Contact NC - External alarm (indication only);
[,,,5]
: Contact NO - Control shutdown;
[,,,6]
: Contact NC - Control shutdown;
[,,,7]
: Pushbutton NO - Economy mode;
[,,,8]
: Pushbutton NC - Economy mode;
[,,,9]
: Pushbutton NO - Fast Freezing;
[,,10]
: Pushbutton NC - Fast Freezing;
[,,11]
: Pushbutton NO - Defrost;
[,,12]
: Pushbutton NC - Defrost;
[,,13]
: Door temperature sensor, anti condensation (S3 sensor).
F43 - Length of time door is open for instant defrost if
[,F42]
= 1 or 2:
If the door is kept open for a period longer than that defined in this function, instant defrosting will take
place, as long as the temperature in the evaporator (S2 sensor) is less than
[F31]
and the room
temperature (S1 sensor) is less than
[F32]
.
F44 - Length of time door is open until fan and compressor are turned off
[,F42]
= 1 or 2:
For safety, if the door remains open longer than the time set here, both the compressor and fan will be
switched off.
F45 - Length of time door is closed until light is switched off if
[,F42]
= 1 or 2 and
[,F70]
= 1:
With the door closed, this parameter defines how long it will be until the lamp is turned off. Helps save
electricity.
F46 - Length of time door is closed until economy mode is activated if
[,F42]
= 1 or 2:
With the door closed, this parameter defines how long until economy mode is activated. The ouputs fot
the lamp will be deactivated if it is turned on and the operational setpoint is switched to the economy
setpoint.
F47 - Maximum time in economy mode with closed door if
[,F42]
= 1 or 2:
Allows you to configure a maximum time for the economy mode to operate while the door is closed. After
this time, the setpoint returns to economy mode in normal operation.
F48 - Minimum variable compressor on time:
This is the minimum amount of time the compressor will be on, i.e. The period of time between the last
section and the next time it is stopped. This helps to avoid power surges from the electricity grid.
F49 - Minimum time of variable compressor off:
This is the minimum amount of time the compressor will be off, i.e. The period of time between the last
time it stops and the next section. This helps to relieve the discharge pressure and increases the
working life of the compressor.
F50 - Proportional Gain (P):
Determines the proportional increase based on the PID Control Algorithm.
F51 - Full Time (I):
Determines the Integral Time based on the PID Control Algorithm.
F52 - Derivative Time (D):
Determines the derivative time of the PID Control Algorithm.
F53 -Minimum frequency for variable compressor PID control:
Defines the minimum working frequency of the variable compressor in automatic control mode (PID
algorithm).
Note:
check the technical manual of the variable compressor.
F54 - Maximum frequency for variable compressor PID control:
Defines the maximum working frequency of the variable compressor in automatic control mode (PID
algorithm).
Note:
Check the technical manual of the variable compressor.
F55 -Maximum operating frequency of the variable compressor:
Defines the maximum operating frequency of the compressor. This frequency is used when it is
necessary to quickly cool the controlled environment, for example, high temperature in the controlling
environment, for example, high temperature in the environment
[F69]
, Fast Freezing process or after
a defrost cycle.
Note
:
Check the technical manual of the variable compressor.
F56 - Compressor stop frequency (switch-off):
Defines the output frequency to inform the compressor to stop. This frequency is lower than the
minimum working frequency
Note
: Check the technical manual of the variable compressor,
F57 - Variable compressor frequency during a hot gas defrost:
Sets the frequency of the variable compressor during the hot gas defrost process, when
[,F20]
= 1.
F58 - Variable compressor frequency in the event of and error in sensor S1 (room sensor):
Defines the frequency of the variable compressor if an error is detected for temperature sensor S1
(room sensor). This parameter works in conjunction with
[F59]
and
[F60]
.
F59 - Variable compressor time on in case of error in sensor S1 (room sensor):
F60 - Variable compressor time off in case of error in sensor S1 (room sensor):
If the room sensor (S1 sensor) is disconnected or goes out of the measurement range, the compressor
will switch on or off according to the parameters set in these functions.
F61 - Variable compressor smooth start frequency:
When switching on the variable compressor, it is kept at a low speed for a few seconds, as set in
[F62]
. The purpose of this feature is to improve the lubrication of the compressor.
F62 - Variable compressor smooth start time:
When switching on the variable compressor, it is kept at a low speed for a few seconds, as set in
[F62]
. The purpose of this feature is to improve the lubrication of the compressor.
F63 - Variable compressor time on after reaching the setpoint:
After reaching the temperature setpoint, it is possible to keep the compressor running at a speed
calculated by the PID control algorithm. The purpose is to avoid successive starts of the compressor,
obtaining a reduction in energy consumption (energy efficiency) as well as low oscillation of the room
temperature (sensor S1).
If set to
[OFF,]
, the variable compressor is switched off immediately after reaching the temperature
setpoint. If set to
[On,,]
, the compressor will always be on.
In case the temperature reaches the low temperature limit
[F68]
, the compressor is switched off and
will start again according to the setpoint and the control hysteresis.
F64 - Variable compressor time below the limit frequency
[,F66]
for lubrication:
Time in which the variable compressor must be turned on with the frequency below the limit set in
[F66]
to operate at the frequency set in
[F54]
for the time set in
[F65]
.
This process of periodic acceleration of the control frequency promotes lubrication of the variable
compressor through the migration of the lubricating oil.
F65 - Variable compressor time on frequency
[,F54]
for lubrication:
Time that the variable compressor will stay on at the frequency defined in
[F54]
for lubricating the
compressor.
F66 - Minimum frequency for variable compressor lubrication control:
Limit frequency for the instrument to use the variable compressor lubrication process.
F67 - Maximum time for the variable compressor turned on the maximum frequency:
Maximum time for the variable compressor at maximum frequency. This parameter works in
conjunction with
[F55]
.
F68 - Low temperature limit (differential for the temperature setpoint):
Sets the low temperature limit to be used to turn off the variable compressor. In this parameter, the
differential for the setpoint is adjusted.
Example: Setpoint =
[,-6.0]
and
[F68]
=
[,,3.0]
. In this case, the temperature limit for turning off
the compressor will be
[,-9.0]
(
[,-6.0]
-
[,,3.0]
).
F69 - High temperature limit (differential for the temperature setpoint):
Sets the high temperature limit to activate the variable compressor at its maximum operating
frequency. The purpose of this parameter is to quickly lower the temperature of the controller
environment.
In this parameter, the differential for the setpoint is adjusted. The hysteresis of this parameter is fixed at
1.0°C (1.8°F).
Example: Setpoint =
[,-6.0]
and
[F69]
=
[,11.0]
In this case, the compressor will operate at maximum speed
[F55]
when the temperature is above
[,,5.0] [,-6.0] [,11.0]
and will return to operating at normal speed (between
[F54]
and
(
+
),
[F55]
when the temperature is below
[,,4.0] [,-6.0] [,11.0] [,,1.0]
(
+
-
)
F70 -
:
AUX output mode
[,,,0]
: Output off;
[,,,1]
: Lamp - Controls lighting;
[,,,2]
:
[,F71]
,
Alarm - Activates the output during the occurrence of the alarms of functions
[,F72]
,
[,F73]
and
[,F76]
;
[,,,3]
: Door resistance (without S3 sensor): The door heater remains on, regardless of the door
temperature. The resistor is switched off only during the occurrence of the alarms of functions
[,F71]
,
[,F72]
,
[,F73]
and
[,F76]
;
The buzzer is not activated during the occurrence of the alarms.
[,,,4]
:
[,F42]
=
[,,13]
:
Door resistance (with sensor S3, if
The door resistance to prevent
condensation is controlled by the temperature of the S3 sensor and the values configured in functions
[,F78]
and
[,F79]
.
[,F71]
,
The output is switched off in the event of alarms in functions
[,F72]
,
[,F73]
and
[,F76]
.The buzzer is not activated during the occurrence of the alarms.
F71 - Desired temperature differential (setpoint) for minimum room temperature alarm (sensor
S1):
It is the temperature difference in relation to the current setpoint to activate the low temperature alarm.
Example: Setpoint =
[,,3.0]
and
[,F71]
=
[,,2.0]
.In this case, the alarm will only be triggered if
the room temperature is less than
[,,1.0]
(
[,,3.0]
-
[,,2.0]
).
F72 - Desired temperature differential (setpoint) for maximum room temperature alarm (sensor
S1):
It is the temperature difference in relation to the current setpoint to activate the high temperature alarm.
Example: Setpoint =
[,,3.0]
and
[,F72]
=
[,10.0]
. In this case, the alarm will only be triggered if
the room temperature is greater than 130
[,130]
(
[,,3.0]
-
[,10.0]
).
F73 -
:
Length of time the door is open to trigger alarm
When the door is opened, the message
appears on the display and the door open timer
[OPEn]
starts. If this time is longer than the time configured in this function, the audible alarm (buzzer) will be
triggered and the message
will be displayed.
[AOPn]
F74 -Time for validating the alarm by temperature:
This function serves to inhibit the alarm for a period due to an eventual rise in temperature.
F75 - Alarm inhibition time on power-on:
During this time the alarm remains off while waiting for the system to go back to an operating mode.