6.3. Controller power supply
Use the pins according to table below, considering the set version:
6.4. Recommendations of IEC60364 standard
a)
Install overload protectors in the controller supply.
b)
Install transient suppressors – suppressor filter RC – in the circuit to increase the service life of the
controller relay. See connection instructions of the filter on the previous page.
c)
The sensor cables may be together, but not in the same conduit where the power supply of the
controller and/or of the loads passes through.
7. FASTENING PROCEDURE
a)
Cut out the panel plate (Image V - item 13) where the controller shall be fastened, with sizes
X = 71±0,5 mm and Y = 29±0,5 mm;
b)
Remove side locks (Image VI - item 13): to do that, compress the central elliptical part (with the Full
Gauge Controls logo) and displace the locks backwards;
c)
Introduce the controller in the notch made on the panel, inwards;
d)
Place the locks again and then displace them until they compress into the panel, fastening the
controller to the housing (see arrow indication in Image VI - item 13);
e)
Perform the electric installation as described in item 6;
f)
Adjust the parameters as described in item 8.
ATTENTION: for installations requiring liquid tight sealing, the notch sizes for the controller
installation should be no more than 70.5x29mm. The side locks should be fastened so that they
press the sealing rubber avoiding infiltration between the notch and the controller.
Protector vinyl - Image VII (item 13)
It protects the controller when installed at a site subject to water spills, such as refrigerated counters.
This adhesive vinyl is supplied with the instrument in the package.
IMPORTANT: Make the application only after completing the electrical connections.
a)
Retreat the side locks (Image VI - item 13);
b)
Remove the protective film from the adhesive vinyl face;
c)
Apply the vinyl over the entire upper part, bending the flaps, as indicated by the arrows - Image VII (item
13);
d)
Reinstall the locks.
NOTE:
The vinyl is transparent, allowing visualization of the wiring system of the instrument.
Pins
RT-607E plus
RT-607EL plus
9 and 10
9 and 11
115 Vac
230 Vac
12 Vac/dc
24 Vac/dc
8. OPERATIONS
8.1. Quick Access Menu Map
To access or browse the quick access menu use the
;
key (quick touch) while the controller is
displaying the temperature/time. With each touch the next function in the list is displayed. To confirm use
the
/
key (quick touch). See chapter 8.3 for more details. The map of functions is shown below:
8.3.2. Functions lock
The use of the functions lock brings greater security to the operation of the instrument. When it is active,
the setpoint and other parameters can be visible to the user, but are protected against undue changes
[,f15]
= 2 or you can block changes of control functions and leave the adjustment of the setpoint
enabled
[,f15]
=1. Using the
;
key (quick touch), access the function
[LOC,]
in the quick access
menu, confirm by pressing
/
(quick touch), then the message
[no,,]
will be displayed. After that
keep the
>
key pressed for the time configured for the functions lock
[,f16]
until
[LOC,]
is
displayed. The message
[On,,]
will be displayed indicating the function lock is activated upon
releasing the key.
RT-607
e
plus
To unlock, turn the controller off and then turn it on again with the
>
key pressed. Keep the key pressed
until
[LOC,]
is displayed. Keep the key pressed for 10 seconds and the message
[OFF,]
will be
displayed indicating the function lock is deactivated upon releasing the key.
8.3.3. Control functions shutdown
Turning the control functions off allows for the controller to operate just as an indicator of temperature,
keeping the control outputs and the alarms disconnected. Use of this feature is enabled or not by the
control functions shutdown function
[,f17]
. When enabled, the control and alarms functions are
turned off (
[CTRL][OFF,]
) or on (
[Ctrl][ON,,]
) through the quick access menu in the option
[Ctrl]
. When the control functions are off the message
[OFF,]
will then be displayed alternately
with the temperature and the other messages.
Except when
[,f17]
is equal to 3 or 4, in which case the display is switched off, keeping only the
.
icon on.
RT-607
e
plus
NOTE:
It is also possible to switch the control functions on/off by pressing the
;
key for five seconds.
NOTE:
When switching the control functions back on,
RT-607
e
plus
will continue to respect the
functions “
[,f06]
- Minimum thermostat output off time”.
8.3.4. Minimum and Maximum Temperature Record
Holding the
<
key down (quick touch) or also via the quick access menu, will cause the message
[rEg,]
to be displayed and the minimum and maximum temperatures to be recorded.
NOTE:
If the
<
key is pressed while the events are being displayed the values will be reset and the
message
[rsEt]
will be displayed.
NOTE:
If the temperature sensor is disabled the messages
[____]
and
[++++]
will be displayed.
8.3.5.View current date and time
Quickly pressing the
/
key makes possible to view the current date and time set in the controller.
However the display will show sequentially the current day (
[,--d]
), month (
[,--m]
), year
(
[,--y]
), weekday(
[day-]
), hour and minute (
[00:00]
) and if the preferred view set in
[,f09]
is
[Hour]
, the temperature is also displayed. It is also possible to view the date and time through the
quick access menu in the option
[ClO,]
.
8.3.6. Manual triggering of event output
Pressing the key
>
for 10 seconds activates an event manually. This will be deactivated after the time
set in the
[,f09]
function has elapsed. Pressing the key
>
again for 10 seconds deativavates the
manual operation. When activating the manual trigger, the
[Eon,]
message and the
[EOff]
message are displayed when you turn off the manual trigger. It is also possible to perform the activation
in the
[man,]
menu.
8.2. Quick access keys map
When controller is on temperature/time display mode, the following keys can be used as a shortcut for
the following functions:
Hold down for 2 seconds: setpoint adjustment (desired temperature).
/
<
Hold down for 10 seconds: manual activation of the event output.
Quick touch: enter the quick access menu.
;
/
Quick touch: the current day, month, year, day of the week, hour, and minute/
temperature will be shown in sequence on the display.
Quick touch: display of the maximum and minimum measurements recorded.
<
Hold down for 2 seconds: clear history when records are being displayed.
<
Hold down for 5 seconds: control functions shutdown.
;
Enters function selection.
<
<
8.3. Basic operations
8.3.1. Adjusting setpoint (desired temperature)
Hold the
/
key down for 2 seconds until the message
[SET,]
. is displayed. The adjusted control
temperature will be displayed when the key is released. Use the
<
or
>
key to change the value and
then press
/
to save. The desired temperature can also be changed in the quick access menu, (see
map on item 8.1).
;
FUNCTIONS LOCKDOWN
RT-607
e
plus
;
CONTROL FUNCTIONS
SHUTDOWN
RT-607
e
plus
;
ADJUSTING DESIRED
TEMPERATURE
(SETPOINT)
RT-607
e
plus
EXIT FUNCTION
;
RT-607
e
plus
FUNCTION SELECTION
;
RT-607
e
plus
RT-607
e
plus
SWITCH THE EVENT OUTPUT
ON/OFF (MANUAL MODE)
;
RT-607
e
plus
DATE AND TIME VIEW
;
;
SCHEDULE EVENT
PROGRAMMING
RT-607
e
plus
8.3.7. Date and time adjustment
Through the quick access menu, the
[CLO,]
option allows you to set controller date and time.
Use
<
or
>
to change the value and press
/
when ready to save the configured value. If the date
entered is invalid, the message
[ECLO]
will be shown on the display.
Example 1
(correct access code entered):
[,00d]
-
day
[,00M]
-
month
[,00Y]
-
year
[00:00]
time
minute
flashing
IMPORTANT:
The controller has an auxiliary internal power supply to keep the clock running for at least 72 hours in
case of a power cut. If the controller remains off for a long period of time, the message
[ECLO]
may be
displayed to indicate that the clock is not programmed. In this case, the date and time must be adjusted
and the controller must be kept on for 10 hours to fully recharge the auxiliary power supply.
NOTE:
To set the date and time through the menu outside the facilitated menu, it is necessary to enter
the access code
123
.
a) Press the key
;
(quick touch) simultaneously,
<
and
>
(quick touch), the
[Code]
option appears,
asking you to entered the access code.
b) Press
/
and enter the access code
123
using the
<
or
>
keys, confirming with the key
/
. The
[Code]
option will again appear.
c) Navigate through the menu using the
<
or
>
keys until
[Clo,]
appears, and then press
/
key.
If the controller's clock is not programmed (message
[ECLO]
) it is possible to adjust the time even
when the functions are locked (message
[LOC,]
). Under these conditions the clock adjustment is
enabled and the other functions remain locked. After the clock is adjusted the adjustment function is
locked again.