1. DESCRIPTION

The 

MT-444

Faston

  has  3  recipe  options,  each  with  its  control  temperature  and  their 

differentials (hysteresis), as well as specific keys for triggering / disabling and turn the lamp on / off. It 
also has a digital filter, which has the purpose of simulating an increase in mass in the ambient sensor 
(S1), delaying its response time (thermal inertia) and avoiding unnecessary compressor trips. It also 
includes an intelligent blocking of functions and a shutdown mode of the control functions.
Product conforming to UL Inc. (United States and Canada).
 

2. SAFETY RECOMMENDATIONS

- Check the controller for correct fastening;
- Make sure that the power supply is off and that it is not turned on during the controller installation;
- Read the present manual before installing and using the controller;
- Use adequate Personal Protective Equipamenet (PPE); 
- For application at sites subject to water spills, such as refrigerated counters, install the protecting vinyl 
supplied with the controller;
-  For  protection  under  more  critical  conditions,  we  recommend  the  Ecase  cover,  which  we  make 
available as an optional item (sold separately);
- The installation procedures should be performed by a qualified technician.

3. APPLICATIONS

        

• Beverage displays;        • Reach-in coolers;
• Refrigeration counters;
• Up right freezers.

4.TECHNICAL SPECIFICATIONS

evolution

 

 

V

er

.01

Setpoint Temperature

5. INDICATORS AND KEYS

Upper key

Lower  key

Set Key

Quick Access 
Menu Key (Flatec)

Refrigeration indicator LED

Defrost indicator LED

Temperature unit indicator LED

- 50 to 75°C (-58 to 167°F)

Power supply

MT-444E Faston: 

115 or 230Vac ±10%(*) (50/60 Hz)

MT-444EL Faston: 

12 or 24Vac/dc +10%(*)    

 

Operating Temperature

-10 to 50°C / 14 to 122°F

Operating humidity

10 to 90% RH (without condensation)

(*) Admissible variation in relation to the voltage rating.
(**) Maximum dimensions without connectors.

Maximum dimensions (**) (mm)

Cutouts dimensions (mm)

76 x 34 x 84 (WxHxD)

X = 71±0,5  Y = 29±0,5  (see Image V)

Maximum current per output

COMP:

 12(8)A / 240Vac 1HP

DEFR:

 3A / 240Vac 720W

FAN:

 5(3)A / 240Vac

LIGHT:

 5(3)A / 240Vac

Digital input

input for open-door detection (dry contact type)

6. WIRING DIAGRAM

The 

sensor S1

 (black) must be in the ambient.

The

 sensor S2

 (gray) must be placed in the evaporator 

through metallic cramp.

6.1. Temperature sensor connection

 

- Connect the 

sensor S1

 wires to terminals "1 and 2" and wires 

sensor S2

 to terminals "3 and 4": the 

polarity is not relevant.
- Length of the sensor cables can be increased by user himself to up to 200 meters, using a PP 2x24 
AWG cable.

6.2. Recommendations of IEC60364 standard

a) 

Install overload protectors in the controller supply.

b)

 Install transient suppressors – suppressor filter RC – in the circuit to increase the service life of the 

controller relay. See connection instructions of the filter on the previous page.

c) 

The sensor cables may be together, but not in the same conduit where the power supply of the 

controller and/or of the loads passes through.

Light indicator LED

Fan indicator LED

Power-saving mode indicator LED

MT-444

Controller power supply

Use the pins according to table below, considering the set version:

Pins

MT-444E Faston

MT-444EL Faston

9 and 10

9 and 11

115 Vac
230 Vac

12 Vac/dc
24 Vac/dc

DIGITAL REFRIGERATION 

CONTROLLER

Control 

functions 

shutdown

Functions 

lock

Serial 

Programming

Protection

level

On/off 

light

IP 65

FRONT

Power-saving 

mode

Connector 

for quick 
coupling

Buzzer

Approximate consumption

3.4 VA

NEW CONNECTION SYSTEM (QUICK COUPLING):

FASTON and PUSH-IN FAST

CONNECTION:

- Hold the wire near its end and insert it into the 
desired slot.
-  If  necessary,  press  the  bottom  to  assist  the 
connection.

DISCONNECT:

- To disconnect the cord, press the bottom and 
remove it.

NOTE:

-  In  the  connectors  1  to  6  the  maximum  wire 
diameter that can be used is 1,5mm².
- The wires must be tinned or use Rocket Pin 
terminals with a maximum diameter of 0,75mm².

BOTTOM

WIRE INPUT

The wire should be picked
in  5  mm  and  tinned.

Terminal Rocket Pin.

7. FIXING PROCEDURE 

a)

  Cutout  the  panel  plate  (Image  V  -  item  13)  where  the  controller  will  be  fixed,  with  dimensions              

X = 71±0,5 mm and Y = 29±0,5 mm;

b)

 Remove the side locks (Image VI - item 13): To do this, squeeze the elliptical central part (with the 

Logo Full Gauge Controls) and move the latches back;

c)

 Pass the wires through the cutout of the plate (image VII - Item 13) and make the electrical installation 

as described in item 6;

d)

 Insert the controller into the panel cutout, from the outside in;

e)

 Replace the latches and push then until they are pressed against the panel, securing  the controller to 

the housing (see arrow in Figure VI - item 13);

f)

 Adjust the parameters as described in item 9.

      WARNING:

 

for installations requiring liquid-tight sealing, the cut-off for the installation of the 

controller should be at must 70.5x29mm. The side latches must be secured so that they press 
the rubber sealing to prevent infiltration between the cutout and the controller.
Vinyl protector - Image IX (item 13)

Protects the controller should when installed in a place with splashing water, such as in refrigerated 
counters. This adhesive vinyl accompanies the instrument, on the packaging.

       IMPORTANT:

 

Apply only after completing electrical connections.

a)

 Retract the lateral locks (Image VI - item 13);

b)

 Remove the protective film from the adhesive side of the vinyl;

c)

 Apply the vinyl over the whole top, folding the flaps, as indicated by the arrows - Image IX (item 13);

d)

 Reinstall the latches.

NOTE:

 The vinyl is transparent, allowing to visualize the electric scheme of the instrument.

Image I - Connection 115 Vac

Image II - Connection 230 Vac

Image III - Connection 12 Vac/dc

Image IV - Connection 24 Vac/dc

3

4 5 6

7

8

9

10 11 12 13 14

DIG

DEFR

LIGHT

115 Vac

 S1

 S2

COMP

FAN

1

2

3

4 5 6

7

8

9

10 11 12 13 14

DIG

DEFR

LIGHT

230 Vac

 S1

 S2

COMP

FAN

1

2

3

4 5 6

7

8

9

10 11 12 13 14

12 Vac/dc

Power 
supply

DEFR

LIGHT

COMP

FAN

1

2

DIG

 S1

 S2

3

4 5 6

7

8

9

10 11 12 13 14

24 Vac/dc

Power 
supply

DEFR

LIGHT

COMP

FAN

1

2

DIG

 S1

 S2

MT444EF

AST

ONV01-03T

-16719

MT-444

Faston

MT-444

 

MT-444

 

E251415

Summary of Contents for Faston MT-444e

Page 1: ...upply of the controllerand oroftheloadspassesthrough Light indicator LED Fan indicator LED Power saving mode indicator LED MT 444e Controller power supply Usethepinsaccordingtotablebelow consideringth...

Page 2: ...keys to select the desired preset 1 2 or 3 and press to confirm Press for 2 sec rec This message will be displayed press to confirm 1 Preset Use or to select the preset 2 3 8 9 Maximum and Minimum Tem...

Page 3: ...he room sensor sensorS1 Localcalibrationoftheroomsensor sensorS1 Local calibration of the evaporator sensor sensor S2 0 Thefilteroperatesbothwhenthetemperaturerisesandwhenitfalls 1 The filter operates...

Page 4: ...ff 1 999 min 999 Off On Off 50 58 75 0 167 C F 75 0 167 50 58 75 0 167 C F 2 0 36 no 999 min 1 no 999 min 30 no 999 min 5 Fan OFF Time if F45 and F46 are in automaticmode Auto Fanoperationwhenopeningt...

Page 5: ...change of presetsisallowed 2 Allowsafulllockleavingonlytheaccesstothefunctionsofthequickaccessmenu available Note Toactivateordeactivatethefunctionslock pleaserefertoitem9 3 2 2 FunctionsLock f63 f64...

Page 6: ...me controller forexample Ithasthreetypesofconnectionstoloadorunloadtheparameters Serial RS 485 It connects via RS 485 network to the controller only forcontrollersthathaveRS 485 USB it can be connecte...

Page 7: ...the technical team of Full Gauge Controls Damage has been caused by a fall blow and or impact infiltration of water overload and or atmospheric discharge USE OF WARRANTY To make use of the warranty cu...

Reviews: