CONTROLLER FOR REFRIGERATION

 WITH REAL TIME DEFROSTING

 AND SERIAL OUTPUT

Ver.10

TC-900Ri clock

1. DESCRIPTION

TC-900Ri clock

 is a temperature controller for refrigerated products. It automates defrost processes 

according to the need of the installation, saving energy. It has two sensors, one for room temperature and 
another that, fixed to the evaporator, controls the end of defrost and fan return. In addition, it has an 
internal real time clock that enables creating an agenda with up to eight daily defrosts for each day of the 
week. The controller's internal battery guarantees its synchronism, even during power shortage, tor many 
years. It has an output for serial communication, and can be managed remotely through Sitrad ® via 
Internet. 
Product complies with  CE  (European Union), NSF  (

and  UL  Inc.  (United States and 

Canada).

2. APPLICATION

• Refrigeration chambers
• Counters

United States) 

3. TECHNICAL SPECIFICATIONS

- Power Supply: 

TC-900Ri clock -115/230 Vac ±10% (50/60 Hz)

                           TC-900RiL clock -12/24 Vac/dc

- Control temperature: 

-50 to 75°C / -58 to 167°F

- Resolution: 

0.1ºC from -10 to 75ºC and 1ºC outside this range / 1°F in all range

- Operating temperature: 

0 to 50 ºC / 32 to 122°F

- Operation humidity: 

10 to 90% RH (without condensation)

- Dimensions: 

71 x 28 x 71mm

- Load current (outputs):

REFR: 5(3)A / 250Vac 1/8HP (compressor, solenoid valve or contactor) 
FANS: 5(3)A / 250Vac1/8HP (evaporator fans) 
DEFR: 5(3)A / 250Vac (defrost  resistance or hot gas)

- Sensors:

S1: ambient sensor (black cable) 
S2: evaporator sensor (gray cable)

4. 

4.1 - Control temperature adjust (SETPOINT):

- Press          for 2 seconds until appears            , and release it after that. The adjusted temperature will 
appear. 
- Use         and         to change the value and then press           to record it.

CONFIGURATIONS

SET

SET

CLASSIFICATION ACCORDING TO IEC60730-2-9 STANDARD:

- Temperature limit of the installation surface: 

50º C

- Type of construction: 

Built-in electronic controller

- Automatic action: 

Type 1 

- Control of pollution: 

Level 2 

- Impulse voltage: 

1,5kV

- Temperature for the test of sphere pressure: 

75ºC and 125ºC

 

- Insulation: 

Class II

Fun

Defrost by programmed time (weekly schedule) 

Control differential (hysteresis)

Minimum setpoint allowed to the end user

Maximum setpoint allowed to the end user

Delay when the instrument is powered on

Act point of low ambient temperature alert (S1)

Act point of high ambient temperature alert (S1)

Refrigeration time (interval between defrosts)

Compressor delay after on (on - off)

Compressor delay after off (off - on)

Compressor status with detached ambient sensor (S1) 

Defrost when the instrument is powered on

Evaporator temperature (S2) for end defrost

Maximum defrost duration (for security)

Fan turned on during defrost 

4.2 - Parameters table

Description

Min

Max

Unit Standard

Min

Max

Unit Standard

CELSIUS

FAHRENHEIT

0 - no

0.1

-50

F03

0

-50.0

-50.0

1

0

0

0 - off

0 - no

-50.0

0=disable

0 - no

1 - yes

20.0

F04

75.0

30

75.0

75.0

999

999

999

1 - on

1 - yes

75.0

90

1 - yes

-

°c

°c

°c

min.

°c

°c

min.

sec.

sec.

-

-

°c

min.

-

0 - no

1

-58

F03

0

-58

-58

1

0

0

0 - off

0 - no

-58

0=disable

0 - no

1 - yes

36

F04

167

30

167

167

999

999

999

1 - on

1 - yes

167

90

1 - yes

-

°F

°F

°F

min.

°F

°F

min.

sec.

sec.

-

-

°F

min.

-

1 - yes

2.0

-50.0

75.0

0

-50.0

75.0

240

0

0

1 - on

0 - no

40.0

45

0 - no

1 - yes

4

-58

167

0

-58

167

240

0

0

1 - on

0 - no

104

45

0 - no

Defrost type  

Locked temperature indication (S1) during defrost 

Draining time (dripping of defrost water)

Evaporator temperature (S2) for fan return after draining

Maximum time of fan return after draining (fan-delay)

Fan on with compressor off (refrigeration)

Fan stopped for high temperature in the evaporator (S2)

Offset indication for ambient sensor (S1)

Network equipment address RS - 485 (serial communication)

0 - electric

0 - no

0

-50

0

0 - no

-50

-20.0

001

-

-

min.

°C

min.

-

°C

°C

-

1- hot gas 

1 - yes

30

75.0

30

1 - yes

75.0

20.0

247

0 - electric

0 - no

10

0.0

1

1 - yes

50.0

0.0

001

0 - electric

0 - no

10

32

1

1 - yes

122

0

001

0 - electric

0 - no

0

-58

0

0 - no

-58

-36

001

1- hot gas

1 - yes

30

167

30

1 - yes

167

36

247

-

-

min.

°F

min.

-

°F

°F

-

Exemple: To control the temperature in 4.0°C with differential of 1.0°C. Soon, the refrigeration will be 
turned off in 4.0°C and turned on again in 5.0°C (4.0+1.0)

F03 - Minimum setpoint allowed to the end user 

F04 - Maximum setpoint allowed to the end user

Electronic limits whose purpose is prevent that too high or too low setpoint temperatures are
regulated.

F05 - Delay when the instrument is powered on

When the instrument is powered on, its control is kept disabled during a time, delaying the start of 
process. During this time, it works only as temperature indicator. It serves to prevent demand of electric 
energy peaks, in case of lack or return of the same and when exists a lot of equipment connected on the 
same net. For this, just adjust different times for each equipment. This delay may be of compressor or 
defrost (when exist defrost on turn on).

F06 - Act point of low ambient temperature alert

F07 - Act point of high ambient temperature alert

If the ambient temperature (S1) reaches this point during the refrigeration, this will be visually signaled 
by the indication of a blinking light on the display.

F08 - Refrigeration time (interval between defrosts)

It is the time which compressor will turn on and turn off only for ambient temperature and starts to 
becounted when the fan is turned on , after fan-delay stage (fan return after draining).
Caution: The defrost will only begin if the temperature indicated in S2 (evaporator sensor) is less than 
indicated in F13.

F09 - Compressor delay after on (on-off)

It is the minimum time that compressor will keep on, it means, space of time between the last drive and 
the next stop. It serves to prevent high voltage events in the electric network. 

4.2.1 - Parameters description

F01 - Defrost by programmed time (weekly schedule)

This function allows that the defrosts scheduled by time are enabled.
"O" = The defrosts normally happen after the end of the refrigeration stage.
"1" = The defrosts are activated by the programmed time that is set in the weekly schedule.

F02 - Control differential (hysteresis)

It is the difference of temperature (hysteresis) between to turn OFF and turn ON the refrigeration output.

CLOCKV10-04T

-1

1000

COMPONENT

UL-Underwriters Laboratories