background image

Example 3: Depressurize, Start/Stop On

Setpoint: 50 psi
Hysteresis of digital outputs: 20 psi
Number of stages: 3
Hysteresis of analog output: 25 psi

5.7 Control Mode 6 - Analog and digital outputs with activation by 

capacities

In this operating mode the analog output works together with the digital outputs in such a way to meet the 
system demand in full. The activation point for each digital output is calculated in accordance with the 
output capacity and the number of stages configured. The activation will be made such that the digital 
stages meet most of the demand, thus leaving only the residual needs for the analog output. Due to the 
fact that this operating mode uses digital and analog outputs, the controller will assume the hysteresis that 
is equal to the sum of the following functions: "digital output hysteresis" and "analog output hysteresis."

When the operation mode is in depressurize, the controller works to decrease the read pressure until 
reaches setpoint value. If it is working in the pressurize mode, the controller works to increase the read 
pressure until reaches setpoint value. 
If the Start / Stop function is enabled, the first digital output starts to act as enabling control for a frequency 
inverter. At depressurize mode, if the read pressure is less than or equal to the setpoint, the OUT 1 output 
will be with the relay off, otherwise, if the read pressure is greater than the setpoint, the OUT 1 output will 
be with the relay on. 

As the demand will be the same percentage for pressurization or depressurization mode, the following 
example is for both cases.

Capacity of digital output 1 (OUT1): 10%
Capacity of digital output 2 (OUT2): 20%
Capacity of digital output 3 (OUT3): 30%
Capacity of digital output 4 (OUT4): 30%
Hysteresis of digital outputs: 10 psi
Capacity of analog output (ANALOG): 40%
Hysteresis of analog output: 10 psi
Setpoint: 40 psi

The activation levels will be as follows: (NOTE: the activation level of the analog output is proportional to 
the demand being supplied, for example: when the analog output is supplying 40% of the demand (full 
capacity), it will have the output at 100% (10 Vcc). When the analog output has to supply 20% of the 
demand (half capacity), it will have the output at50% (5 Vcc).

Note: When the user wants to use the Start / Stop output in control mode for capabilities with 

analog and digital outputs, the number of stages (F16) follows the following rule:

1 Stage: uses OUT1 output only (Start/Stop)

2 Stages: use OUT1 output (Start/Stop) and capacity of stage 2

3 Stages: use OUT1 output (Start/Stop), capacity of stage 2 and capacity of stage 3

4 Stages: use OUT1 output (Start/Stop), capacity of stage 2, capacity of stage 3 and capacity 

of stage 4

Example 1: Depressurize, Start/Stop Off (Setpoint: 40 psi)

Analog

output

Demand

Setpoint

OUT4

25%

0%

OUT3

50%

75%

OUT2

100%

OUT1

60%

10%

70%

20%

80%

30%

90%

40%

100%

50%

Time

Time

Time

Digital

outputs

Example 4: Pressurize, Start/Stop On

Hysteresis of digital outputs: 20 psi
Number of stages: 3
Hysteresis of analog output: 25 psi

 

Setpoint: 50 psi

Example 3: Depressurize, Start/Stop On

Setpoint: 40 psi                                        Analogic hysteresis = 10                                  
Digital hysteresis = 10                             Number of stages = 4
Stage capacity: OUT2=10, OUT3=20, OUT4=30 and Analog=40%

40 psi
41 psi
42 psi
43 psi
44 psi
45 psi
46 psi
47 psi
48 psi
49 psi
50 psi
51 psi
52 psi
53 psi
54 psi
55 psi
56 psi
57 psi
58 psi
59 psi
60 psi

40 psi
41 psi
42 psi
43 psi
44 psi
45 psi
46 psi
47 psi
48 psi
49 psi
50 psi
51 psi
52 psi
53 psi
54 psi
55 psi
56 psi
57 psi
58 psi
59 psi
60 psi

Pressure

Pressure

Demand

Demand

0 (%)
5 (%)

10 (%)
15 (%)
20 (%)
25 (%)
30 (%)
35 (%)
40 (%)
45 (%)
50 (%)
55 (%)
60 (%)
65 (%)
70 (%)
75 (%)
80 (%)
85 (%)
90 (%)
95 (%)

100 (%)

0 (%)
5 (%)

10 (%)
15 (%)
20 (%)
25 (%)
30 (%)
35 (%)
40 (%)
45 (%)
50 (%)
55 (%)
60 (%)
65 (%)
70 (%)
75 (%)
80 (%)
85 (%)
90 (%)
95 (%)

100 (%)

OUT1

OUT1 (10%)

ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON

OFF
OFF
OFF
OFF

ON
ON
ON

OFF

ON
ON
ON

OUT2 (10%)

OUT2 (20%)

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON

OFF
OFF

ON
ON
ON
ON
ON
ON
ON
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON

OFF
OFF
OFF
OFF

ON

OFF

ON
ON
ON

OUT3(20%)

OUT3 (30%)

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

OUT4(30%)

OUT4 (30%)

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON
ON
ON
ON
ON
ON
ON
ON

ANALOG

AN. (40%) 

0

12.5

25

37.5

50

62.5

75

87.5

100

12.5

0

12.5

0

12.5

25

37.5

50

62.5

75

87.5

100

0

12.5

25

37.5

50

62.5

75

87.5

100

0
0

12.5

0

12.5

0

12.5

0

12.5

0

12.5

25

The graph below illustrates either example 1 and example 2.

Example 2: Pressurize, Start/Stop Off (Setpoint: 60 psi)

60 psi
59 psi
58 psi
57 psi
56 psi
55 psi
54 psi
53 psi
52 psi
51 psi
50 psi
49 psi
48 psi
47 psi
46 psi
45 psi
44 psi
43 psi
42 psi
41 psi
40 psi

Pressure

Demand

0 (%)
5 (%)

10 (%)
15 (%)
20 (%)
25 (%)
30 (%)
35 (%)
40 (%)
45 (%)
50 (%)
55 (%)
60 (%)
65 (%)
70 (%)
75 (%)
80 (%)
85 (%)
90 (%)
95 (%)

100 (%)

OUT1 (10%)

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON

OFF
OFF
OFF
OFF

ON
ON
ON

OFF

ON
ON
ON

OUT2 (20%)

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON

OFF
OFF
OFF
OFF

ON

OFF

ON
ON
ON

OUT3 (30%)

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

OUT4 (30%)

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON
ON
ON
ON
ON
ON
ON
ON

AN. (40%) 

0

12.5

25

37.5

50

62.5

75

87.5

100

12.5

0

12.5

0

12.5

0

12.5

0

12.5

75

87.5

100

OUT1

OUT4

OUT3

OUT2

0%

80%

20%

40%

60%

100%

Measured
pressure

Measured
pressure

Analog

output

Digital 

outputs

Digital

Hyteresis

Digital

Hyteresis

Setpoint

+6 psi

+12psi

+18 psi

+18 psi

+12 psi

+6 psi

Setpoint

OUT1

OUT4

OUT3

OUT2

0%

80%

20%

40%

60%

100%

Measured
pressure

Measured
pressure

Analog

output

Digital 

outputs

Setpoint

-6 psi

-12psi

-18 psi

-18 psi

-12 psi

-6 psi

Setpoint

Digital

Hyteresis

Digital

Hyteresis

-45 psi

-45 psi

+45 psi

+45 psi

Summary of Contents for PCT-410Ri plus

Page 1: ...2 Capacityofthedigitalstage3 Capacityofthedigitalstage4 Capacityoftheanalogstage Digital outputs state when a sensor error is detected Analog output value when a sensor error is detected Minimum time...

Page 2: ...uish between one of the alarm situations or a transitory condition of the system Numberofstages Functionthatindicateswhichstageswillbeactivated Capacityofthedigitalstage1 This function sets the capaci...

Page 3: ...Setpoint 5 psi 10 psi 15 psi 20 psi 25 psi Measured pressure Analog output OUT1 Start Stop 5 psi 20 psi 15 psi 10 psi 5 psi 5 psi Setpoint Digital ouputs 25 0 50 75 100 Setpoint 5 psi 10 psi 15 psi Me...

Page 4: ...alog Hyteresis Digital Hyteresis Digital Hyteresis 5 psi 10 psi 15 psi 20 psi 25 psi 30 psi 35 psi 40 psi 45 psi 45 psi 40 psi 25 psi 0 psi 5 psi 10 psi 15 psi 20 psi 30 psi 35 psi Measured pressure M...

Page 5: ...T2 100 OUT1 60 10 70 20 80 30 90 40 100 50 Time Time Time Digital outputs Example 4 Pressurize Start Stop On Hysteresis of digital outputs 20 psi Number of stages 3 Hysteresis of analog output 25 psi...

Page 6: ...r will operate between with the access code 312 on the function and confirm with the key The indication will appear press or tochoosebetween dischargepressureswi Confirm the selection with the key and...

Page 7: ...nection of supresors to contactors Suppresor A1 A2 A1 and A2 are the contactor coil terminals Schematic for the connection of supresors to direct activation loads Load Suppresor For direct activation...

Reviews: