7.2  Parameter table

6.3.2 Function Lock

To unlock, turn off the controller and reconnect it with the key

>

 pressed. Keep the key pressed until 

the message 

[LOC,]

 appears, them release and 

[OFF,]

will appear on the display.

6.3.3 Control Functions Shutdown

6.3.4 

Registers of minimum and maximum measures

Pressing key 

<

 or also through the quick access menu (see chapter 6), the message 

[rEg,]

 will 

appear, followed by the minimum and maximum recorded temperatures.

For safety reasons, this controller provides the ability to lock functions. With this setting enabled, the 
setpoint and the other parameters are protected against undue changes however, they can be viewed. 
In this condition, when trying to change these values the message 

[LOC,]

 will appear on the display. 

To perform the lock function is necessary, first, that the parameter 

"

[,F42]

 

- Time lock function"

 is 

set to the value exceeding 14 (below the value 15, it is shown

[no,,]

is not allowing the blocking of 

functions). With the key

 

;

(short press), select     ,then press 

/

 (short press), after hold the key

>

 

until 

[LOC,]

(time in seconds programmed in 

[,F42]

). When you release the key the message

 

[On,,]

will appear on the display.

With the shutdown of the control functions the controller will operate only as a temperature and humidity 
indicator and the output relays stays off.
The  way  to  operate  the  control  functions  shutdown  depends  on  the  parameter  setting  “

[,F43]

Control functions shutdown

”:

[,,,0]

Does not allow the shutdown of the control functions.

[,,,1]

Allows to turn on and off the control functions only if the functions are unlocked.

[,,,2]

Allows  to  turn  on  and  off  the  control  functions  even  when  the  functions  are  locked

With key 

;

(quick touch), select 

[Ctrl]

, then press 

/

(quick touch) to confirm.

Then, the message 

[ctrl][Off,] 

will appear. At this time the temperature display will switch to 

the

 [OFF,]

 message.

To turn the control functions on again, just follow the same procedure as that for shutdown, selecting 
with the 

;

 key (quick touch). Once the user presses the 

/

 key the message 

[ctrl][On,,]

 will 

ap p e a r .

6.3.7 Unit Selection (ºC / ºF)

 “

[,F01]

 

[,231]

 

 

/

then the user can select the unit by pressing the keys 

<

and

>

where there are alternating messages 

[,=C,]

or

[,=F,]

. Press the key

/

to confirm the 

desired unit. Therefore, the corresponding indication unit 

{

or

}

 will be turned on.Every time the unit is 

changed, the parameters must be

 

reconfigured, since they assume the "standard" values.

In order to define the unit that the instrument will operate in, enter function

with the access 

code

and confirm with the

key. 

7. ADVANCED OPERATIONS

7.1 Changing the parameters of the controller

Access function 

[,F01] 

by

 

pressing keys 

<

and

>

 simultaneously or through the quick access 

menu. After that, 

[,F01]

 will appear, then, press the

/

 key (short press). Use keys 

<

or 

>

to enter 

with access code 

[,123]

 and, when ready, press 

/

. Use keys 

<

or

>

 to access the desired 

function. After selecting the function, press the key

/

 (short press), to visualize the set value for that 

function. Use keys 

<

or

>

 to change the value, and when ready, press

/

 to memorize the set value 

and  return  to  the  functions  menu.  To  exit  the  menu  and  return  to  normal  operation  (temperature 
indication) press

/

(long press) until 

[----]

appears on the display.

Obs:

 If the lock function is active, by pressing the 

<

or

>

 to change the value of the function, the 

controller will displays the message 

[LOC,]

 and will not allow to set the of parameter.

Description

Fun

Access code: 123 (one hundred and twenty-three)

T

hermostat operation mode (THERM output)

Minimum setpoint allowed to the end user  (thermostat)

Maximum setpoint allowed to the end user (thermostat)

Control differential (hysteresis) of the thermostat

Minimum delay to turn the thermostat output on

Humidistat operation mode (HUMID output)

Minimum setpoint allowed to the end user (humidistat)

Maximum setpoint allowed to the end user (humidistat)

Control differential (hysteresis) of the humidistat

Minimum delay to turn the humidistat output on

Humidity output (time on)

Humidity output (time off)

Auxiliary output operation mode (AUX)

Minimum setpoint allowed to the end user (AUX output)

CELSIUS

FAHRENHEIT

Min.

-99

0 - refrig.

-10.0

-10.0

0.1

no

0 - dehum.

0

0

0.1

no

0

0

0

0

Max.

999

1 - heat

70.0

70.0

20.0

999

1 - humid.

100

100

20.0

999

999

999

10

100

Unit

-

-

°C

°C

°C

seg.

-

%RH

%RH

%RH

sec.

sec.

sec.

-

-

Standard

-

0 - refrig.

-10.0

70.0

1.5

no

1 - humid.

0

100

5

no

5

5

5

0

Min.

-99

0 - refrig.

14

14

1

no

0 - dehum.

0

0

0.1

no

0

0

0

0

Max.

999

1 - heat

158

158

36

999

1 - humid.

100

100

20.0

999

999

999

10

100

Unit

-

-

°F

°F

°F

seg.

-

%RH

%RH

%RH

sec.

sec.

sec.

-

-

Standard

-

0 - refrig.

14

158

3

no

1 - humid.

0

100

5

no

5

5

5

0

[,F01]
[,F02]
[,F03]
[,F04]
[,F05]
[,F06]
[,F07]
[,F08]
[,F09]
[,F10]
[,F11]
[,F12]
[,F13]
[,F14]
[,F15]

6.3.5 

To visualize humidity or temperature

It is possible to view the other measure (humidity or temperature) by pressing 

>

.

6.3.6 Buzzer Inhibit 

When buzzer starts it  can be inhibited by pressing

 

>

 for two seconds or by quick access menu.

Indication:

- '' T'' temperature record

- '' H'' record humidity

To turn the current minimum and maximum values off, press key 

;

(short press) repeatedly, until the 

message

 [CrEg]

 is displayed, finally press the

 

/

 button to confirm. Another way is to press

<

seconds while displaying the records. This operation is indicated by the message 

[RSET]

.

1

5 6 7 8

2 3 4

9

POWER
SUPPLY

10 11 12 13 14 15 16 17

THERM

HUMID 

AUX 

A B

RS - 485

Connection

Vac/dc

 24 

1

5 6 7 8

2 3 4

9

POWER
SUPPLY

10 11 12 13 14 15 16 17

THERM

HUMID 

AUX 

A B

RS - 485

Loads supply

Connection 12 Vac/dc

1
2

3
4

Yellow
Orange/Brown

Green
Red

LEGEND

To the terminal     

 of the distribution box

To the terminal     

 of the distribution box

Maximum setpoint allowed to the end user (AUX output)

Control differential (hysteresis) of the AUX output

Minimum delay to turn the AUX output on

Time base of AUX output timer

AUX output (time on)

AUX output (time off)

Low room temperature alarm

High room temperature alarm

Low room humidity alarm

High room humidity alarm

Minimum delay to turn the AUX output on (alarm mode)

Buzzer operation mode

0

0.1

no

0

0

0

-10.0

-10.0

0

0

0

0

100

20.0

999

999

999

999

70.0

70.0

100

100

999

1

-

-

sec.

-

sec.

sec.

°C

°C

%RH

%RH

min.

-

100

5

no

0

5

5

-10.0

70.0

0

100

0

1

0

0.1

no

0

0

0

14

14

0

0

0

0

100

20.0

999

999

999

999

158

158

100

100

999

1

100

5

no

0

5

5

14

158

0

100

0

1

-

-

sec.

-

sec.

sec.

°F

°F

%RH

%RH

min.

-

[,F16]
[,F17]
[,F18]
[,F19]
[,F20]
[,F21]
[,F22]
[,F23]
[,F24]
[,F25]
[,F26]
[,F27]

12 Vac/dc

24 Vac/dc

Loads supply

MT-530

%uper

MT-530

%uper

MT-530

%uper

MT-530

%uper

MT-530

%uper