Full Gauge Controls MT-519Ri Manual Download Page 2

OUT1

(NA)

C1

OUT1

(NA)

OUT2

(NA)

C2

ALRM

(NF)

2 3 4 5 6 7 8

10 11 12

Above specified current use

a contactor.

1

Loads

supply

- Thermostat 2 output

C2

- Thermostat 1 output

C1

9

Sensor

1

Sensor

2

Power

supply

115 V

(12 V)

230 V
(24 V)

0

4 - 5
4 - 6

115V
230V

12V
24V

MT-519Ri

MT-519RiL

- Alarm output

[f17]

[f18]

[f19]

[f20]

[F22]

[f21]

[f22]

[OFF]

[,S,]

[,M,]

- Hysteresis of thermostat 2

- Minimum setpoint allowed to the user (thermostat 2)
- Maximum setpoint allowed to the user (thermostat 2)

- Minimum time of thermostat 2 output turned off

- Thermostat 2 delay when the instrument is powered on

- cyclic timer operation mode (thermostat 2)

- Cyclic timer disabled -

- Cyclic timer activated with time base in seconds
- Cyclic timer activated with time base in minutes

It is the difference of temperature(hysteresis) between turn ON and turn OFF the

output.

Electronic limits whose purpose is prevent that too high or too low setpoint temperatures are regulated.

It is the minimum time that the

output will keep turned off, it means, the space of time between

the last stop ant the next start. If

is configured as cyclic timer, this time will not be observed.

A delay that thermostat 2 will wait before activating its control functions. During this time only the
temperature is measured.

Allows configuring the cyclic timer associated to output

.

Output

will be constantly on or off depending only on

the temperature.

OUT2

OUT2

OUT2

OUT2

[,H,]

[F23]

[F24]

[F25]

[F26]

[F30]

[OFF]

[,1,]

[F27]

[F28]

[,2,]

[F27]

[F28]

[,3,]

[SP2] [F27]

[SP2] [F28]

[,4,]

[SP2] [F27]

[SP2] [F28]

- Cyclic timer activated with time base in hours

- cyclic timer - Time off (thermostat 2)
- cyclic timer - Time on (thermostat 2)

- Temperature sensor offset (thermostat 2)

- Alarm display mode (thermostat 2)

For configurations in s, m or h (seconds, minutes or hours) output

will keep cycling as

long as the temperature of the thermostat needs output

to be activated.

The initial state of

is always on.

This function allows adjusting any deviation in the reading of sensor 2 caused by an increase (splice) in
the sensor cable or occasional replacement.

Selects how the thermostat 2 checks for the presence of an alarm. The activation of this function only
enables the alarm display. If the alarm output must also be enabled, function

must be configured.

- Alarm off
- In-range alarm (

and

)

- Out-range alarm (

and

)

- In-range alarm relating to the setpoint (

-

and

+

)

- Out-range alarm relating to the setpoint (

-

and

+

)

OUT2

OUT2

OUT2

Functions

and

are used when

is configured as cyclic timer, observing the time

base configured in

.

[F22]

[F24]

[F22]

OUT2

[f27]

[f28]

[f26]

[f29]

[f21]

[f30]

[Off]

[,1,]

[,2,]

[,3,]

[,4,]

[f31]

[f32]

[,0,]

- Minimum value of the thermostat 2 alarm
- Maximum value of the thermostat 2 alarm

- Activation delay of thermostat 2 alarm

- Alarm output operation mode

- Alarm output cyclic timer - Time off
- Alarm output cyclic timer - Time on

These are the minimum and maximum values for the alarm to actuate if configured in

.

The time that the alarm of thermostat 2 will remain off even in alarm conditions. This time is counted after
the time configured in

has elapsed.

Selects how the alarm output is activated

- Alarm output off
- The alarm output is activated when there is an alarm for thermostat 1
-The alarm output is activated when there is an alarm for thermostat 2
- The alarm output is activated when there is an alarm for thermostat 1 or 2
- The alarm output is activated when there is an alarm for thermostat 1 and 2 at the same

time.

Selects the cycling time of the alarm output when it is active. If one of these functions is set to

, the

output will always be on.

[F33]

[t-1]

[t-2]

[all]

<

[F02]

[F16]

[OFF]

[F02] [F16]

[OFF]

<

[rst]

- Preferential display indication

Selects how the temperatures are shown in the display.

- Thermostat 1
- Thermostat 2
- Alternating thermostats 1 and 2

Press

, led

will turn on showing the minimum temperature recorded. Soon after, the maximum

temperature recorded for thermostat 1 will be displayed. Then led

will turn on and the respective

minimum and maximum temperatures recorded will be displayed. If any temperature is turned off
(

or

in

), the respective information will not be displayed. Caso alguma

temperatura estiver desligada (

ou

em

), as respectivas informações não serão

mostradas.
Note: To reset the registers, keep the key

pressed while the maximum and minimum temperatures

are displayed, until

appears.

5
5.1 -

-

FUNCTIONS WITH FACILITATED ACCESS

Register of minimum and maximum temperatures

T1

T2

5.2 Alarm inhibition

5.3 Viewing current

SIGNALING

-

-

temperatures

6 -

To disable the alarm, press

and

simultaneously. Only the output will be disabled. The

message will keep displaying. When disabled, the alarm will happen again after exiting the current alarm
condition and return to a new condition.

If function

is configured as

or

, the other temperature can be displayed, i.e. upon

pressing

and with function

configured as

temperature 2 will be displayed 2, and if

configured as

temperature 1 will be displayed.

The temporary indication lasts 15 seconds.

- Temperature displayed at sensor 1;
- Temperature displayed at sensor 2;

- Thermostat 1 output on;
- Thermostat 2 output on;

-Alarm output on;

- Sensor 1 temperature;
- Sensor 2 temperature;
- Sensor 1 detached or temperature out the range;
- Sensor 2 detached or temperature out the range;
- Thermostat 1 extra-range upper alarm ;

<

@

[F33]

[t-1] [t-2]

>

[F33]

[t-1]

[t-2]

[t-1]

[t-2]

[Er1]

[Er2]

[A1H]

T1

T2

OUT1

OUT2

ALRM

[A1L]

[A1n]

[A2H]

[A2L]

[A2n]

[rst]

[SOF]

[CyC]

[PPP]

.

[FAC]

[F01]

- Thermostat 1 extra-range lower alarm;
- Thermostat 1 intra-range alarm;
- Thermostat 2 extra-range upper alarm;
- Thermostat 2 extra-range lower alarm ;
- Thermostat 2 intra-range alarm;
- Indicates that the minimum and maximum values are being restarted;
- Indicates the device software version;
- Indicates that the chosen output is configured for “cyclic timer " mode.
- Invalid configuration parameters, in this situation the outputs will be turned off.

Check which parameter have invalid information and correct it to return to normal
operation.

The indic

soon after the current temperature unit

message will appear, and the instrument will return to the function

. Every

time that the unit is changed, the parameters should be reconfigured, since they assume the “standard”
values.

7 -

U

.

NIT SELECTION (ºC / ºF)

In o

After selecting

the unit the

rder to define the unit that the instrument will operate in, enter function

with the access code

231 and confirm with the

key.

ation

and

Press

or

to choose between

or

and confirm with the

key

[F01]

@

[UNi]

> <

[,=C] [,=F]

@

Note:

Sensor cable length can be increased by the user until 200 meters, using 4 x 0,20mm².

8 -

WIRING DIAGRAM

IMPORTANT

1:
2:

3:

According to the chapters of norm IEC 60364:

Install

on the power supply

Sensor cables and signal cables of the computer may be joined, but not in the same electric conduit

through which the electric input and the activation of the loads run

Install transient suppresors (RC filters) parallel to the loads as to increase the product life of the

relays.

protector against overvoltage

Schematic for the connection of supresors
to contactors

A1 and A2 are the
contactor coil terminals.

Schematic for the connection of supresors to
direct activation loads

Load

Suppresor

For direct activation the maximum
specified current should be taken
into consideration.

A1

A2

Supresor

ENVIRONMENTAL INFORMATION
Package:

Products:

Disposal:

The packages material are 100% recyclable. Just dispose it through specialized
recyclers.

The electro components of Full Gauge controllers can be recycled or reused if it is
disassembled for specialized companies.

Do not burn or throw in domestic garbage the controllers which have reached the end-of-
life. Observe the respectively law in your region concerning the environmental
responsible manner of dispose its devices. In case of any doubts, contact Full Gauge
controls for assistance.