Full Gauge Controls microsol II plus User Manual Download Page 2

Overheating temperature S1 to switch off the pump

Allows configuring the temperature for sensor 1 (panels) to turn the pump off to prevent damages in PVC 
piping by not allowing hot water to circulate. 

      

Overheating hysteresis to switch on the pump 

Overheating hysteresis to switch on the pump (S2)

Solar backing 1 operating mode

Temperature difference to turn the circulation pump on again. 
Example: F11= 80°C and F12= 10°C. The circulation pump will be turned off when sensor 1 reaches 
80°C. When the temperature drops and reaches 70°C, the circulation pump is turned on again (80 - 10 = 
70).

Overheating temperature S2 to switch off the pump

Required temperature for the swimming pool. It is the value at which the circulation pump will be turned off.

Temperature difference to heat the swimming pool again.
Example:
F13= 28.0 and F14=1.0. This way the swimming pool will be heated until reaching 28°C. After reaching this 
value the pump will be turned off. When the temperature drops to 27°C the swimming pool will be heated 
again (28 - 1 = 27).

The user can use this function to configure whether the auxiliary systems will be independent from each 
other. The modes are:

Solar backing 1 working independently of the support 2
Solar backing 1 deactivated when the solar backing 2 is activated

If programmed to 1, this function allows turning off the gas support system (connected to support 1) and 
turning on support 2 (electric heater) automatically. The support systems will never work together.

Solar backing 1 temperature setpoint

Temperature to turn off  the solar backing 1.

Solar backing 1 activation hysteresis

Temperature difference to turn on the solar backing 1. 
Exemple: F16= 30.0 and F17=1.0 
The solar backing turns on at 29º C and turns off at 30º C (30 - 1 = 29)
It should be noted that the first support system is linked to an event schedule (acts in accordance with 
user-defined times for up to four daily events). Therefore the times must be programmed for this support to 
work properly.

Minimum value for solar backing 1 temperature setpoint

Maximum value for solar backing 1 temperature setpoint

Functions F18 and F19 are only limits to configure F16 (setpoint temperature for support 1). They are used 
to block the setpoint if an out-of-range value is wrongly programmed.

Solar backing 1 manual activation time

If the user activates the solar backing 1 manually, 

MICROSOL II plus

 will count the time configured in 

this functions and then return to automatic mode.

Solar backing 2 operating mode

 The user can chose the operation mode for solar backing 2.

Cooling thermostat
Heating thermostat
Cooling thermostat linked to the event schedule
Heating thermostat linked to the event schedule
Cyclic timer with initial state "ON”
Cyclic timer with initial state “ON” linked to the event schedule

      

Cooling thermostat for heat dissipation to reduce any excess temperature in the water 
tank.
Heating thermostat of the water line
Heating thermostat of the water line linked to the event schedule

When the thermostat mode is selected for the water line heating, the supports are controlled by different 
sensors. Support 2 is controlled by sensor 3 while support 1 continues to be controlled by sensor 3. For 
this, sensor 3 must be enabled in F34. In the other thermostat functions, both supports are controlled by 
the same sensor. If sensor 3 is disabled (F34=OFF), both supports are controlled by sensor 2, or else 
they are controlled by sensor 3, if it is enabled.

Solar backing 2 temperature setpoint

Temperature desired for the pool (or thermal reservoir), as well as the function F13.

Solar backing 2 activation hysteresis

Temperature difference to turn on the solar backing 2 heating again.
Exemple: F22= 30.0 and F23=1.0 
The auxiliary system turns on at 29ºC and turns off at 30ºC (30 - 1 = 29)
This example is valid only if function F21 is configured to 1.

Maximum S1 temperature alarm

S1 temperature indication offset

S2 temperature indication offset

S3 temperature indication offset

Maximum solar panel temperature to activate the alarm.
This alarm is visual, shown in the display of 

MICROSOL II plus

 as the message          .

This  function  allows  adjusting  (or  correcting)  any  deviation  in  the  reading  of  sensor  1  caused  by  an 
increase (splice) in the sensor cable or occasional replacement, only if required.

This  function  allows  adjusting  (or  correcting)  any  deviation  in  the  reading  of  sensor  2  caused  by  an 
increase (splice) in the sensor cable or occasional replacement, only if required.

This  function  allows  adjusting  (or  correcting)  any  deviation  in  the  reading  of  sensor  3  caused  by  an 
increase (splice) in the sensor cable or occasional replacement, only if required.
To disable the temperature sensor for the solar backing systems (sensor 3), access this function in the 
advanced function menu. Then press the key        successively until the message           is displayed. 
Press          to confirm. After sensor 3 is disabled, solar backing 1 and 2 will be controlled by sensor 2 
(tank/swimming pool).
If the activation of the water pump is linked to sensor 3 and this sensor is disabled, the controller will 
automatically unlink them.

SET

           RS-485 network address

®

Equipment's network address for communicating with SITRAD  software.
Note: 

 

it is not allowed to have more than one device with the same address in a network.

           

             

Water pump activation mode

It allows to set the operation mode of the water circulation pump, the options are:

Water pump always OFF
Water pump always ON
Circulation pump operating in automatic mode and not linked to sensor 3. 

                    With this mode the pump is activated only by the temperature differential (S1-S2).

Circulation pump operating in automatic mode and linked to sensor 3. With this mode the 
pump is activated by the temperature differential and when the temperature at sensor 1 is 
higher

 

than that at sensor 3.

4.2.2 - Events schedule operating mode

In this option, you can choose how the events planner will operate.

Weekly programming

 - In this mode, the instrument can configure up to 4 events for every day of the 

week.

Programming for business days

 - In this mode, the instrument keeps the events the same for 

business days (Monday through Friday), and allows the programming of different events for Saturday 
and Sunday.

Daily programming 

- In this mode, the instrument keeps the events the same for all of the days of the 

week.

4.2.3 - Programming of the events schedule

In this option, you can enter the values for the time periods for each event. The entry of the data depends 
on the operating mode configured. You can configure up to four events for each day. For each event, the 
start and end time are configured through the options                      up to                      ,  where:

Start time for the first event
End time for the first event

Start time for the 4º event
End time for the 4º event

If you do not need to use the four events, you can configure it to be deactivated, and all you have to do is 
increase  the  off  time  (            for  example)  until  the            indication  appears.  It  is  also  possible  to 
configure an event to overlap that it begins in one day and it finishes in the other, and for that you should 
increase the off time until the option           appears and adjust an event for the next day to start at 00h 
and 00min. According to the operating mode configured, the following scheduling possibilities may be 
presented.

Sunday

Weekly schedule

Scheduling for business days

Daily schedule

Monday
Tuesday
Wednesday
Thursday
Friday
Saturday

Monday through Friday
Saturday

Sunday

Everyday

Start time for fourth event
End time for fourth event

Start time for first event
End time for first event

Events that are programmable

NOTE:

 Should the controller remain off for more than 24 hours, the message               will flash on the 

display, indicating that the clock is no longer programmed, a function of the discharge circuit internal. In 
this case, simply adjust the controller clock. If this happens, the controller should remain powered on for 
10 hours so that the 

 fully recharges.

internal circuit

4.2.4 - Adjustment of the current time and day of the week

Press the key        until the message            appears in the visor.
Hit key          . The settings will appear in the following order:
                                     

HOURS      MINUTES      DAY OF THE WEEK

 

Ex.: 12h43min - Friday

Hours
Minutes
Day of the week

SET

Cyclic timer off time

Event schedule linking mode

Functions F27 and F28 work when the user configures the solar backing 2 to filter the swimming pool. 
Then Microsol will cycle (on time and off time) the filter system. 
If function F21 is programmed to 4 or 5, the solar backing 2 will cycle in accordance with the times 
programmed in F27 (on time) and F28 (off time).

This function allows the user to configure whether the auxiliary system 2 must work in conjunction with 
auxiliary system 1 or not. 
If support 2 is programmed as linked to the schedule of support 1 (F21=2 or F21=3), this function will inform 
for which events (times) the support systems must be activated.

 

Minimum value for solar backing 2 temperature setpoint

Maximum value for solar backing 2 temperature setpoint

Functions F24 and F25 are only limits to configure F22 (setpoint temperature for solar backing 2). They are 
used to block the setpoint if an out-of-range value is wrongly programmed.

Solar backing 2 manual activation time

If the user activates the support 2 manually, 

MICROSOL II plus

 will count the time configured in this 

function and then return to automatic mode.

Cyclic timer on time

                     

 

 

     

   

 Aux 1 linked to events 1, 2, 3 and 4

        

Aux 1 linked to events 1 and 2

Aux 2 linked to events 1, 2, 3 and 4  

Aux 2 linked to events 3 and 4

Aux 1 linked to event 1                

Aux 1 linked to events 1, 2

 

and 3  

Aux 2 linked to events 2, 3 and 4

Aux 2 linked to event 4       

Minimum S1 temperature alarm

Minimum solar panel temperature to activate the alarm.

Summary of Contents for microsol II plus

Page 1: ...ctivation time Solar backing 2 operating mode Solar backing 2 temperature setpoint Solar backing 2 activation hysteresis Minimum value for solar backing 2 temperature setpoint Maximum value for solar backing 2 temperature setpoint Solar backing 2 manual activation time Cyclic timer on time Cyclic timer off time Event schedule linking mode Minimum S1 temperature alarm Maximum S1 temperature alarm S...

Page 2: ...he key successively until the message is displayed Press to confirm After sensor 3 is disabled solar backing 1 and 2 will be controlled by sensor 2 tank swimmingpool If the activation of the water pump is linked to sensor 3 and this sensor is disabled the controller will automaticallyunlinkthem SET RS 485networkaddress Equipment snetworkaddressforcommunicatingwithSITRAD software Note it is not all...

Page 3: ...between the temperature views for sensor 1 sensor 2 sensor 3 or temperature difference betweensensors1and2 differentialtemperature press tilthedesiredtemperatureisdisplayed Sensor1temperature Sensor2temperature Sensor3temperature Differentialtemperature S1 S2 Theselectedtemperaturewillbedisplayedfor15secondsandthenthedefaultindicationreturns asper parametersetting 6 2 Visualize the current time Qu...

Page 4: ...ng for setting of the instrument in panel 29 mm ENVIRONMENTALINFORMATION Package The packages material are 100 recyclable Just dispose it through specialized recyclers Products The electro components of Full Gauge controllers can be recycled or reused if it is disassembledforspecializedcompanies Disposal Do not burn or throw in domestic garbage the controllers which have reached the end of life Ob...

Reviews: