1.DESCRIPTION

The

 Microsol

 

BMP Advanced

 

 is a differential thermostat for solar heating with 

three sensors and two outputs, which operate in the water circulation pump control and in 
thermal support. It is equipped with a clock and an event schedule for economic and 
rational use of the thermal support, as well as the exclusive Vacation* function that adds 
protection and energy saving to the solar heating system in low hot water consumption 
periods. 
The controller has functions that avoid overheating and the freezing of the water in the 
solar collector. It's equipped with access protection to the parameters settings. 

The 

Microsol

 

Advanced

 

line  is  characterized  by  its  unique  design  for  use  in 

residential environments, by the easiness of operation with keys for easy access to the 
controller's main resources and by the use of the custom display. The display technology 
employed allows presenting in a complete and simple manner the solar heating system's 
information,  such  as:  output  status,  pump  operation  mode,  and  sensor  position  and 
temperature.

*required patent

2. APPLICATION

Solar heating with auxiliary heating system

3. TECHNICAL SPECIFICATIONS

- Power: 

Microsol

 

BMP Advanced

230Vac 

±

10%(50/60Hz) or version 115Vac 

±

10%(50/60Hz)

- Operation temperature: 

0 to 40ºC

- Operation humidity: 

10 to 90% UR (without condensation)

- Sensors:

 The 

Microsol

 

BMP Advanced 

 has 3 sensors:

                   

Sensor T1: 

Solar Collector – SB59 Sensor, metal tip, Silicone, 1m

Sensor T2: 

Thermal reservoir – SB41 Sensor, plastic tip, 2m

Sensor T3: 

Support – SB41 Sensor, plastic tip, 2m

- Control temperature: Sensor T1: 

-50 to 200ºC / -58 to 392ºF

Sensor T2: 

-50 to 105ºC / -58 to 221ºF

Sensor T3: 

-50 to 105ºC / -58 to 221ºF

- Resolution: 

0.1ºC between -10 and 100ºC and 1ºC in the remainder of the range
1ºF in all of the range

- Control output:

 The 

Microsol

 

BMP Advanced  

has two relay outputs:

PUMP

 - Relay output, max. 1HP in 220Vca (½ HP in 127 Vca) 

AUX

 - Relay output, max. 16A, resistance

3500W in 220Vca (1750W in 127 Vca)

- Dimensions: 

104 x 148 x 32 mm

- Display:

 LCD 2.75'' with backlight

5. OPERATIONS FOR DOMESTIC USER
5.1 KEY MAP

The controller has easy-access to user resources. Contains table with description of the following:

Short touch:  support heating temperature set

Long touch (4 seconds): access to advanced settings

Long touch (see F25 parameter): enables/disables function block 

Short touch: switches temperature display (DIF, T1, T2, T3) for 10 seconds

Short touch: switches pump mode (AUT / MAN)

Long touch (4 seconds): switch off pump (OFF mode)

Short touch: switches way support mode (AUT / MAN)

Long touch (4 seconds): enables/disables Vacation support mode (OFF)

Short touch: accesses hour and day settings menu 

L ong touch:  (4 seconds): accesses settings menu for event schedule

 SOLAR HEATING 

DIFFERENTIAL THERMOSTAT 

Ver. 02

SET

SET

BMP 

Advanced

 

4. INDICATIONS AND SCREEN
4.1 PRESENTATION

1
2
3
4
5
6
7
8
9

10
11
12

Pump mode key
Support mode key 
Clock key 
Lowering key
Set key 
Increasing key
Indication of the pump operation mode
Indication of the operation support mode
Controller signals
Representation of the solar heating system
Lower display numbers
Upper display numbers

4.2 INDICATIONS

SET

LOC

In programming, cleared parameter setting
In programming, blocked parameter setting
Fahrenheit scale temperature Indication
Celsius scale temperature Indication
Pump turned on due to cooling function
Pump turned on due to antifreeze function
Pump turned on due to vacuum tube function
Pump turned on due to temperature differential (T1-T2)
Pump outlet turned on

Support outlet turned on
Support outlet turned on due to function F21
T1 Sensor Position - solar collector
T2 Sensor Position - thermal reservoir
T3 Sensor Position - support
Indicates overheating occurrence T1
Indicates overheating occurrence T2
Indicates that the maximum differential (T1-T2) for protection against
thermal shock in the vacuum tube function has been exceeded.
Indicates sensor error occurrence T1
Indicates sensor error occurrence T2
Indicates sensor error occurrence T3
Function block setting
Before noon (standard clock 12pm)
After noon (standard clock 12pm)

5.2 SUPPORT HEATING TEMPERATURE (SENSOR T3)

Defines the support operation temperature (T3).
To set this parameter, give a short touch on key 

SET

 . Use keys     or     to set value. To 

confirm give a short touch on key 

SET

 and the value will be saved in the controller 

memory. This parameter can be

 

adjusted between the values defined in the advanced 

settings for the parameters:

[,F17]

- Minimum value for the support temperature and 

[,F18]

- Maximum value for support temperature.

Note:

 When the T3 sensor is deactivated in 

[,f24]

, the support is controlled by the T2 

sensor.

5.3 WATER PUMP OPERATION MODE

For  every  touch  on  key          the  water  pump  operation  mode  is  switched.  The  water 
circulation pump between the solar collector and the thermal reservoir can operate in three 
distinct modes. A description follows:
                                             
                                                        

                                                

Obs.:

 In the pump mode settings, the controller takes on the new mode 5 seconds after its 

selection. This also is the time necessary for the parameter to be stored in its memory.
When the MAN mode is selected (MANUAL), the operation mode remains in this state for the 
period defined in function 

[,F09]

 - Maximum pump time turned in manual mode. After, the 

controller takes on the AUT mode (AUTOMATIC). If you wish to return to AUT mode before this 
period, press the      key at any time.

PUMP

AUT

PUMP

MAN

PUMP

5.4 SUPPORT OPERATION MODE

On every short touch on the         key it is possible to change the support outlet operation 
mode between MAN and AUT modes.

AUX

AUT

AUX

MAN

SET

AUT = Support in automatic mode, operating
according  to  the  event  schedule  settings
T3 sensor temperature (parameter 

[temp]

). 

MAN = Support in manual mode, remains in this 
mode for the time defined in 

[,F19]

 - Time of

Manual support activation, after which it returns 
to AUT mode.

 OFF = Circulation pump always turned off

AUT = Circulation pump in automatic mode 
operating according to parameter settings

 MAN = Circulation pump turned on

am

pm

MAX

+

MAX

+

+

+

+

AUX

+

AUX

SET

1

2

3

6

5

4

MAX

AUX

am pm

SET LOC

AUX

AUT

off

MAN

AUT

off

MAN

PUMP

am pm

7

8

12

9

10

11

BMP

MCSOLADV

ANBMP01-01P- 14493

BMP

AUX

AUX

AUT

AUT

PUMP

MCSOLADV

ANBMP02-01T

-17097

Obs: 

the sum of the

 loads should not 

surpass 24A

Attention: 

In this mode the pump is maintained turned on , 

ignoring the protection functions and temperature sensors

.

MAX

+

+

off

Quick touch

Quick touch

4 seconds