Full Gauge Controls d-core Quick Start Manual Download Page 2

The controller temperature can be displayed either in Celsius (°C) degrees or Fahrenheit (°F) degrees. To
configure the unit, press keys 1 and 3 simultaneously for 2 seconds until

appears in the display, then

[SL]

release it. Select the

menu (press key 2 quickly) enter code

and confirm. The message

[Cd]

[31]

[UN]

will be displayed and then it is possible to switch between the two units mentioned.

5.8 Select temperature unit

Press key 1 for 4 seconds until the message

appears hen release it. The controller splays the

[LH]

, t

di

minimum and maximum temperatures of sensors S1 and S2 (if enabled in function

), as well as

[S4]

minimum and maximum voltages and the number of times the door has been opened.

Press key 2 for 4 seconds until the

message appears hen release it. The following information will be

[Se]

, t

shown:

To configure the selected

setpoint press key 2 for 8 seconds until the message

appears hen

preset

, t

[sp]

release it. The current setpoint value

displayed. Use keys 1 and 3 to adjust the desired value (setpoint).

is

Press key 2 to confirm.

To manually turn the lamp on or off, press the

key for 2 seconds until the [LI] mssage appears, then

[ECO]

release it. The lamp remains on by the time configured in

, while the power save mode is not active.

[P5]

Note

:

The lamp output must be configured as Light (

=

).

[A1] [1]

Voltage

Hundred

Unit

(ex: 120V)

release

key

release the

key

release the

key

Insert the

access

code 31

Note:

Each time the unit is changed the parameters

reset as they assume the “factory default’’ values.

are

Note

:

If by activating fast freezing mode the controller identifies that there is a defrost programmed to start

by time during this period, the defrost will be anticipated and then starts fast freezing mode.

In Fast Freezing mode, the control uses the temperature limit parameter for fast freezing (

,

,

,

o1 o2 o3

o4

) to accelerate the refrigeration or freezing process. Upon reaching this temperature or the maximum

fast freezing time (

) the fast freezing process is automatically deactivated.

o5

To start or stop Fast Freezing mode, press

until the

message appears,

[ff]

keys 2 and 3 for 2 seconds

then release it. The

message is displayed when it starts and

when it is interrupted.

[On]

[Of]

Note 1

: To reset the values, press key 1 for 1s during

the display of the information and the message

will

[rt]

be shown on the display.

Note 2

: If the sensor S2 or the voltage monitor are

disabled, the message

is displayed instead of the

[OF]

minimum and maximum values.

Note

: If the sensor S2 or the

voltage monitor are disabled, the message

[OF]

is displayed instead of the current value.

5.6 View current sensor temperature and voltage

5.10 Configure the setpoint

5.11 Turn the lamp on / off

5.7 Minimum and maximum temperatures, voltage and number of the

open door

5.9 Fast Freezing

Mains voltage

Display view

Cabinet Sensor (S1)

Minimum temperature (ex: 1.2ºC)

Maximum temperature

2.0ºC)

(ex:

Minimum temperature

1.2ºC)

(ex:

Hundred

Unit

(ex: 135)

Maximum temperature

2.0ºC)

(ex:

Door opening number

Minimum voltage
(ex: 112V)

Maximum voltage
(ex: 125V)

release the

key

release the

key

release the

key

release the

key

release the

key

release the

key

On

Off

On

Off

On

Off

It is possible to view controller settings without being able to edit them. To do this, press keys 1 and 3
simultaneously for 2 seconds until the message

appears, then release it. It is possible to view all

[SL]

controller settings. Navigate between menus using the 1 (increase) and 3 (decrease) keys. Confirm
selection with key 2.

6. ADVANCED OPERATIONS

6.1 Configured parameters display

P

, t

ress keys 1 and 3 simultaneously for 2 seconds until the message

appears hen release it. Select

[SL]

the

menu (short

key 2) enter code

and confirm.

to edit all controller settings.

[Cd]

[23]

touch

It is possible

Navigate between menus using the 1 (increase) and 3 (decrease) keys. Confirm selection with key 2.

6.2 Changing the configured parameters

Pressing key 2 for 4 secs. returns to the main screen.

Pressing key 2 for 4 secs. returns to the main screen.

Hold pressing for the time set in

.

[L5]

Using the function lock makes operating the instrument safer, with it active, the presets and other
parameters are visible to the user, but protected against undue changes (

=

). Or it can be set to

[L4] [2]

allow changes on the presets, and setpoint and locks all other parameters (

=

). When function lock

[L4] [1]

is activated and there is a try to change parameters, the message

is displayed.

[LC]

To enable the function

in param

This is the time to press

lock, configure the time for function lock

eter

.

[L5]

for validation of the function lock. To lock or unlock the keypad, press keys 2 and 4 for the time set in

[L5]

until the message

appe

, then release it. An

message will be displayed

oc

ars

when it is l ked and

[LC]

[On]

[Of]

when it is unlocked.

6.3 Function Lock

6. Turning the control functions off (Monitoring only)

4

When turning off the control functions (

), the controller will only operate as a temperature and voltage

[l6]

indicator with all outputs disabled. This function can operate as follows:

[,0]

Does not allow control functions to be turned off.

[,1]

Allow to turn control functions on and off only if the functions are unlocked.

[,2]

Allow to turn control functions on and off even if the functions are locked. To switch control functions

on/off, press key 3 for 8 seconds until message appears

hen release it:

[Ct]

, t

Note:

When reconnecting control functions, the controller continues to respect the functions

[C1]

(minimum compressor off time),

(Defrost when energizing controller) and

(Delay time when

[d8]

[C5]

powering the controller).

Confirm

Enter the

access

code 23

Confirm

Confirm

Confirm

Cabinet

1

Temperature (S )

If

=

or

[L1] [1]

[2]

Example: 4,5ºC

Evaporator Temperature (S2)

Example: 0.3ºC

Evaporator Sensor (S2)

press  or

f

4 seconds

press for

4 seconds

press  or

f

2 seconds

press  or

f

se

2

conds

press for

8 seconds

press  or

f

2 seconds

press  or

f

2 seconds

press  or

f

8 seconds

Summary of Contents for d-core

Page 1: ...que that reduces thefinaltemperatureoftheelectricalresistanceandtheamountofheatemitted Using its digital input door opening can be monitored and economic setpoint defrost or Fast Freezing can be activ...

Page 2: ...m temperature 2 0 C ex Minimum temperature 1 2 C ex Hundred Unit ex 135 Maximum temperature 2 0 C ex Door opening number Minimum voltage ex 112V Maximum voltage ex 125V release the key release the key...

Page 3: ...or S1 and the temperature of the evaporator sensor S2 reaches the value configured in this function the controller startsconfirmationtimecounttostartthedefrost d7 If the controller is configured to pe...

Page 4: ...shut down compressor and fan Defines the unit of time used in parameter P5 0 Seconds 1 Minutes 2 Hours With the door closed this parameter defines how long It ontributes to energy for light turn off c...

Page 5: ...current setpoint to activate the alarm buzzer forLOWroomtemperature Example Setpoint Inthiscase thealarmwillonlybe if 3 0 A2 2 0 active cabinet temperatureisbelow 1 0 3 0 2 0 Low temperature alarm di...

Page 6: ...Checktheconnectiononthecontroller Ifnecessary replacethesensor Reason Lowtemperatureoncabinetsensor S1 hecksensorS1connectionandfunctioning room Provisions C Checkrefrigerationsystem Checkfunction a2...

Page 7: ...rge WARRANTY USE In order to receive the warranty the customer must send the duly packaged product along with the corresponding purchase Tax Receipt to Full Gauge Controls The shipping charge of the p...

Reviews: